| Payment Terms | L/C, D/A, D/P, T/T, Western Union, MoneyGram | 
| Supply Ability | 10000 units/year | 
| Delivery Time | 45 days | 
| Packaging Details | Wooden Carton | 
| Frequency | 50Hz | 
| Special Conditions | Depends on The Customer | 
| System Voltage | 132KV 145Kv | 
| Capacity | 16000KVA | 
| Sound level | ≤65 dB | 
| Protection accuracy | 5P20 | 
| Brand Name | Tianan Electric | 
| Model Number | CZBT1-132 | 
| Certification | IEC | 
| Place of Origin | CHINA | 
View Detail Information
Explore similar products
132KV Mobile Transformer Substation / Distribution Movable Power Substation
132 Kv Vehicle Mounted Transformer Substation / Prefabricated Mobile Substation
Prefabricated 132KV Semi-trailer Vehicle-mounted Mobile Substation
132kv Prefabricated Mobile Vehicle Mounted semi-trailer Transformer Substation
Product Specification
| Payment Terms | L/C, D/A, D/P, T/T, Western Union, MoneyGram | Supply Ability | 10000 units/year | 
| Delivery Time | 45 days | Packaging Details | Wooden Carton | 
| Frequency | 50Hz | Special Conditions | Depends on The Customer | 
| System Voltage | 132KV 145Kv | Capacity | 16000KVA | 
| Sound level | ≤65 dB | Protection accuracy | 5P20 | 
| Brand Name | Tianan Electric | Model Number | CZBT1-132 | 
| Certification | IEC | Place of Origin | CHINA | 
| High Light | Transformer Mobile Compact Substation ,IEC Mobile Compact Substation ,IEC Power Transformer Substation | ||
Promotional Various Durable Using Power Transformer Mobile Compact Substation
* Carefully Selected Materials
  The shell is made of stainless steel, aluminum alloy, cold-rolled plate, color steel plate, tiled, wooden strip, etc., and has good insulation, sealing and excellent heat resistance.
* With Major Brands
  Effective control and protection system, fast installation and operation, superior performance.
* High Quality
  The internal wiring is neatly arranged, the loss is low, and the heat dissipation performance is strong, which can be used in different environments.
* Long Service Life Of Equipment
  The use of automated equipment to ensure accurate product size, production and production in strict accordance with international standards, maintenance-free during the period, the quality is more guaranteed.
Service condition
1 Ambient condition
a. Altitude ≤ 1000m;
b. Ambient temperature
Range of temperature: -25℃~+40℃;
c. Wind speed (outdoor) ≤ 35m/s;
d. Relative humidity ≤ 90%(+25℃);
e. Installation spot
The place shall have no fire, explosion, chemical corrosion and exquisite vibration.
2 Move condition of the substation
a. Max. speed ≤ 30km/h,when road surface is flat;
b. Max. speed ≤ 10km/h, when road surface is not flat.
Note: If the above condition can’t satisfy requirements, customer can consult with manufacturer to resolve it.
Table1
| No. | Item | Unit | Parameter | 
| 1 | System voltage | kV | 132 | 
| 2 | Rated voltage | kV | 145 | 
| 3 | Rated frequency | Hz | 50 | 
| 4 | Rated current | A | 2000 ,1600 | 
| 5 | Rated 1min power frequency withstand voltage | kV | 275 | 
| 6 | Rated lightning impulse withstand voltage | kV | 650 | 
| 7 | Rated short time withstand current | KA | 25,31.5,40 | 
| 8 | Rated short time withstand time | s | 3 | 
| 9 | Rated peak withstand current | kA | 63,80,100 | 
| No. | Item | Unit | Parameter | ||
| 1 | System voltage | kV | 132 | ||
| 2 | Rated voltage | kV | 145 | ||
| 3 | Rated frequency | Hz | 50 | ||
| 4 | Rated current | A | 2000 | ||
| 5 | Rated 1min power frequency withstand voltage | kV | 275 | ||
| 6 | Rated lightning impulse withstand voltage | kV | 650 | ||
| 7 | Rated short time withstand current / time | KA/s | 40/4 | ||
| 8 | Rated peak withstand current | kA | 100 | ||
| 9 | Rated short circuit breaking current | kA | 40 | ||
| 10 | Rated short circuit making current | kA | 100 | ||
| 11 | DC component | % | 40 | ||
| 12 | Rated operation sequence | O 0.3s CO 180s CO | |||
| 13 | Opening time | ms | 35±5 | ||
| 14 | Closing time | ms | 105±15 | ||
| 15 | Breaking time | ms | ≤60 | ||
| 16 | Non-simultaneity between poles | Closing | ms | ≤5 | |
| Opening | ms | ≤3 | |||
| 17 | Fracture no. of each pole | 1 | |||
| 18 | Mechanical endurance | Times | ≥6000 | ||
| 19 | Full capacity continuous breaking times | Times | ≥20 | ||
| 20 |   			 SF6 gas pressure (20℃)  |   			Rated value | MPa | 0.60 | |
| Alarm value | MPa | 0.55 | |||
| Locking value | MPa | 0.50 | |||
| 21 |   			 SF6 gas moisture content(μl/l)  |   			Acceptance value | PPm | ≤150 | |
| Operation allowable value | PPm | ≤300 | |||
| 22 | SF6 yearly gas leakage rate | % | ≤0.5 | ||
| 23 | Total weight of each circuit breaker | kg | 2000 | ||
Table3 table4 Parameters of current transformer
| Rated primary current | 150,300,500,750,1000,1500,2000 | 
| Rated secondary current | 5A | 
|   			 Rated output capacity and accuracy level 
  |   			See table 4 | 
| Current ratio | Rated output capacity VA | Measure accuracy level | Protection accuracy level | 
|   			 150/5 300/5 500/5 750/5 1000/5 1500/5 2000/5  |   			  			 20 20 30 30,40 40,50 50 50  |   			  			 0.5 0.5 0.5 0.5 0.5 0.5 0.5  |   			  			 5P20 5P20 5P20 5P20 5P20 5P20 5P20  |   		
Note: (1) Straight-through type bushing current transformer is attached in the circuit breaker.
Table5 Parameters of lightning arrester
| No. | Item | Unit | Parameter | 
| 1 | System voltage | kV | 132 | 
| 2 | Rated voltage | kV | 150 | 
| 3 | Rated frequency | Hz | 50 | 
| 4 | Nominal discharge current | kA | 10 | 
| 5 | DC 1mA reference voltage | kV | ≥245 | 
| 6 | Residual voltage under lightning impulse current (peak) | kV | ≤435 | 
| 7 | Residual voltage under operation impulse current (peak) | kV | ≤370 | 
| 22 | Residual voltage under steep wave impulse current (peak) | kV | ≤490 | 
Table 6 Parameters of neutral point lightning arrester
| No. | Item | Unit | Parameter | 
| 1 | System voltage | kV | 132 | 
| 2 | Rated voltage | kV | 90 | 
| 3 | Rated frequency | Hz | 50 | 
| 4 | Nominal discharge current | kA | 1.5 | 
| 5 | DC 1mA reference voltage | kV | ≥140 | 
| 6 | Residual voltage under lightning impulse current (peak) | kV | ≤260 | 
| 7 | Residual voltage under operation impulse current (peak) | kV | ≤240 | 
| 8 | Residual voltage under steep wave impulse current (peak) | kV | / | 
Table7 Technical parameters of switch equipment on LV side
| No. | Item | Unit | Parameter | 
| 1 | System voltage | kV | 11.5 | 
| 2 | Rated voltage | kV | 12 | 
| 3 | Rated frequency | Hz | 50 | 
| 4 | Rated current | A | 2000,1600,1250, | 
| 5 | Rated 1min power frequency withstand voltage | kV | 42/48 | 
| 6 | Rated lightning impulse withstand voltage | kV | 75/85 | 
| 7 | Rated short time withstand current | kA | 40,31.5,25 | 
| 8 | Rated short time withstand time | s | 4 | 
| 9 | Rated peak withstand current | kA | 100,80,63 | 
| 10 | Rated short circuit breaking current | kA | 40,31.5,25 | 
| 11 | Rated short circuit making current | kA | 100,80,63 | 
| 12 | Rated operation sequence | O 0.3s CO 180s CO | |
| 13 | Mechanical endurance | Times | ≥10000 | 
![]()
Company Details
Business Type:
Manufacturer,Exporter,Trading Company,Seller 
Year Established:
1969 
Total Annual:
250000000-300000000
Employee Number:
3000~3500 
Ecer Certification:
Verified Supplier 
Ningbo Tianan (Group) Co, Ltd is a famous leading influential enterprise of the power transmission equipment manufacturing in China.It was founded in 1969,currently under the group, we have 1 national-level R&D center, 2 provincial-level R&D center, 10 professional companies, 70 sales office... Ningbo Tianan (Group) Co, Ltd is a famous leading influential enterprise of the power transmission equipment manufacturing in China.It was founded in 1969,currently under the group, we have 1 national-level R&D center, 2 provincial-level R&D center, 10 professional companies, 70 sales office...
Get in touch with us
Leave a Message, we will call you back quickly!