Ecer asks for your consent to use your personal data to:
Personalised advertising and content, advertising and content measurement, audience research and services development
Store and/or access information on a device
Your personal data will be processed and information from your device (cookies, unique identifiers, and other device data) may be stored by, accessed by and shared with 135 TCF vendor(s) and 65 ad partner(s), or used specifically by this site or app.
Some vendors may process your personal data on the basis of legitimate interest, which you can object to by do not consent. Contact our platform customer service, you can also withdraw your consent.
{"title":"Non-Contact Eddy Current Sensor PR6423\/00R-101 CON031 API 670 Compliant and","imgUrl":"https:\/\/img.chinax.com\/nimg\/4d\/0d\/036cbc894814387bb076c3cc2bac-200x200-1\/non_contact_eddy_current_sensor_pr6423_2f00r_101_con031_api_670_compliant_and_explosive_area_rated.jpg","attrs":{"Shipping":"TNT, DHL, FedEx, EMS, UPS","MOQ":"1 Piece","Packaging":"Original New Packaging","Country Of Origin":"USA"}}
Eight-channel field-powered current input termination
02 · CURRENT INPUT PATH
Field-powered analog acquisition
The 1C31116G02 personality module conditions eight field-powered current inputs for the Ovation 13-bit analog input subsystem. It works with electronic module 1C31113G05 and provides per-channel 250 Ω signal networks.
8 CHANNELS
0–20 mA SELECTABLE 4–20 mA
250 Ω CHANNEL NETWORK
DETAILED PARAMETERS
Electrical and System Identity
INPUT MODE Field-powered current
CHANNEL COUNT 8 analog inputs
CURRENT RANGE 0–20 / 4–20 mA
CONVERSION FAMILY 13-bit subsystem
Electronic module pairing
1C31113G05
Channel signal network
250 Ω resistor and capacitor network
Shield treatment
Dedicated shield terminals with grounding jumpers
Default grounding
Local grounding with vertical jumpers installed
SIGNAL RELATIONSHIP
From Transmitter to Ovation Point
◉
Field transmitter
Externally powered current loop
▥
1C31116G02
250 Ω conditioning and shield termination
⌘
1C31113G05
Electronic conversion for Ovation
USE AND INSTALLATION
Deployment Essentials
⌖ Use scope
Eight field-powered current transmitters in an Ovation 13-bit analog input subsystem.
⚙ Function
Converts each loop current into a voltage across its 250 Ω network for the paired electronic module.
↧ Wiring
Land positive, negative and shield conductors at the assigned channel terminals; preserve pair polarity and shielding.
✓ Grounding
Use installed vertical jumpers for local shield grounding or remove them when the approved field-grounding scheme requires it.
FAMILY COMPARISON
Choose by Signal and Power Method
VOLTAGE INPUT
1C31116G01
Voltage ranges with the matching electronic-module variant.
FIELD-POWERED
1C31116G02
0–20 mA or configured 4–20 mA field-powered loops.
LOCALLY POWERED
1C31116G03
Current loops supplied from the local auxiliary bus.
THERMOCOUPLE
1C31116G04
Compensated thermocouple input arrangement.
AMIKON · SINCE 2005
Keep critical control hardware moving
Support for difficult automation part numbers, planned maintenance and urgent replacement needs across global industrial operations.
sales@amikon.cn
WhatsApp: 86-18020776792
BUYER FAQ
Loop-Design Questions Worth Resolving
❖ Q Why does Westinghouse 1C31116G02 use 250 Ω on each channel?
◉ A The resistor network converts loop current into the voltage level processed by the paired analog electronic module.
◆ Q Can Westinghouse 1C31116G02 power a two-wire transmitter?
◉ A G02 is the field-powered loop variant, so the transmitter uses an external field supply. Use G03 for the locally powered arrangement.
◇ Q Can Westinghouse 1C31116G02 accept 4–20 mA although its range is 0–20 mA?
◉ A Yes. The Ovation I/O configuration can select 4–20 mA and apply the appropriate channel setup.
✦ Q How should shield grounding be chosen for Westinghouse 1C31116G02?
◉ A Vertical jumpers installed provide local grounding. Remove them only where the approved loop design calls for field grounding.
❖ Q Is Westinghouse 1C31116G02 a direct substitute for 1C31116G03?
◉ A No. G02 is for field-powered current loops, while G03 uses the local auxiliary supply. Their wiring and power architecture differ.