China Eaton MTL7764+ 2-Channel Zener Safety Barrier with Strain-Gauge Bridge
China Eaton MTL7764+ 2-Channel Zener Safety Barrier with Strain-Gauge Bridge

  1. China Eaton MTL7764+ 2-Channel Zener Safety Barrier with Strain-Gauge Bridge
  2. China Eaton MTL7764+ 2-Channel Zener Safety Barrier with Strain-Gauge Bridge
  3. China Eaton MTL7764+ 2-Channel Zener Safety Barrier with Strain-Gauge Bridge

Eaton MTL7764+ 2-Channel Zener Safety Barrier with Strain-Gauge Bridge

  1. MOQ: 1
  2. Price: Negotiable
  3. Get Latest Price
Payment Terms T/T,Western Union
Supply Ability 500pcs/month
Delivery Time In stock
Packaging Details original package
Condition MTL original brand new
Warranty one year
Application oil gas chemical industry
Shipping way DHL FedEx
Brand Name MTL
Model Number MTL7764+
Place of Origin England
Certification CE

View Detail Information

Inquiry by Email Get Latest Price
Chat online Now Ask for best deal
  1. Product Details
  2. Company Details

Product Specification

Payment Terms T/T,Western Union Supply Ability 500pcs/month
Delivery Time In stock Packaging Details original package
Condition MTL original brand new Warranty one year
Application oil gas chemical industry Shipping way DHL FedEx
Brand Name MTL Model Number MTL7764+
Place of Origin England Certification CE
High Light Eaton MTL7700 Zener BarrierDIN-rail mounting safety barrierMTL7764+ intrinsic safety barrier
MTL7764+ Eaton MTL Zener Safety Barrier
Product Overview

The MTL7764+ is a high-performance 2-channel shunt-diode safety barrier (Zener barrier) from Eaton's Crouse-Hinds series MTL7700 range, specifically engineered for strain-gauge bridge circuits, load cells, and Wheatstone bridge applications requiring intrinsic safety protection in hazardous areas.

This passive device limits the voltage and current that can reach a hazardous area under fault conditions, preventing ignition of flammable atmospheres. With a working voltage of 12 V, end-to-end resistance of 1,000 Ω, and positive polarity configuration, the MTL7764+ is the ideal solution for protecting sensitive strain-gauge based measurement equipment in Zone 0, 1, and 2 hazardous locations (gas groups IIC, IIB, IIA).

Key Features & Benefits
  • 2-Channel Efficiency: Two independent intrinsically safe channels in a single compact housing
  • Strain-Gauge Bridge Optimization: Specifically designed for strain-gauge bridge circuits and load cell applications
  • 12 V Working Voltage: Provides safe voltage limiting for strain-gauge bridge circuits
  • 1,000 Ω End-to-End Resistance: Matches impedance requirements of typical strain-gauge bridge circuits
  • Positive Polarity Configuration: Designed for positive ground applications
  • Ultra-Slim DIN Rail Mounting: Compact 12.6 mm width for standard 35 mm DIN rail installation
  • Removable Terminals: Unique removable terminal blocks for easy cabling and maintenance
  • Bussed Power Capability: Reduces cabling requirements with integrated bussed power distribution
  • High Accuracy Signal Transfer: Passive shunt-diode design ensures minimal signal distortion
  • Wide Operating Temperature: Functions reliably from -20°C to +60°C
Technical Specifications
General Specifications
ParameterValue
ManufacturerEaton (Crouse-Hinds series MTL)
SeriesMTL7700 Range
Product ModelMTL7764+
Alternative Part Number5710-032-006
Product TypeShunt-Diode Safety Barrier (Zener Barrier)
Number of Channels2 (dual-channel)
PolarityPositive (+)
Electrical Ratings
ParameterValue
Working Voltage (Vwkg)12 V
Safety Description12 V, 1,000 Ω, 12 mA
End-to-End Resistance1,000 Ω (±10%)
Maximum Current12 mA
Fuse Rating50 mA
Max. End-to-End Resistance1,050 Ω
Hazardous Area Specifications (Ex ia)
ParameterValue
Maximum Voltage (Vmax)10.9 V
Gas GroupsIIC, IIB, IIA
ZonesZone 0, 1, 2
Equipment Protection Level (EPL)Ga, Gb, Gc
Permitted Capacitance (Co)9 μF
Permitted Inductance (Lo)226 mH
Intrinsically Safe Circuit Power0.072 W
Intrinsically Safe Circuit Current24 mA
Non-Intrinsically Safe VoltageAC250V (50/60Hz), DC250V
Mechanical Specifications
ParameterValue
Width12.6 mm / 13 mm
Height90 mm / 88 mm
Depth105 mm / 107 mm
Weight100 g / 0.119 kg
Enclosure MaterialPolycarbonate
MountingDIN rail (35 mm)
TerminalsRemovable screw terminals
Environmental Specifications
ParameterValue
Minimum Operating Temperature-20°C
Maximum Operating Temperature+60°C
Storage Temperature-40°C to +80°C
Humidity95% max (non-condensing)
Degree of ProtectionIP20
Function Description

The MTL7764+ is a passive shunt-diode safety barrier that operates on the Zener barrier principle. It limits both voltage and current that can be delivered to a hazardous area circuit under fault conditions.

How it works:
  • Voltage limiting: Zener diodes clamp the output voltage to a safe level (12 V)
  • Current limiting: A series resistor (1,000 Ω) limits fault current to a safe value (12 mA)
  • Fusing: Internal 50 mA fuses provide backup protection under severe fault conditions
  • Grounding: The barrier requires a connection to a high-integrity earth ground
Safe Area (Control Side) → MTL7764+ → Hazardous Area (Field Side) Indicator/Excitation → (Voltage/Current limiting) → Strain-Gauge Bridge/Load Cell 12 V DC supply → (Zener diodes + 1kΩ resistor + 50mA fuse) [High-integrity earth ground required]
Applications

The MTL7764+ is specifically designed for strain-gauge and load cell applications in hazardous area installations:

IndustryApplication
Oil & GasTank level measurement using load cells on storage tanks
Chemical ProcessingVessel weighing systems, hopper scales, and silo level monitoring
PharmaceuticalBatch weighing systems for solvent handling equipment
MiningConveyor belt weighing systems, bin level monitoring
Food & BeverageTank weighing for flammable liquid storage
Marine & OffshoreCargo tank monitoring, mooring line tension measurement
Typical Field Devices Connected:
  • Strain-gauge bridge sensors (full Wheatstone bridge configuration)
  • Load cells (350 Ω to 800 Ω resistance)
  • Torque sensors
  • Pressure sensors based on strain-gauge technology
  • Weighing systems in hazardous areas
Certifications & Approvals
CertificationStatusDetails
CCC Ex (China)✅ CertifiedCertificate 2020322316002294 - Valid to 2030-09-01
ATEX✅ CertifiedBAS01 ATEX 7217 - II (1) GD [Ex ia] IIC
IECEx✅ CertifiedInternational certification for explosive atmospheres
NEPSI✅ CertifiedChina certification body approval
RoHS✅ CompliantLead-free
Installation Information
ParameterDetail
MountingStandard 35 mm DIN rail (EN 60715)
TerminalsRemovable screw terminals
GroundingRequires high-integrity earth ground connection
ClearanceMinimal - 12.6 mm width enables high-density installation
Operating PositionAny orientation
Important Installation Notes:
  • A high-integrity earth ground connection is mandatory for proper Zener barrier operation
  • Do not install in areas where condensation may occur
  • The barrier must be installed in a safe area (non-hazardous location)
  • Maximum cable parameters for IIC gas group apply to field wiring: Co = 9 μF, Lo = 226 mH

Company Details

Bronze Gleitlager

,

Bronze Sleeve Bushings

 and 

Graphite Plugged Bushings

 from Quality China Factory
  • Business Type:

    Distributor/Wholesaler,Exporter,Seller,Manufacturer,Trading Company

  • Year Established:

    2013

  • Total Annual:

    2000000-5000000

  • Employee Number:

    20~50

  • Ecer Certification:

    Verified Supplier

Shenzhen Hengyo Power Technology Co., Limited is your best partner for industrial automation. We provide ideal design and solution for automated industries with products from different international brands like MTL, PEPPERL+FUCHS, Phoenix Contact, Weidmueller, Honeywell, Max, Tamagawa, Delta, Panaso... Shenzhen Hengyo Power Technology Co., Limited is your best partner for industrial automation. We provide ideal design and solution for automated industries with products from different international brands like MTL, PEPPERL+FUCHS, Phoenix Contact, Weidmueller, Honeywell, Max, Tamagawa, Delta, Panaso...

+ Read More

Get in touch with us

  • Reach Us
  • Shenzhen Hengyo Power Technology Co., Limited
  • Room 2407, B Block No.145 Chengshi Zhuchang Bld, Bagua 2nd Rd, Futian Dist. Shenzhen City, China 518029
  • https://www.ac-servomotors.com/

Leave a Message, we will call you back quickly!

Email

Check your email

Phone Number

Check your phone number

Requirement Details

Your message must be between 20-3,000 characters!

Submit Requirement