| SPD Type | Explosion-Proof Signal Surge Protector |
| Nominal Operating Voltage (Un) | 24Vdc |
| Maximum Continuous Operating Voltage (Uc) | 32Vdc |
| Voltage Protection Level (X-X @C1) | ≤60V |
| Response Time (tA) | ≤1ns |
| Brand Name | LLH |
| Model Number | LS-Ex/24C |
| Place of Origin | Guangdong Province.China |
View Detail Information
Explore similar products
Grounding Down Conductor Lightning Arrester Wire Copper Outdoor Grounding Cable
Ex Proof Signal SPD 24Vdc IP67 10kV Hazardous Area Petrochemical Protection
Lightning Down Conductor Cable Copper Outdoor Grounding Wire 200kA 32mm
Outdoor Earthing Down Conductor Cable 200kA 32mm Copper Lightning Protection
Product Specification
| Payment Terms | L/C,D/A,D/P,T/T,Western Union | Supply Ability | 5000-10000 pieces/mouth |
| Delivery Time | 7-15 days | Packaging Details | box |
| Standards | IEC 61643.21 | SPD Type | Explosion-Proof Signal Surge Protector |
| Nominal Operating Voltage (Un) | 24Vdc | Maximum Continuous Operating Voltage (Uc) | 32Vdc |
| Voltage Protection Level (X-X @C1) | ≤60V | Response Time (tA) | ≤1ns |
| Brand Name | LLH | Model Number | LS-Ex/24C |
| Place of Origin | Guangdong Province.China | ||
| High Light | Explosion Proof SPD Components ,SPD Components 24Vdc ,IP67 Signal SPD | ||
| Product Features |
|
● Sus 304 stainless steel housing.
|
|
● Protection Level IP67.
|
|
● Standard threaded interface mounting.
|
|
● Series connection, low residual voltage.
|
|
● Suitable for installation in LPZ2-3 and subsequent lightning protection zones, as lightning protectors for communication signal line equipment in intrinsically safe areas of natural gas, gas stations, petroleum, and petrochemical systems, such as sensors and transmitters.
|
Applications
![]()
Product specifications
![]()
|
Standards
|
IEC 61643.21
|
|
Models
|
LS-Ex/24C
|
|
Parameter
|
|
|
Nominal operating voltage Un
|
24Vdc
|
|
Maximum continuous operating voltage Uc
|
32Vdc
|
|
X-X Shock rating C1
|
2kV/1kA
|
|
X-C Shock rating C2
|
10kV/5kA
|
|
X-X,X-C Shock rating B2
|
4kV(10/700μs)
|
|
X-X,X-C Shock rating D1
|
2.5kA(10/350μs)
|
|
X-X Up@C1
|
≤60V
|
|
X-C Up@C2
|
≤500V
|
|
X-X Up@B2
|
≤30V
|
|
X-C Up@B2
|
≤300V
|
|
Response time tA
|
≤1ns
|
|
Load current IR
|
250mA
|
|
Line to line bandwidth fG
|
3MHz
|
|
Protective Line
|
X1-X2,X1-C,X2-C
|
|
Threaded interface
|
M20 thread, 1/2NPT, 3/4NPT optional
|
|
Lead length
|
25mm
|
|
Wire cross-sectional area
|
1.5mm²
|
|
Product size
|
75mmx27mm(excluding leads)
|
|
Housing material
|
SUS 304 stainless steel+epoxy resin potting
|
|
Installation location
|
Outdoor,Indoor
|
|
Shell protection rating
|
IP67
|
|
Temperature range
|
-40℃…+120℃
|
|
Humidity range
|
Relative humidity≤95%
|
Notices
●This product is for intrinsically safe areas; ensure it is used in compliance with explosion-proof regulations.
●Select the appropriate threaded interface (M20, 1/2NPT, 3/4NPT) based on installation requirements.
●The lead length is 25mm with a cross-sectional area of 1.5mm²; do not extend the lead without professional modification.
●Do not exceed the maximum load current (250mA) to avoid overheating.
●Avoid installing in areas with severe mechanical impact or chemical corrosion.
●Regularly inspect the housing for damage or corrosion; replace if compromised.
FAQ
Q1: What is the difference between LS-Ex/24 and LS-Ex/24C?
A1: LS-Ex/24 uses parallel connection, while LS-Ex/24C uses series connection with low residual voltage and 250mA load current capacity.
Q2: Can it be used outdoors?
A2: Yes, the IP67 protection level makes it dustproof and waterproof, suitable for both indoor and outdoor installation.
Q3: What is the load current capacity?
A3: It supports a maximum load current of 250mA, suitable for most industrial control signal lines in hazardous areas.
Q4: What is the operating temperature range?
A4: It can operate in temperatures ranging from -40℃ to +120℃, adapting to harsh environmental conditions.
Q5: Is it suitable for 4-20mA current loops?
A5: Yes, it is specifically designed for 4-20mA current loops and other industrial control signal lines in hazardous areas.
Company Details
Business Type:
Manufacturer
Year Established:
2018
Total Annual:
1000000-10000000
Employee Number:
20~100
Ecer Certification:
Verified Supplier
Shenzhen Leilihai Electric Co., Ltd We are a high-tech enterprise that integrates the research and development, manufacturing, sales, and installation services of lightning protection devices and lightning protection system supporting products. The company has successively passed the German TUV cer... Shenzhen Leilihai Electric Co., Ltd We are a high-tech enterprise that integrates the research and development, manufacturing, sales, and installation services of lightning protection devices and lightning protection system supporting products. The company has successively passed the German TUV cer...
Get in touch with us
Leave a Message, we will call you back quickly!