| Operating temperature range | (0~49)℃ |
| Melting point temperature | 170℃±10℃ |
| Nominal working pressure | 5.7Mpa |
| Delivery Time | 15-20days |
| Payment Terms | T/T,L/C |
| Supply Ability | 30000set/month |
| Maximum tube length | 25m |
| Maximum loading factor | 0.6kg/L |
| Packaging Details | Wooden Box Or Plywood Outer Box With Bubble Bag Or Paper |
| Certification | GSG\TUV\GB6653-2008 |
| Model Number | WZ-Q/T-QZ3-XJ60 |
| Place of Origin | Guangzhou,China |
| Brand Name | XINGJIN |
View Detail Information
Explore similar products
3Kg Fm200 Fire Extinguisher Tube With GB25972-2010 Standard
42kg Co2 Fire Extinguishing Devices Fire Detection Tube Of Indirect Type: 0-49℃,
Co2 Direct Type Fire Extinguisher Tube 12.1Mpa Max Working Pressure
Automatic Carbon Dioxide Fire Extinguisher
Product Specification
| Operating temperature range | (0~49)℃ | Melting point temperature | 170℃±10℃ |
| Nominal working pressure | 5.7Mpa | Delivery Time | 15-20days |
| Payment Terms | T/T,L/C | Supply Ability | 30000set/month |
| Maximum tube length | 25m | Maximum loading factor | 0.6kg/L |
| Packaging Details | Wooden Box Or Plywood Outer Box With Bubble Bag Or Paper | Certification | GSG\TUV\GB6653-2008 |
| Model Number | WZ-Q/T-QZ3-XJ60 | Place of Origin | Guangzhou,China |
| Brand Name | XINGJIN | ||
| High Light | CO2 gas fire suppression system ,industrial fire suppression system ,high pressure CO2 release nozzle | ||
The CO2 fire detection tube system is an innovative fixed non-electric self-actuating fire suppression device that combines fire detection and extinguishing functions into a single flexible tube. Unlike traditional gas systems, it requires no power supply, no complex detectors, no control panels, and no intricate piping networks – making it ideal for protecting enclosed electrical cabinets, control panels, and compact equipment spaces where conventional systems cannot be installed.
The fire detection tube is made of specialized polymer material with an outer diameter of 6mm, inner diameter of 4mm, and wall thickness of 1.0mm±0.1mm. When a fire occurs, the tube bursts at the point of highest temperature (170±10°C), releasing pressure and activating the container valve. The extinguishing agent is then discharged directly through the burst opening (direct type) or through dedicated nozzles (indirect type), delivering targeted fire suppression within seconds.![]()
Direct Type vs Indirect Type Configuration Comparison:
| Parameter | Direct Type | Indirect Type |
|---|---|---|
| Protected Volume | ≤10m³ | ≤100m³ |
| Agent Charge Weight | 6kg | 45kg |
| Min. Agent Required per Unit | 2.5kg/m³ | 1.5kg/m³ |
| Max. Detection Tube Length | 25m | 25m |
| Max. Release Tube Length | — | 12m |
Key Technical Specifications:
Working Pressure: 5.7MPa; Max Working Pressure: 12.1MPa
Max Filling Rate: 0.6kg/L
Operating Temperature Range: 0~49°C![]()
Company Details
Business Type:
Manufacturer,Exporter
Year Established:
2010
Total Annual:
600000-1200000
Employee Number:
100~300
Ecer Certification:
Verified Supplier
About Us: Guangzhou Xingjin Fire Equipment Co., Ltd. is a professional enterprise dedicated to the research, development and production of HFC-227ea (FM200), Novec1230, CO2 and inert gas products. For many years, the company has been committed to improving product quality, enriching pro... About Us: Guangzhou Xingjin Fire Equipment Co., Ltd. is a professional enterprise dedicated to the research, development and production of HFC-227ea (FM200), Novec1230, CO2 and inert gas products. For many years, the company has been committed to improving product quality, enriching pro...
Get in touch with us
Leave a Message, we will call you back quickly!