| Payment Terms | L/C,D/P,T/T,Western Union |
| Supply Ability | >300sets/month |
| Delivery Time | 1-7working days(depand on raw materials stocking) |
| Packaging Details | export standard wooden case |
| Water Quality | Resistivity ≥15-18.25 MΩ·cm |
| Flow Rate | 60m³/H (Customizable) |
| Operation Mode | Fully Automatic |
| Core Process | Double-pass Reverse Osmosis + EDI + Polishing Resin |
| Key Components | UF filter ,RO Membrane Modules, EDI Units |
| Electricity Supply | 380V/220V |
| After-Sales Service | 2-Year Warranty |
| Product Features | Stable Water Quality,Low Operation Cost,Reliable Performance |
| Brand Name | HongJie |
| Certification | ISO 14001,ISO 9001,CE,EPA |
| Place of Origin | Shenzhen,China |
| Model Number |
View Detail Information
Explore similar products
1000LPH Ultrapure Water System with PLC Control and Stainless Steel
Ultrapure Water Purification Equipment With Advanced RO & EDI Technology
RO + EDI Ultrapure Water System With Precision Welding & Polishing Process
1 Ton Stainless Steel RO System For Ultrapure Laboratory Water Treatment
Product Specification
| Payment Terms | L/C,D/P,T/T,Western Union | Supply Ability | >300sets/month |
| Delivery Time | 1-7working days(depand on raw materials stocking) | Packaging Details | export standard wooden case |
| Water Quality | Resistivity ≥15-18.25 MΩ·cm | Flow Rate | 60m³/H (Customizable) |
| Operation Mode | Fully Automatic | Core Process | Double-pass Reverse Osmosis + EDI + Polishing Resin |
| Key Components | UF filter ,RO Membrane Modules, EDI Units | Electricity Supply | 380V/220V |
| After-Sales Service | 2-Year Warranty | Product Features | Stable Water Quality,Low Operation Cost,Reliable Performance |
| Brand Name | HongJie | Certification | ISO 14001,ISO 9001,CE,EPA |
| Place of Origin | Shenzhen,China | Model Number | |
| High Light | Industrial Water Purification System 60m3/H ,PLC Controller Industrial Water Purification System ,60m3/H industrial water treatment systems | ||
I.Overview
PLC (Programmable Logic Controller) serves as the control hub and intelligent decision-making core in ultra-pure water (UPW) systems. Through real-time data acquisition, multi-variable coordinated control, and fault diagnosis, it ensures water quality consistently meets the semiconductor-grade standard of 18.2 MΩ·cm. In ultra-pure water systems, PLCs have evolved from basic automation to intelligent decision-making hubs. In advanced processes below 3nm, their control precision (e.g., TOC ±0.05 ppb) directly determines chip yield rates.
II.Process
Raw Water → Raw Water Tank → Booster Pump → Flocculant/Reducer Dosing → Activated Carbon Filter → Ultrafiltration (UF) → Scale Inhibitor Dosing → Security Filter → 1st Stage High-Pressure Pump → 1st Stage RO → pH Adjustment → Intermediate Tank → 2nd Stage High-Pressure Pump → 2nd Stage RO → Purified Water Tank → EDI Booster Pump → UV Sterilizer → Cartridge Filter → EDI System → Ultra-Pure Water Tank → Transfer Pump → TOC Removal Unit → Polishing Resin → Final Filter → Point of Use
III.Core application scenarios of PLC
| Full - process Technology Automation | ||||||
| Process Segment | PLC Control Function | |||||
| Pretreatment | Sequential control of backwashing of sand - carbon filter (triggered by both pressure difference/time), precise dosing of dosing pump (scale inhibitor/NaClO) | |||||
| RO Membrane System | Frequency control of high - pressure pump (maintaining constant product water flux), adjustment of concentrate valve opening (recovery rate 75% - 85%) | |||||
| EDI Module | Adaptive adjustment of DC voltage (0 - 600V), switching of limiting current mode (preventing polarization) | |||||
| Mixed - bed Polishing | Judgment of resin failure (resistivity drop > 0.5 MΩ·cm), fully automatic cycle of acid - base regeneration (flow/concentration closed - loop) | |||||
| Closed - loop Control of Water Quality Parameters | ||||||
| Parameter | Control Strategy | |||||
| Resistivity | PID algorithm dynamically adjusts the inlet flow of mixed - bed (set value 18.18 MΩ·cm, response time < 5s) | |||||
| TOC | UV - ozone unit interlock control (increase ozone concentration by 10% - 30% when TOC> 0.3 ppb) | |||||
| Dissolved Oxygen (DO) | Vacuum degree adjustment of membrane degassing system (target DO < 3 ppb) | |||||
| System Safety Interlock Protection | ||||||
| Risk Type | PLC Response Mechanism | |||||
| High Pressure of RO Membrane | Emergency shutdown of pump + opening of pressure relief valve when pressure > 1.5 MPa | |||||
| UPW Microbial Contamination | Trigger ozone shock disinfection (0.1 ppm×2h) when bacteria > 0.01 CFU/mL | |||||
| Water Tank Liquid Level | Lack - of - liquid - level interlock to stop pump (prevent idling), close inlet valve at high liquid level (prevent overflow) | |||||
IV.Here is a guideline for you to get a proper quotation
Tell us the raw water/source of water(tap water, well water, or sea water, etc)
Provide water analysis report(TDS , conductivity, or resistivity, etc)
Required production capacity( 5m³/H, 50m³/H,or 500m³/H, etc)
What's the pure water used for( industrial,Food and Beverage,or agriculture, etc )
Company Details
Business Type:
Manufacturer
Year Established:
2013
Total Annual:
25000000-30000000
Employee Number:
50~100
Ecer Certification:
Verified Supplier
... ...
Get in touch with us
Leave a Message, we will call you back quickly!