Payment Terms | T/T |
Supply Ability | 100+pc+on stock |
Delivery Time | on request |
Packaging Details | carton |
Color | White and blue |
material | plastic and metal |
Shipping Weight | 1.0Kg |
Dimensions ( D x W x H ) | 1.58 cm x 10.98 cm x 12.36 cm |
Number of channels | One |
Voltage applied to sensor | 7 to 9V dc from 1kO ±10% |
Product No | MTL5511 |
Estimated Lead Time | Usually ships in 1-7 working days. |
Brand Name | MTL |
Model Number | MTL5511 |
Certification | ROHS |
Place of Origin | UK |
View Detail Information
Explore similar products
MTL5531 MTL Instruments Proximity Detector Interface Blue
MTL4544 MTL Instrument Repeater Power Supply
MTL SLP32D Surge Protection Device Maximum Rated Load Current 1.50A
5531 Vibration Transducer Interface MTL Instruments 20 To 35VDc
Product Specification
Payment Terms | T/T | Supply Ability | 100+pc+on stock |
Delivery Time | on request | Packaging Details | carton |
Color | White and blue | material | plastic and metal |
Shipping Weight | 1.0Kg | Dimensions ( D x W x H ) | 1.58 cm x 10.98 cm x 12.36 cm |
Number of channels | One | Voltage applied to sensor | 7 to 9V dc from 1kO ±10% |
Product No | MTL5511 | Estimated Lead Time | Usually ships in 1-7 working days. |
Brand Name | MTL | Model Number | MTL5511 |
Certification | ROHS | Place of Origin | UK |
High Light | MTL5511 MTL Safety Barrier ,9V MTL Safety Barrier ,MTL safety barrier instrument |
MTL5511 MTL Instruments Switch/Proximity Detector Interface
The MTLx511 enables a safe-area load to be controlled by a switch or proximity detector located in a hazardous-area
Hazardous-area inputs : Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
Hazardous-area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for
proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1kΩ ±10%
Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200µA (650Ω) nominal
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. A line fault is
indicated by an LED. The channel output relay is de-energised if an
input line fault is detected.
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100Ω
Short-circuit alarm off if Rin > 360Ω
Note: Resistors must be fitted when using the LFD facility with a contact input
500Ω to 1kΩ in series with switch
20kΩ to 25kΩ in parallel with switch
Safe-area output
Single pole relay with changeover contacts
Note: reactive loads must be adequately suppressed
Company Introduction
Great System In.(GSI) a name synonymous with Process Control Instrumentation and Electrical and Instrument and Solution Provider have established themselves as a Quality Leader since its inception in 1998 based at Hong Kong ( China ).
Company Details
Business Type:
Distributor/Wholesaler
Year Established:
1998
Total Annual:
7000000-10000000
Employee Number:
50~100
Ecer Certification:
Verified Supplier
Great System In.(GSI) a name synonymous with Process Control Instrumentation and Electrical and Instrument and Solution Provider have established themselves as a Quality Leader since its inception in 1998 based at Hong Kong ( China ). For more than 26 years, we have successfully execute... Great System In.(GSI) a name synonymous with Process Control Instrumentation and Electrical and Instrument and Solution Provider have established themselves as a Quality Leader since its inception in 1998 based at Hong Kong ( China ). For more than 26 years, we have successfully execute...
Get in touch with us
Leave a Message, we will call you back quickly!