| Payment Terms | L/C,D/A,D/P,T/T,Western Union |
| Supply Ability | 5000-10000 pieces/mouth |
| Delivery Time | 7-15 days |
| Packaging Details | box |
| Power Supply | 220VAC / 12VDC (optional) |
| Power Consumption | 2W |
| Display | 1 Inch OLED |
| Communication Interface | MODBUS-RTU protocol, RS485, RS232 |
| Trigger Current | 0.5/1/2.5/5kA (optional, default 1kA) |
| Measurement Range | 1-100kA (via micro-rogowski coil) |
| Brand Name | LLH |
| Model Number | LS-LM100A |
| Place of Origin | Guangdong Province.China |
View Detail Information
Explore similar products
SPD Intelligent Monitor 3 Way Leakage Current MODBUS RTU Lightning Surge
RS485 RS232 Lightning Strike Monitor Grounding Resistance Monitor 220V AC 12V DC
100kA Lightning Current Peak Monitor MODBUS RTU Surge Recorder For Lightning
100kA MODBUS RTU Lightning Surge Recorder Intelligent Lightning Protection
Product Specification
| Payment Terms | L/C,D/A,D/P,T/T,Western Union | Supply Ability | 5000-10000 pieces/mouth |
| Delivery Time | 7-15 days | Packaging Details | box |
| Power Supply | 220VAC / 12VDC (optional) | Power Consumption | 2W |
| Display | 1 Inch OLED | Communication Interface | MODBUS-RTU protocol, RS485, RS232 |
| Trigger Current | 0.5/1/2.5/5kA (optional, default 1kA) | Measurement Range | 1-100kA (via micro-rogowski coil) |
| Brand Name | LLH | Model Number | LS-LM100A |
| Place of Origin | Guangdong Province.China | ||
| High Light | Lightning current peak monitor 100kA ,MODBUS RTU lightning protection system ,Surge recorder lightning strike monitor | ||
| Product features |
| ● 4 switch acquisition ports. |
| ●High accuracy. |
| ●Designed for intelligent lightning protection monitoring system. |
| ●Support Ethernet, Lora, 4G and other communication modes |
| ●DC 12V and AC 220V power supply optional. |
| ●Up to 10 Switch alarm records (channel number, alarm date and time) . |
| ●Support for standard 35mm DIN-RAIL and wall mounting, 1 inch OLED display, Standard MODBUS-RTU protocol. |
|
●1 RS485 communication serial port for branch computer communication (connect with host communication port) . |
| ●1 RS232 communication serial port for host communication (connect with branch communication port) . |
| ●The default protocol is the non- standard Communication Protocol of the earth grid monitoring system. Customized protocol for simplified communication Gateway available. |
| ●Switch data acquisition port is equipped with independent alarm indicator(normal open), remote alarm triggers when closed with visual and Buzzer warning. |
|
●1 surge peak value acquisition port. General 8/20us and 10/350us waveforms, trigger sensitivity adjustable, large memory with 9999 surge records (polarity, peak value, time of occurrence of surge and waveform of last surge) . |
Product Specification
![]()
| Models | LS-LM100A | |
| Power supply | 220VAC, 12VDC optional | |
| Power | 2W | |
| Screen | 1 Inch OLED | |
| Communication interface | MODBUS-RTU protocol | |
| RS485 | ||
| RS232 | ||
| Switch acquisitionT01~T04 | 4 switch monitoring channels: dry contact, normal open, visual and buzzer warning. | |
| Surge Channel |
Lightning surge infomation | polarity of surge current, peak value, max memory: 9999 |
| Trigger current | 0.5/1/2.5/5KA optional, default is 1kA | |
| Resolution | 0.1kA | |
| Acquisition frequency | 10/sec | |
| Surge type | 8/20us,10/350us | |
| Sensors | Micro-rogowski coil, acquisition range 1-100kA | |
| Interface protection | Serial port | Built-in surge protection circuit, 4000V lightning protection |
| Data safety | Alarm data could be saved safely when power failure | |
| Enclosure | Black aluminum / red plastic stand | |
| Mounting | 35 mm DIN-RAIL and wall mounting | |
| Operation Environment | -20~85℃,0~95% RH | |
Notices
1.Select the appropriate power supply (220VAC or 12VDC) based on on-site conditions.
2.The micro-rogowski coil sensor must be correctly installed to ensure accurate current acquisition (range 1-100kA).
3.Set the trigger current according to actual application scenarios (default 1kA) for optimal monitoring sensitivity.
4.Ensure reliable grounding of the device to avoid electromagnetic interference affecting measurement accuracy.
5.Regularly export stored data to prevent memory overflow (supports 9999 records).
6.The device automatically saves alarm data during power outage; restore power promptly to avoid data loss.
FAQ
Q1: What communication interfaces does the product support?
A1: It supports RS485 (for branch computer communication) and RS232 (for host communication), compatible with MODBUS-RTU protocol.
Q2: How many surge records can it store?
A2: It can store up to 9999 surge records, including polarity, peak value, occurrence time, and the last surge waveform.
Q3: What surge waveforms does it support?
A3: It supports both 8/20μs and 10/350μs waveforms, covering common lightning surge scenarios.
Q4: Can the trigger current be adjusted?
A4: Yes, the trigger current is adjustable (0.5/1/2.5/5kA), with a default setting of 1kA.
Q5: Is the device protected against surges?
A5: Yes, the serial port has a built-in 4000V lightning protection circuit to ensure device safety.
Company Details
Business Type:
Manufacturer
Year Established:
2018
Total Annual:
1000000-10000000
Employee Number:
20~100
Ecer Certification:
Verified Supplier
Shenzhen Leilihai Electric Co., Ltd We are a high-tech enterprise that integrates the research and development, manufacturing, sales, and installation services of lightning protection devices and lightning protection system supporting products. The company has successively passed the German TUV cer... Shenzhen Leilihai Electric Co., Ltd We are a high-tech enterprise that integrates the research and development, manufacturing, sales, and installation services of lightning protection devices and lightning protection system supporting products. The company has successively passed the German TUV cer...
Get in touch with us