Payment Terms | T/T |
Supply Ability | 100 pc 1 week |
Delivery Time | 7-14 days |
Signal Output | 4-20mA 0-20mA 1-5V 0-5V |
Pressure Sensing Element | Piezoresistive |
Ingress Protection | IP67 |
Mounting | Direct or remote |
Operating Temperature | -40°C to 85°C |
Mounting Method | DIN rail or wall mount |
Long Term Stability | ±0.2% of URL for 5 years |
Weight | 0.5 kg |
Flange Material | 316SST |
Turndown Ratio | 100:1 |
Measuring Principle | Absolute and gauge pressure |
Certifications | CE, RoHS, ATEX |
Wetted Materials | 316L stainless steel |
Protocol | HART/RS485 |
Brand Name | Yokogawa |
Model Number | EJX530A |
Place of Origin | China |
View Detail Information
Explore similar products
Automated Products EJA110E Pressure Transmitter For High Temperature Application
EJA110E Accurate Differential Pressure Transmitter Eja110e-Dms4j-912db
Customizable EJA510E/EJA530E 0-50Mpa Differential Pressure Transmitter for
Customizable EJA510E/EJA530E 0-50Mpa Yokogawa Pressure Transmitter / Differentia
Product Specification
Payment Terms | T/T | Supply Ability | 100 pc 1 week |
Delivery Time | 7-14 days | Signal Output | 4-20mA 0-20mA 1-5V 0-5V |
Pressure Sensing Element | Piezoresistive | Ingress Protection | IP67 |
Mounting | Direct or remote | Operating Temperature | -40°C to 85°C |
Mounting Method | DIN rail or wall mount | Long Term Stability | ±0.2% of URL for 5 years |
Weight | 0.5 kg | Flange Material | 316SST |
Turndown Ratio | 100:1 | Measuring Principle | Absolute and gauge pressure |
Certifications | CE, RoHS, ATEX | Wetted Materials | 316L stainless steel |
Protocol | HART/RS485 | Brand Name | Yokogawa |
Model Number | EJX530A | Place of Origin | China |
The EJX530A is a high-performance in-line gauge pressure transmitter in Yokogawa’s premium EJX-A (DPharp) series. It’s used to measure the pressure of liquids, gases, or steam and produce a proportional 4–20 mA output (linear or square-root) with superimposed digital communications (BRAIN or HART). FOUNDATION Fieldbus and PROFIBUS PA versions are also available.
Choose the EJX530A when your application requires gauge pressure (pressure referenced to atmosphere). If you need absolute pressure, the companion model is EJX510A.
Reference accuracy: Up to ±0.04% of span (Span A) with scaled accuracy rules for higher ranges (see table below).
Long-term stability: ±0.1% of URL for 15 years under normal operating conditions.
Fast response: 90 ms (all capsules) when damping set to zero.
Capsule | Calibrated Span | Range Limits | Approx. Upper Range Limit (URL) |
---|---|---|---|
A | 8–200 kPa | −100 to 200 kPa | 200 kPa |
B | 0.02–2 MPa | −0.1 to 2 MPa | 2 MPa |
C | 0.1–10 MPa | −0.1 to 10 MPa | 10 MPa |
D | 0.5–50 MPa | −0.1 to 50 MPa | 50 MPa |
(Conversions: 200 kPa ≈ 29 psi; 2 MPa ≈ 290 psi; 10 MPa ≈ 1450 psi; 50 MPa ≈ 7200 psi.)
Signal: 2-wire 4–20 mA DC with superimposed BRAIN or HART FSK; linear or square-root selectable.
Integral LCD indicator (option) displays pressure, % span, scaled engineering units, bargraph.
Local Parameter Setting (LPS): Configure tag, units, LRV/URV, damping, output mode, and perform local re-range using the push button/zero screw—useful for fast commissioning without a communicator.
Optional advanced diagnostics can detect impulse line blockage and heat trace failure, and can drive an analog alert status when enabled.
Standard EJX series units (except Fieldbus/PROFIBUS types) are certified to SIL 2 for safety applications; consult the Functional Safety Manual for integration into safety instrumented functions. Distributors note third-party TÜV/Exida certifications are available in certain configurations—verify per your project safety requirements.
Ambient: −40 to +85 °C; with LCD display −30 to +80 °C.
Process temperature: −40 to +120 °C (may be further limited by approvals/options).
Working pressure: Up to capsule URL (to 50 MPa for D capsule). See over-pressure and approval tables when applying in hazardous areas.
Wetted parts selections include 316L SST process connections and Hastelloy C-276 diaphragms among others (specified via suffix codes).
Housing options: low-copper cast aluminum (standard), corrosion-resistant coated variants, or ASTM CF-8M stainless steel (optional).
Enclosure ratings: IP66/IP67, Type 4X.
Multiple global approvals are available (ordered by option codes), including ATEX Flameproof / Intrinsically Safe, IECEx Flameproof / IS, FM/CSA Explosionproof, and combinations packages (e.g., KU22, FU1, etc.). Check the code string on your model for exact certification and temperature class.
A typical code string (example only): EJX530A-E D S7N-017DL /D1 /KF22 indicates model, output (HART), capsule (span D), wetted materials, process connection, indicator, calibration units (psi), and ATEX approval option. Always confirm each suffix in the current Yokogawa General Specifications before ordering.
Company Details
Business Type:
Manufacturer
Year Established:
2003
Total Annual:
3000000-5000000
Employee Number:
101~200
Ecer Certification:
Verified Supplier
Xi'an Xiyi Central Control Technology Co., Ltd. is an enterprise engaged in the production, sales and R & D of industrial automation instruments. The company is located in the ancient city of Xi'an, a prosperous international city in China. The company is mainly engaged in Rosemount a... Xi'an Xiyi Central Control Technology Co., Ltd. is an enterprise engaged in the production, sales and R & D of industrial automation instruments. The company is located in the ancient city of Xi'an, a prosperous international city in China. The company is mainly engaged in Rosemount a...
Get in touch with us
Leave a Message, we will call you back quickly!