Standard | BS 7846, BS 5266, BS 8434-2, BS 5839-1 26.2e |
Insulation | XLPE (Cross-Linked Polyethylene) |
Bedding | LSZH (Low Smoke Zero Halogen) |
Separator | Mica/glass fire barrier tape |
Armour | SWA (Steel Wire Armour) |
Sheath | LSZH (Low Smoke Zero Halogen) |
Packaging Details | 100 m / tied, or customized |
Delivery Time | 10 day |
Payment Terms | 30% deposit, the balance is settled on the delivery date |
Supply Ability | 100,000 m / month |
Place of Origin | Guangzhou, China |
Brand Name | SUNWIN |
Certification | ISO9001, ISO14001, OHSAS18001 |
View Detail Information
Explore similar products
Low Smoke Halogen Free Flame Retardant Cables Xlpe Fire Resistant Cable
Low Voltage Flame Retardant Cable Environment Friendly Copper Core BS EN 60332-3
Single Core Flame Retardant Low Smoke Cables Solid Or Stranded Copper Conductor
Single Core Flame Retardant Cable Low Smoke Zero Halogen Polymer Type
Product Specification
Standard | BS 7846, BS 5266, BS 8434-2, BS 5839-1 26.2e | Insulation | XLPE (Cross-Linked Polyethylene) |
Bedding | LSZH (Low Smoke Zero Halogen) | Separator | Mica/glass fire barrier tape |
Armour | SWA (Steel Wire Armour) | Sheath | LSZH (Low Smoke Zero Halogen) |
Packaging Details | 100 m / tied, or customized | Delivery Time | 10 day |
Payment Terms | 30% deposit, the balance is settled on the delivery date | Supply Ability | 100,000 m / month |
Place of Origin | Guangzhou, China | Brand Name | SUNWIN |
Certification | ISO9001, ISO14001, OHSAS18001 | ||
High Light | fire retardant cable ,fire retardant wire |
LSZH Flame Retardant Cable Single Core Heat Resistant Cable BS 7846 SWA Armour
APPLICATION
Firetec Power is a fire resistant armoured cable suitable for use in fixed installations for power circuits, fire alarm systems and emergency lighting systems. It is robust, flexible and suitable for use inside and outside buildings, meeting the enhanced grade of BS 5839-1 26.2e
CONSTRUCTION
Conductor
Class 2 stranded copper conductor to BS EN 60228 (previously BS 6360)
Separator
Mica/glass fire barrier tape
Insulation
XLPE (Cross-Linked Polyethylene)
Bedding
LSZH (Low Smoke Zero Halogen)
Armour
SWA (Steel Wire Armour)
Sheath
LSZH (Low Smoke Zero Halogen)
STANDARDS
BS 7846, BS 5266, BS 8434-2, BS 5839-1 26.2e, BS EN 50200 PH30, PH60, PH120, BS 6387 C W and Z, BS EN 50267, BS EN 50268, BS EN 50265 and 50266, BS EN/IEC 60332, BS EN/IEC 60754, BS EN/IEC 61034, LUL 1-085
We supply LPCB Certified products
The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the Cables laboratory. Cable performance in respect of conductor resistance, construction quality (workmanship), dimensional consistency, and other parameters are verified to published standards and approved product drawings. Conformance to RoHS (Restriction of the use of Hazardous Substances) is determined and confirmed
CHARACTERISTICS
Voltage Rating
600/1000V
Operating Temperature
-10°C to +90
Minimum Bending Radius
Up to 25mm2: 6 x overall diameter
Above 25mm2: 8 x overall diameter
Core Identification
2 cores: Blue Brown
3 cores: Brown Black Grey
4 cores: Blue Brown Black Grey
5 core: Green/Yellow Blue Brown Black Grey
(5 core also available with White numbered cores)
Outer Sheath Colour
Black
Note: Cables above 4 core are not LUL approved
Company Details
Business Type:
Manufacturer
Ecer Certification:
Active Member
Shengyu Cable Co., Ltd was founded in 1999. The production base is located in Guangzhou Development Zone with a registered capital of 248 million yuan. It is committed to providing cable solutions for social power grid construction, engineering projects, household electricity and other fields to hel... Shengyu Cable Co., Ltd was founded in 1999. The production base is located in Guangzhou Development Zone with a registered capital of 248 million yuan. It is committed to providing cable solutions for social power grid construction, engineering projects, household electricity and other fields to hel...