| Payment Terms | L/C,D/A,D/P,T/T,Western Union |
| Supply Ability | 5000-10000 pieces/mouth |
| Delivery Time | 7-15 days |
| Packaging Details | box |
| Standards | IEC 61643.11 |
| Nominal Operating Voltage (Un) | 220Vac(50Hz) |
| Maximum Continuous Operating Voltage (Uc) | L-N:385Vac; N-E:255Vac |
| Power Capacity | 30KW, 45A (Line) |
| Impulse Current (8/20μs) | 20kA / 50kA / 100kA |
| Voltage Protection Level (Up) | ≤1000V / ≤1150V / ≤1250V |
| Brand Name | LLH |
| Model Number | M-LBS 5000 |
| Place of Origin | Guangdong Province.China |
View Detail Information
Explore similar products
AC Power Lightning Protection Box 3 Phase 385V 255V For Communication Base
Wall Mount Lightning Arrester Box 220V 40kA 80kA IP20 Electrical System
Lightning Protection 3 Phase AC Whole House Surge Protectors 220V 20kA 40kA T2
AC Lightning Protection Box 3 Phase Whole Home Surge Protector T2 SPD 220V 20kA
Product Specification
| Payment Terms | L/C,D/A,D/P,T/T,Western Union | Supply Ability | 5000-10000 pieces/mouth |
| Delivery Time | 7-15 days | Packaging Details | box |
| Standards | IEC 61643.11 | Nominal Operating Voltage (Un) | 220Vac(50Hz) |
| Maximum Continuous Operating Voltage (Uc) | L-N:385Vac; N-E:255Vac | Power Capacity | 30KW, 45A (Line) |
| Impulse Current (8/20μs) | 20kA / 50kA / 100kA | Voltage Protection Level (Up) | ≤1000V / ≤1150V / ≤1250V |
| Brand Name | LLH | Model Number | M-LBS 5000 |
| Place of Origin | Guangdong Province.China | ||
| High Light | 3 Phase Lightning Protection Box ,Lightning Protection Box 220V ,Light Alarm Surge Suppressor | ||
Featuring high current capacity (up to 100kA impulse current) and low residual voltage, M-LBS 5000 adopts pluggable lightning protection modules for easy maintenance and replacement.
The built-in lightning status monitoring (counting) system accurately records lightning strikes, while the sound and light alarm function provides real-time alerts for SPD failures.
M-LBS 5000 is a high-performance three-phase AC power lightning protection box designed for LPZ 0B-1 and subsequent partitions.
It is specifically installed in equipment-intensive rooms such as communication base stations, broadcasting and television system rooms, computer rooms,
and medical equipment rooms to provide comprehensive lightning protection for three-phase AC distribution systems.
![]()
|
Pluggable Lightning Protection Modules |
|
|
Modular Layered Protection |
|
|
Intelligent Monitoring & Alarm System Built-in lightning strike counter and visual status indicators for real-time fault alerts. |
Product Specification
![]()
|
Standards
|
IEC 61643.11
|
||
|
Models
|
M-LBS 5000
|
||
|
Parameter
|
|||
|
Nominal operating voltage Un
|
220Vac(50Hz)
|
||
|
Maximum continuous operating voltage Uc
|
L-N:385Vac(50Hz),N-E:255Vac(50Hz)
|
||
|
Power W
|
30KW,45A(Line)
|
||
|
L-N Impulse current(8/20μs)
|
20kA
|
50kA
|
100kA
|
|
Voltage protection level Up
|
≤1000V
|
≤1150V
|
≤1250V
|
|
Response time tA
|
≤25ns
|
||
|
Protection Circuit
|
L1,L2,L3-N,N-E
|
||
|
Auxiliary functions
|
Number of lightning strikes, sound and light alarms, remote
signaling dry contacts
|
||
|
Lightning stroke count
|
|||
|
Counting current range
|
0.5A(8/20μs)-100kA(8/20μs)
|
||
|
Counting digit
|
0-999
|
||
|
Installation method
|
Auxiliary installation bracket; Hole spacing 330mmx263mm
|
|
Screw torque
|
5N*m
|
|
Strip length
|
12mm
|
|
Wiring cross-sectional area
|
6mm2-32mm2
|
|
Product size
|
510mmx370mmx140mm
|
|
Shell material and flame retardant grade
|
Cold rolled steel plate painted orange
|
|
Deterioration indication
|
LED green: OK; Red: Fail; SPD failure buzzer alarm
|
|
Remote signaling contact type
|
Normally closed and normally open switching contacts
|
|
Remote signaling contact switching ability
|
125 Vac / 1 A, 125 Vdc A / 0.2
|
|
Maximum connection capacity of remote signaling
|
2.5mm2
|
|
Installation position
|
Indoor
|
|
Temperature range
|
-40℃…+80℃
|
|
Humidity range
|
Relative humidity ≤ 95% (max 40 ℃)
|
Notices
●Install the lightning protection box in a well-ventilated, dry indoor environment away from flammable and explosive materials.
●Use wiring with cross-sectional area 6mm²-32mm² and tighten screws to 5N·m torque.
●Ensure the grounding system meets requirements (ground resistance ≤4Ω) for optimal surge diversion.
●Regularly check the lightning strike count and status indicator—replace faulty modules immediately.
●The product is heavy; ensure the installation surface can bear its weight (product size: 510mmx370mmx140mm).
●Only qualified electricians are allowed to install, maintain, or replace modules to avoid electrical hazards.
FAQ
Q1: What is the maximum impulse current capacity of M-LBS 5000?
A1: It supports three impulse current levels: 20kA, 50kA, and 100kA (8/20μs waveform) to meet different protection requirements.
Q2: Does the product have a lightning strike counting function?
A2: Yes, it has a built-in lightning strike counting system with a counting range of 0.5A-100kA and counting digit of 0-999.
Q3: What is the alarm method for SPD failure?
A3: It adopts dual alarm methods: LED red indicator and buzzer alarm, and supports remote signaling through dry contacts.
Q4: Can the modules be replaced without power outage?
A4: The pluggable module design allows for hot-swapping, enabling module replacement without disconnecting the entire power supply.
Q5: What is the power capacity of M-LBS 5000?
A5: It has a power capacity of 30KW and a line current of 45A, suitable for large-scale three-phase power systems.
Company Details
Business Type:
Manufacturer
Year Established:
2018
Total Annual:
1000000-10000000
Employee Number:
20~100
Ecer Certification:
Verified Supplier
Shenzhen Leilihai Electric Co., Ltd We are a high-tech enterprise that integrates the research and development, manufacturing, sales, and installation services of lightning protection devices and lightning protection system supporting products. The company has successively passed the German TUV cer... Shenzhen Leilihai Electric Co., Ltd We are a high-tech enterprise that integrates the research and development, manufacturing, sales, and installation services of lightning protection devices and lightning protection system supporting products. The company has successively passed the German TUV cer...
Get in touch with us
Leave a Message, we will call you back quickly!