| SF6 gas leak rate | <1‰ |
| Rated current | 630A |
| Lightning impulse withstand voltage | 85KV |
| Rated voltage | 12KV |
| Rated peak withstand current | 50KA |
| Secondary circuit power frequency withstand voltage | 2KV |
| Enclosure Protection Class | IP66 |
| Rated short time withstand current | 20 KA/3s |
| Rated current breaking times | 100Time |
| Power frequency withstand voltage / phase-phase / to ground / fracture | 42/48KV |
| Rated closed-loop breaking current | 630A |
| SF6 Gas Pressure (Relative & Absolute Pressure) | 40kPa |
| Rated cable breaking current | 10A |
| Applicable Cable Cross-section | ≤400mm² |
| Place of Origin | China |
View Detail Information
Explore similar products
Outdoor High Voltage Cable Distribution Box
SF₆ Gas Insulated Switching Station
Product Specification
| SF6 gas leak rate | <1‰ | Rated current | 630A |
| Lightning impulse withstand voltage | 85KV | Rated voltage | 12KV |
| Rated peak withstand current | 50KA | Secondary circuit power frequency withstand voltage | 2KV |
| Enclosure Protection Class | IP66 | Rated short time withstand current | 20 KA/3s |
| Rated current breaking times | 100Time | Power frequency withstand voltage / phase-phase / to ground / fracture | 42/48KV |
| Rated closed-loop breaking current | 630A | SF6 Gas Pressure (Relative & Absolute Pressure) | 40kPa |
| Rated cable breaking current | 10A | Applicable Cable Cross-section | ≤400mm² |
| Place of Origin | China |
The switching station is an important auxiliary power supply facility in medium-voltage power distribution networks, acting as the downstream hub of ring network power supply systems.
It undertakes voltage transformation, circuit distribution, fault isolation and flexible power supply switching. It can effectively optimize regional power grid topology, shorten power supply radius, and greatly improve power supply reliability and power quality. Widely applied in urban & rural power grids, industrial parks and residential communities, it is also known as an outdoor cable branch distribution station.
Reasonable power supply range division in distribution networks ensures stable and reliable power supply for ring network, branch and terminal loads. Its switching operations will not interfere with normal grid operation and user power consumption.
Meanwhile, it optimizes grid structure, narrows power failure fault scope, reduces line loss and grid operation load, and realizes flexible zoning coordination between power feeders and load sections.
Company Details
Business Type:
Manufacturer,Exporter,Seller
Year Established:
2008
Total Annual:
29460000-44190000
Employee Number:
120~130
Ecer Certification:
Verified Supplier
.gtr-container-a1b2c3 { font-family: Verdana, Helvetica, "Times New Roman", Arial, sans-serif; color: #333; padding: 16px; line-height: 1.6; box-sizing: border-box; width: 100%; overflow-x: hidden; } .gtr-container-a1b2c3 p { font-size: 14px; margin-top: 0; m... .gtr-container-a1b2c3 { font-family: Verdana, Helvetica, "Times New Roman", Arial, sans-serif; color: #333; padding: 16px; line-height: 1.6; box-sizing: border-box; width: 100%; overflow-x: hidden; } .gtr-container-a1b2c3 p { font-size: 14px; margin-top: 0; m...
Get in touch with us
Leave a Message, we will call you back quickly!