China factories

China factory - Guangdong Shengyu Cable Industry Co., Ltd.

Guangdong Shengyu Cable Industry Co., Ltd.

  • China,Guangzhou ,Guangdong
  • Active Member

Leave a Message

we will call you back quickly!

Submit Requirement
China 6kV / 10kV Medium Voltage 2 Phase Cable Xlpe Insulated Wire Fire Resistant
China 6kV / 10kV Medium Voltage 2 Phase Cable Xlpe Insulated Wire Fire Resistant

  1. China 6kV / 10kV Medium Voltage 2 Phase Cable Xlpe Insulated Wire Fire Resistant

6kV / 10kV Medium Voltage 2 Phase Cable Xlpe Insulated Wire Fire Resistant

  1. MOQ: Negotiable
  2. Price: Negotiable
  3. Get Latest Price
Name Medium Voltage cables
Conductor Copper or aluminium, round, multiwire stranded and compact, according to VDE 0295.
Use construction and power distribution industries
Air temperature 30°C
voltage rating 6/10kV
standards - VDE 0276-620 - HD 620 - DIN EN 60228 Class 2
Packaging Details 100 m / tied, or customized
Delivery Time 10 day
Payment Terms 30% deposit, the balance is settled on the delivery date
Supply Ability 100,000 m / month
Place of Origin Guangzhou, China
Brand Name SUNWIN
Certification ISO9001, ISO14001, OHSAS18001

View Detail Information

Contact Now Ask for best deal
Get Latest Price Request a quote
  1. Product Details
  2. Company Details

Product Specification

Name Medium Voltage cables Conductor Copper or aluminium, round, multiwire stranded and compact, according to VDE 0295.
Use construction and power distribution industries Air temperature 30°C
voltage rating 6/10kV standards - VDE 0276-620 - HD 620 - DIN EN 60228 Class 2
Packaging Details 100 m / tied, or customized Delivery Time 10 day
Payment Terms 30% deposit, the balance is settled on the delivery date Supply Ability 100,000 m / month
Place of Origin Guangzhou, China Brand Name SUNWIN
Certification ISO9001, ISO14001, OHSAS18001
High Light xlpe medium voltage cables ,medium voltage wire

6kV / 10kV Medium Voltage 2 Phase Cable Xlpe Insulated Wire Fire Resistant

Since about 1970 the cross-linked polyethylene (XLPE)-insulated power cables have been used in Germany. The XLPE-insulation possesses very good electrical, mechanical and thermal characteristics in

medium voltage networks. This type of insulation is very chemically resistant and also resistant to cold. Due to various advantages, the XLPE-insulated type has vastly displaced the traditional classical paper-insulated types in many sectors.
In order to prevent the penetration of moisture and also to extend the duration of life, the XLPE-insulated
medium voltage cables are designed with longitudinally water-proof screen including an additional swell tape and a PE outer sheath.
The manufacture of this sheath is based on high density polyethylene (HDPE), in which an additive organic peroxide is mixed. Due to the heating and pressure the molecule chains are joined to each other, assuring the transition from thermoplastic to elastic condition.
In comparison to PVC and paper-insulated cables, the advantage of XLPE-insulated medium voltage power cables is that they possess a low dielectric factor, such as it is 100 times smaller than of PVC-insulated cables.
Moreover, a better dielectric constant value has an effect on the low mutual capacitance, the short-circuit to ground and the charging current of XLPE-insulated cables.
The good properties of XLPE-insulated cables remain constant through a wide temperature range.
 
Characteristics of XLPE

  • permissible operating temperature
  • For permanent (normal) operation + 90°C
  • In short circuit +250°C
  • In overload operation and

damage by sea up to +130°C
 

  • Specific heat resistance 3,5 K · m/W
  • Dielectric constant 2,4
  • Specific resistance (20°C) min. 1016 Ohm · cm
  • Loss factor (tan o) (20°C) max. 0,5 · 10–3
  • Density 0,92 g/cm3
  • Breaking strength min. 200%
  • Tensile strength min. 12,5 N/mm2

 

Conductor

  • Copper or aluminium, round, multiwire stranded and compact, according to VDE 0295.

 

Inner semi-conducting layer

  • Semi-conducting compound, cross-linked, mini-mum wall-thickness 0,3 mm.

Insulation

  • Cross-linked polyethylene (XLPE), compound type DIX8 according to HD 620 S2.
  • Insulation nominal wall-thickness for 6/10 kV = 3,4 mm

12/20 kV = 5,5 mm

18/30 kV = 8,0 mm
 

Outer semi-conducting layer

  • Outer semi-conducting layer is extruded together with the inner semi-conducting layer and the insulation in one working process and are spliced with each other.
  • Semi-conducting compound, cross-linked, wall-thickness 0,3 to 0,6 mm.

 

Concentricity of conductor

  • The difference between the maximum and mini-mum value of 0,5 mm should not be exceeded.

 

Semi-conducting type

  • Over the outer semi-conducting layer, a semi- conducting tape must be used.

 

Screen

  • Screening of copper wires must have a minimum diameter of 0,5 mm and over that a copper tape applied helically with a minimum thickness of 0,1 mm.
  • Copper cross-section according to HD 620 S2.

 

Separator

  • Over the screen as well as under outer sheath, a separating layer must be used (e. g. taping).

 

Outer sheath

  • PE compound DMP2 according to HD 620 S2 black or
  • PVC compound DMV6 according to HD 620 S2 red
  • Wall-thickness = 2,5 mm,

for 1x 500 mm2 /30 kV = 2,6 mm

 

Laying of Cable

In order to avoid any damage, the XLPE-insulated medium voltage cables should carefully laid and installed. It must be ensured that the cables should not be pulled over the hard or sharp edges.

The cable ends must be water-tight-sealed. After cutting the length both ends must be sealed immediately.

A laying depth of 60 to 80 cm is recommended. Single conductor cables are normally arranged in a trefoil touching or triangular shape.

For laying in conduits, the influence of thermal insulation of air space between the cable and the inner wall of conduit should be specially considered. The inner diameter of the conduit should be at least 1,5 times that of the diameter of the cable.
 

Bending radius

During the laying of XLPE cables, the bending radius should not be below of the following values:

  • Cable without metal sheath = 15 x cable Ø
  • Cable with Alu-laminated sheath = 30 x cable Ø

 

Temperature range

During the installation, the temperature should not be below the following values:

  • for XLPE-insulation + PVC sheath = – 5°C
  • for XLPE-insulation + PE sheath = –20°C

 

Max. permissible tensile strength

By pulling the conductors with a pulling head (not for armoured cables)
 

P = No. of cores x conductor cross-section x o

o = permissible pulling tension N/mm2

– For Cu-conductor: 50 N/mm2

– For Alu-conductor: 30 N/mm2
 

Current carrying capacity

according to VDE 0276 part 620 or HD 620 S2
 

Laying in earth (ground)

  • Laying depth 0,7 – 0,8 m
  • Earth temperature

in the laying depth 20°C

  • Specific heat resistance 1,0 K · m/W
  • Load factor 0,7 (EVU-Load)

 

Laying in air

  • Air temperature 30°C
  • Load factor (permanent load) 1,0

 

Laying in conduits

Cables for conduit systems laying in earth, a reduction of the current carrying capacity with a factor of

0,85 is recommended.
 

Test voltages
 

Kind of voltage testVoltage test in kV

 

U0/U = 6/10 kV

 

U0/U = 12/20 kV

 

U0/U = 18/30 kV

Voltage test a. c. in kV153045
Voltage test d. c. in kV4896144
Voltage test a. c. (voltage test = 1000 h)183654

 

Voltage test to cable system

During the operation or after laying the medium voltage power cables, the dielectric can be tested with

alternating or direct current. The test duration continues 30 minutes.
 

Kind of voltage test

 

U0/U = 6/10 kV

 

U0/U = 12/20 kV

 

U0/U = 18/30 kV

 

Voltage test a. c. in kV

 

12

 

24

 

36

 

Voltage test d. c. in kV

 

34

up to 48

 

67

up to 96

 

76

up to 108


















Company Details

Bronze Gleitlager

,

Bronze Sleeve Bushings

 and 

Graphite Plugged Bushings

 from Quality China Factory
  • Business Type:

    Manufacturer

  • Ecer Certification:

    Active Member

Shengyu Cable Co., Ltd was founded in 1999. The production base is located in Guangzhou Development Zone with a registered capital of 248 million yuan. It is committed to providing cable solutions for social power grid construction, engineering projects, household electricity and other fields to hel... Shengyu Cable Co., Ltd was founded in 1999. The production base is located in Guangzhou Development Zone with a registered capital of 248 million yuan. It is committed to providing cable solutions for social power grid construction, engineering projects, household electricity and other fields to hel...

+ Read More

Get in touch with us

  • Reach Us
  • Guangdong Shengyu Cable Industry Co., Ltd.
  • No. 23, Dongzhi Rd, Guangzhou Development District, Guangzhou, Guangdong, China.
  • https://www.insulatedpowercable.com/

Leave a Message, we will call you back quickly!

Email

Check your email

Phone Number

Check your phone number

Requirement Details

Your message must be between 20-3,000 characters!

Submit Requirement