Electrical performance | LOW VOLTAGE 0,6/1kV |
Standard | IEC 60502-1 / IEC 60092-353 |
Approvals | CE DNV-GL ABS (in progress) RoHS |
Construction Product Regulation | Cca - s1a, d1, a1 / B2ca - s1a, d1, a1 |
Impact resistance | AG2 Medium severity. |
Water performance | AD5 Jets. |
Packaging Details | 100 m / tied, or customized |
Delivery Time | 10 day |
Payment Terms | 30% deposit, the balance is settled on the delivery date |
Supply Ability | 100,000 m / month |
Place of Origin | Guangzhou, China |
Brand Name | SUNWIN |
Certification | ISO9001, ISO14001, OHSAS18001 |
View Detail Information
Explore similar products
3kV Flexible Low Voltage Power Cable EMC LSZH Screened Cable With Copper
0.6/1KV 3 Core Low Voltage Cable Portable Power Cable For Fixed Installation
Multicore Low Voltage Underground Cable Low Voltage Control Cable ISO Standard
High Tension Single Core Low Voltage Power Cable With Concentric Conductor
Product Specification
Electrical performance | LOW VOLTAGE 0,6/1kV | Standard | IEC 60502-1 / IEC 60092-353 |
Approvals | CE DNV-GL ABS (in progress) RoHS | Construction Product Regulation | Cca - s1a, d1, a1 / B2ca - s1a, d1, a1 |
Impact resistance | AG2 Medium severity. | Water performance | AD5 Jets. |
Packaging Details | 100 m / tied, or customized | Delivery Time | 10 day |
Payment Terms | 30% deposit, the balance is settled on the delivery date | Supply Ability | 100,000 m / month |
Place of Origin | Guangzhou, China | Brand Name | SUNWIN |
Certification | ISO9001, ISO14001, OHSAS18001 | ||
High Light | low voltage armored cable ,low voltage electrical cable |
Low Voltage Variable Frequency Drive Cables VFD Cable AG2 Medium Severity
TOXFREE ZH ROZ1-K AS VFD EMC 0,6/1kV cable has been specially designed for Variable Frequency Drive Motors and installations where it is necessary to limit the effects of electromagnetic interference (EMI).
Electrical performance
LOW VOLTAGE 0.6/1 KV
Standard
IEC 60502-1 / IEC 60092-353
Approval
CE
DNV-GL
ABS (in progress)
RoHS
Construction Product Regulation
Cca - s1a, d1, a1 / B2ca - s1a, d1, a1
Thermal performance
Maximum service temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations).
Fire performance
Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.
Fire non-propagation based on UNE-EN 60332-3 and IEC 60332-3.
LSZH (Low Smoke Zero Halogen) based on UNE-EN 60754-1 and IEC 60754-1.
Low smoke emission based on UNE-EN 61034 and IEC 61034.: Light transmittance > 60%
Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.
Mechanical performance
Minimum bending radius: x10 cable diameter.
Impact resistance: AG2 Medium severity.
Chemical performance
Chemical & Oil resistance: Good.
Water performance
Water resistance: AD5 Jets.
Other
Meter by meter marking.
Ripcord.
Electric fields resistant.
Installation conditions
Open Air.
Buried.
In conduit.
Applications
Industrial use.
Variable Frequency Drive (VFD)
Conductor
Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
Grounding Conductor
The grounding conductor is divided into three conductors; the equivalent cross section is approximately 50% of the section of the phase conductor.
Insulation
Cross-linked polyethylene (XLPE)
The standard identification of insulated conductors is the following:
4G grey + brown + black + Green/yellow (up to 4 mm2)
3x + 3G grey + brown + black + Green/yellow (3 x) (from 6 mm2 onwards)
Screen
Aluminium-polyester tape screen, helically placed over the insulated conductors. Over the tape there is a tinned copper braid screen. The tape and the braid act as a double screen to cut out all of the the electromagnetic interference.
The screen has a cover of 100% and its total section is approximately 10% of one of the conductors.
Outer sheath
Polyolefin LSZH outer sheath, black colour. The ripcord allows you to gently tear the outer-sheath allowing you to gently peel it away without damaging the screen.
Technology
1. Conductor
Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
2. Grounding Conductor
The grounding conductor is divided into three conductors; the equivalent cross section is approximately 50% of the section of the phase conductor.
3. Insulation
Cross-linked polyethylene (XLPE)
The standard identification of insulated conductors is the following:
4G grey + brown + black + yellow/green (up to 4 mm2)
3x + 3G grey + brown + black + yellow/green (3 x) (from 6 mm2 onwards)
4. Screen
Aluminium-polyester tape screen, helically placed over the insulated conductors. Over the tape there is a tinned copper braid screen. The tape and the braid act as a double screen to cut out all of the the electromagnetic interference.The screen has a cover of 100% and its total section is approximately 10% of one of the conductors.
5. Outer sheath
Polyolefin LSZH outer sheath, black colour. The ripcord allows you to gently tear the outer-sheath allowing you to gently peel it away without damaging the screen.
Company Details
Business Type:
Manufacturer
Ecer Certification:
Active Member
Shengyu Cable Co., Ltd was founded in 1999. The production base is located in Guangzhou Development Zone with a registered capital of 248 million yuan. It is committed to providing cable solutions for social power grid construction, engineering projects, household electricity and other fields to hel... Shengyu Cable Co., Ltd was founded in 1999. The production base is located in Guangzhou Development Zone with a registered capital of 248 million yuan. It is committed to providing cable solutions for social power grid construction, engineering projects, household electricity and other fields to hel...