China 0.01S Class Standard 5000A 38.5KV CT PT Test Equipment System
China 0.01S Class Standard 5000A 38.5KV CT PT Test Equipment System

  1. China 0.01S Class Standard 5000A 38.5KV CT PT Test Equipment System

0.01S Class Standard 5000A 38.5KV CT PT Test Equipment System

  1. MOQ: 1
  2. Price: Negotiable
  3. Get Latest Price
Supply Ability 5 sets per month
Delivery Time 30-45 days
Packaging Details Wooden Package
Standard CT Class 0.01S, 0.05, 0.02, 0.01...optional
Standard PT 0.05 Class
Current Range 5-5000A, or more for option
Voltage range 6KV-38.5KV
CT, PT Burden accuracy 3%
Transformer tester 2%
Brand Name HNMC
Model Number HES-30
Place of Origin China

View Detail Information

Contact Now Ask for best deal
Get Latest Price Request a quote
  1. Product Details
  2. Company Details

Product Specification

Supply Ability 5 sets per month Delivery Time 30-45 days
Packaging Details Wooden Package Standard CT Class 0.01S, 0.05, 0.02, 0.01...optional
Standard PT 0.05 Class Current Range 5-5000A, or more for option
Voltage range 6KV-38.5KV CT, PT Burden accuracy 3%
Transformer tester 2% Brand Name HNMC
Model Number HES-30 Place of Origin China
High Light 38.5KV CT PT Test Equipment5000A CT PT Test Equipment0.01S CT PT Test Equipment

 

 

CT PT TEST Equipment System HES-30

 

Configuration

Standard CT, ±0.01S%
Standard PT (6kV-38.5kV), ±0.05%
CT Burden (5A, 1A), ±3%
PT Burden (100V, 100/√3V, 100/3V), ±3%
PT Burden (110V, 110/√3V, 110/3V), ±3%
Transformer Tester (Calibrator), ±2%
Current generator
Voltage Generator
Secondary Test Cables
PC Test Software
CT PT Test Control Bench

 

Technical Parameter

 

HES-30 CT/PT Test Control Bench

 

Input Voltage: AC 220V±10%, 50Hz, Single-Phase
Input Current: AC 0-120A
Rated Capacity: 30kVA
Output Voltage: AC 0-250V
Output Current: AC 0-120A
Output Voltage Adjustment: Provided the Coarse adjustment & Fine adjustment
Protection function: Provided over current & overvoltage protection
Output conversion functions: Connect to Current source / Voltage source conversion functions
The Bench Structure: Horizontal structure
Power Indicator: LED, Output current, Output voltage
Color of the Bench 7035 Gray

 

 

HES-1Bx Transformer Tester

Measure item: Ratio errors & Phase errors of the CT and PT
Rated current: 5A, 1A
Rated voltage: 100V, 110V, 115V, 120V, 150V, 200V, 220V, 230V
Multiplier: 1/√3, 1/3, 1, 1.5, 2
Accuracy class: ±2%
Operation range: (1%-120%).In, (20%-120%).Un
Frequency: 50Hz or 60Hz
Ratio error range: ±0.0001% ~ ±19.99% (3 ranges: 0.1999%, 1.999%, 19.99%).
Minimum resolution:0.0001%.
Phase error range: 0.01' ~ ±900' (3 ranges: 9.00', 90.0', 900')
Minimum resolution: 0.01'
Impedance range: 0.001Ω~ 19.99Ω.
Minimum resolution: 0.001Ω.
Admittance range: 0.001 ms ~ 19.99 ms.
Minimum resolution:0.001 ms.
Alarm Function: Provided the sound & light alarm function when the polarity abnormal or ratio inconsistent.

 

Input Load:

- On Standard CT secondary side: ≈0.11Ω, COSφ≈1.0

- On Test Object CT secondary side: ≈0.003Ω, COSφ≈1.0

- On Standard PT secondary side: ≈0.05VA (100V)

Communication Interface: Provided the RS232 serial PC communication interface
Display model: LCD
Power supply: AC 220V±10%, 60Hz
Power consumption: < 20VA
Product Type:

Portable type

 

CT Burden FY47-49

 

Rated Current: 5A, 1A

 

Power Factor

and Rated Burden:

In=5A:

COSФ=0.8: 2.5/3.75/5/6.25/7.5/10/12.5/15/20/25/30/40/50/60VA

COSФ=1.0: 2.5/3.75/5/6.25/7.5/10VA

(more option available)

In=1A:

COSФ=0.8: 2.5/3.75/5/6.25/7.5/10/12.5/15/20/25/30/40/50/60VA

COSФ=1.0: 2.5/3.75/5/6.25/7.5/10VA

(more option available)

Accuracy Class: ±3%
Operation Range: (1%-120%). In
Frequency: 50Hz or 60Hz
Withstand Voltage: 2kV/1min
Insulation: Air
Operating Model: Short-time (Used in CT Accuracy Testing System)
Product Type: Portable type.

 

High-current Test Cables of the CT

Cables includes: 3000A(600mm2) x 3m x 2pcs, 1000A(200mm2) x 5m x 1pc

500A(100mm2) x 3m x 2pcs, 250A(50mm2) x 3m x 2pcs

 

 

HLB-50G1 Standard CT

 

 

Rated Primary Current(A):

5, 7.5, 10, 12.5, 15, 20, 25, 30, 40, 50, 60, 75, 80, 100, 120, 125, 150, 160, 200, 250, 300, 315, 350, 400, 450, 500, 600, 630, 700, 750, 800, 900, 1000, 1200, 1250, 1400, 1500, 1600, 1800, 2000, 2500, 3000, 3150, 3500, 4000, 4500, 5000A

(more option available)

Rated Secondary Current: 5A, 1A
Rated Current Ratio: 5A~5000A/5A, 5A~5000A/1A (more option available)
Accuracy Class: 0.01S% (0.05%, 0.02%, 0.01% or better are available)
Rated Secondary Burden: 0.2Ω (Burden is 5VA at I2 = 5A, Burden is 0.2VA at I2 = 1A)
Power Factor: COSΦ=1.0
Operating Range: (1%-120%). In

 

Connection Mode:

Fixed connection terminals at Pri.current range is 5A-450A

Pass-through connection with 2 turns at Pri.current range is 500A-900A

Pass-through connection with 1 turn at Pri.current range is 1000A-5000A

Frequency: 50Hz or 60Hz
Voltage Level: AC 600V
Withstand Voltage: 2000V 1min
Insulating Medium: Air

 

 

SLQ-30KVA Current Generator

 

Input Voltage: AC 0-250V
Output Current: AC 0-5000A
Rated Capacity: 30kVA
Rated Input Current: AC 120A
Frequency: 50Hz or 60Hz
Current Output Model:

Fixed terminal at current is 50A, 200A, 500A

Through-hole connection at current is 500A-5000A

Products Shape: Stainless Steel Box
Working condition: 0 - 40ºC, RH ≤ 90%

 

 

FY95-1 PT Burden

Rated Voltage: 100V, 100/√3V, 100/3V
Power Factor: COSФ=0.8, COSФ=1.0
Rated Burden (VA):

1.25VA, 2.5VA, 5VA, 10VA, 20VA, 40VA, 50VA, 80VA, 100VA

(more option available)

Total Output Burden: 308.75VA (more option available)
Accuracy Class: ±3%
Operation Range: (20%-120%). Un
Frequency: 50Hz or 60Hz
Withstand Voltage: 2kV/1min
Insulation: Air
Operating Model: Short-time (Used in PT Accuracy Testing System)

 

 

HJB-35G3 Standard PT

Rated Primary Voltage: 6kV, 10kV, 15kV, 22kV, 35kV, 38.5kV
Rated Secondary Voltage: 100V,110V,100/√3V,110/√3V,100/3V,110/3V

 

 

Rated Voltage Ratio (kV):

6/0.1, 6/√3/0.1/√3, 6/√3/0.1/3, 6/0.11, 6/√3/0.11/√3, 6/√3/0.11/3

10/0.1, 10/√3/0.1/√3, 10/√3/0.1/3, 10/0.11, 10/√3/0.11/√3, 10/√3/0.11/3

15/0.1, 15/√3/0.1/√3, 15/√3/0.1/3, 15/0.11, 15/√3/0.11/√3, 15/√3/0.11/3

22/0.1, 22/√3/0.1/√3, 22/√3/0.1/3, 22/0.11, 22/√3/0.11/√3, 22/√3/0.11/3

35/0.1, 35/√3/0.1/√3, 35/√3/0.1/3, 35/0.11, 35/√3/0.11/√3, 35/√3/0.11/3

38.5/0.1, 38.5/√3/0.1/√3, 38.5/√3/0.1/3, 38.5/0.11, 38.5/√3/0.11/√3, 38.5/√3/0.11/3

Accuracy Class: 0.05% (100V,110V,100/√3V,110/√3V), 0.1% (100/3V,110/3V)
Rated Secondary Burden: 0.2VA(110V, 100V), 0.07VA(110/√3V, 100/√3V), 0.02VA(110/3V, 100/3V)
Power Factor: COSΦ=1.0
Operating Range: (20%-120%). Un
Frequency: 50Hz or 60Hz
Insulation: Epoxy resin casting

 

 

 

 

Company Details

Bronze Gleitlager

,

Bronze Sleeve Bushings

 and 

Graphite Plugged Bushings

 from Quality China Factory
  • Business Type:

    Manufacturer,Distributor/Wholesaler,Seller

  • Year Established:

    2009

  • Total Annual:

    100-500

  • Employee Number:

    8 ~10

  • Ecer Certification:

    Active Member

Zhengzhou Great Electric Co.,Ltd, established in 2011, is a fast growing company in Zhengzhou, Henan Province, in the same year, Henan Muchen Trading Co.,Ltd was founded as our export sales company, taking charge of all export deals. We specialize in production & supply of high-quality produc... Zhengzhou Great Electric Co.,Ltd, established in 2011, is a fast growing company in Zhengzhou, Henan Province, in the same year, Henan Muchen Trading Co.,Ltd was founded as our export sales company, taking charge of all export deals. We specialize in production & supply of high-quality produc...

+ Read More

Get in touch with us

  • Reach Us
  • Zhengzhou Great Electric Co.,Ltd.
  • No.1207-1, Building #1, the National University Sci-Tech Park of Henan Province, No.11 Changchun Road, Zhengzhou, Henan 450000
  • MrTony Han
  • 86-15237157117
  • https://www.powertest-equipment.com/

Leave a Message, we will call you back quickly!

Email

Check your email

Phone Number

Check your phone number

Requirement Details

Your message must be between 20-3,000 characters!

Submit Requirement