China P-IOM633 Programmable I/O Module | BACnet MS/TP & Modbus RTU, Built-in PID
China P-IOM633 Programmable I/O Module | BACnet MS/TP & Modbus RTU, Built-in PID

  1. China P-IOM633 Programmable I/O Module | BACnet MS/TP & Modbus RTU, Built-in PID

P-IOM633 Programmable I/O Module | BACnet MS/TP & Modbus RTU, Built-in PID

  1. MOQ: 1 Piece
  2. Price: US$60 - 72 / Piece
  3. Get Latest Price
Product Type Programmable I/O Module
OEM / ODM Firmware logic, PID defaults, protocol behaviour, branding and packaging
Delivery Time 7-15 work days
Output Channels 3 x analog output + 3 x relay output
Power Supply DC 24 V (21-28 V DC), <= 3 W typical, <= 5 W with 3 relays on
Packaging Details 1 pc per anti-static bag, standard export carton; neutral or OEM branded packing available
Analog Output 0-10 V / 4-20 mA, 12-bit PWM, soft start, MAN/AUTO
Operating Temperature -20 ~ +60 degC, 5-95 % RH non-condensing, IP20
Configuration Web interface at 192.168.5.2 over USB-RS485, online firmware upgrade
Payment Terms T/T
Control Function Built-in PID + up to 16 Function Blocks, 100 ms scan cycle
Dimensions 88 x 107 x 59 mm (W x H x D), approx. 220 g
Application BAS/BMS, HVAC, data centre liquid cooling (CDU), PLC/DCS, energy management
Internal Points N1-N32, float or logic, readable over the bus
Mounting 35 mm DIN rail (clip type)
Supply Ability 3000 Piece / Month
Input Channels 6 x universal input: 0-10 V / 4-20 mA / NTC-10K / Dry Contact
Isolation Full isolation between power, RS485 and relay outputs
Communication Modbus RTU slave / BACnet MS/TP master node
Model Number P-IOM633
Certification CE (EMC), RoHS
Place of Origin Shenzhen, China
Brand Name Qingchen

View Detail Information

Contact Now Ask for best deal
Get Latest Price Request a quote
  1. Product Details
  2. Company Details

Product Specification

Product Type Programmable I/O Module OEM / ODM Firmware logic, PID defaults, protocol behaviour, branding and packaging
Delivery Time 7-15 work days Output Channels 3 x analog output + 3 x relay output
Power Supply DC 24 V (21-28 V DC), <= 3 W typical, <= 5 W with 3 relays on Packaging Details 1 pc per anti-static bag, standard export carton; neutral or OEM branded packing available
Analog Output 0-10 V / 4-20 mA, 12-bit PWM, soft start, MAN/AUTO Operating Temperature -20 ~ +60 degC, 5-95 % RH non-condensing, IP20
Configuration Web interface at 192.168.5.2 over USB-RS485, online firmware upgrade Payment Terms T/T
Control Function Built-in PID + up to 16 Function Blocks, 100 ms scan cycle Dimensions 88 x 107 x 59 mm (W x H x D), approx. 220 g
Application BAS/BMS, HVAC, data centre liquid cooling (CDU), PLC/DCS, energy management Internal Points N1-N32, float or logic, readable over the bus
Mounting 35 mm DIN rail (clip type) Supply Ability 3000 Piece / Month
Input Channels 6 x universal input: 0-10 V / 4-20 mA / NTC-10K / Dry Contact Isolation Full isolation between power, RS485 and relay outputs
Communication Modbus RTU slave / BACnet MS/TP master node Model Number P-IOM633
Certification CE (EMC), RoHS Place of Origin Shenzhen, China
Brand Name Qingchen

P-IOM633 is a DIN-rail programmable I/O module that combines remote I/O acquisition with local programmable control. Built on the proven IOM-633 hardware platform with expanded MCU flash and rewritten firmware, it adds built-in PID closed-loop control, a web configuration interface and Function Block programming, so building automation, HVAC and industrial projects can close the control loop inside the module - without an extra controller or a dedicated host computer. Modbus RTU and BACnet MS/TP models are available for direct integration with BMS, PLC and DCS systems.

Key Features

  • Built-in PID control - setpoint SP, proportional gain Kp, integral time Ti, derivative time Td, dead zone, output bias, direct/reverse action and output limits Ymin/Ymax for stable temperature, pressure and flow loops.
  • Up to 16 programmable Function Blocks - PID, Scale, High Select, Low Select, Two-Position, Compare, AND, OR, NOT, Delay and Buffer, executed on a 100 ms scan cycle; local interlocks and coordinated control without adding a PLC.
  • 6 universal inputs (UI1-UI6) - every channel independently selectable as 0-10 V, 4-20 mA, NTC-10K or dry contact with a 12-bit ADC; channels set to dry contact work as 6 digital inputs with 20 ms debounce.
  • 3 analog outputs (AO1-AO3) - 0-10 V or 4-20 mA, 0.1 % resolution, 10-step soft start and MAN/AUTO manual override, for valves, damper actuators and VFD-driven pumps.
  • 3 relay outputs (BO1-BO3) - independent passive relay contacts with no common terminal, LATCH or 100 ms PULSE mode, for fans, pumps and alarm circuits.
  • 32 internal points (N1-N32) - floating-point or logic variables passed between Function Blocks or exchanged with the master station.
  • Fieldbus options - Modbus RTU slave (9600-115200 bps) or BACnet MS/TP master node (76800 bps); BACnet Device, Analog Input, Analog Output, Binary Input and Binary Output objects are supported.
  • Browser-based configuration - double-click the RST key to enter configuration mode, connect the RS485 port through a USB-RS485 adapter with the PC at 192.168.5.1, then open http://192.168.5.2/ to set channels, bus parameters and Function Blocks; firmware can be upgraded online - no dedicated software needed.
  • Reliable on site - complete isolation between power, communication and relay outputs, power-loss save of all parameters, built-in watchdog (auto reset), 500 V DC dielectric withstand, status LEDs plus a 5-bit address LED, and one-button factory reset.

Applications

  • Building automation (BAS/BMS) - remote I/O and local closed-loop control for AHUs, chillers and terminal units.
  • HVAC - temperature and humidity loops, air/water valve regulation, fan interlock and anti-short-cycle control.
  • Data centre liquid cooling (CDU) - PID control of coolant temperature, secondary-loop pressure and pump/valve actuators.
  • Industrial control - analog and digital acquisition, actuator control and interlocking on PLC, DCS and SCADA sites.
  • Energy management - metering, monitoring and on-site logic where a full controller is not justified.

Models and Ordering

Model Fieldbus Bus role Default address
PIOM-633-M Modbus RTU Slave 1 (range 1-247)
PIOM-633-B BACnet MS/TP Master node MAC 1 (range 0-127)

The communication protocol is fixed at the factory according to the model; please confirm the required model when ordering.

Technical Specifications

Universal Input (UI1-UI6 / terminals I1-I6)
Channels 6, each independently configurable
Operating modes 0-10 V / 4-20 mA / NTC-10K temperature / Dry Contact
Resolution 12-bit ADC
Measurement range 0-10 V; 4-20 mA (499 ohm sense resistor); NTC-10K -55 ~ +250 degC
Accuracy 0-10 V: <= +/-0.8 % FS; 4-20 mA: <= +/-1.5 % FS; channel consistency <= 0.2 % FS
Over-range The reading holds the last valid value
Analog Output (AO1-AO3 / terminals M1-M3)
Channels / mode 3, 0-10 V or 4-20 mA, independently configurable
Resolution 0-1000 (0.1 % of full scale), 12-bit PWM
Accuracy <= +/-0.8 % FS (0-10 V)
Control Function Block (AUTO) or manual override (MAN), 10-step soft start
Digital Input and Output
Digital input 6 channels, shared with UI1-UI6 in DRY mode, dry contact, 20 ms debounce, high active
Relay output 3 channels (D1-D3 / Q1-Q3), independent passive contacts with no common terminal, LATCH / PULSE (100 ms default), MAN/AUTO
Internal points N1-N32, floating-point or 0/1 logic, readable and writable over the bus
Communication and System
RS485 Two-wire, 1 channel (A/B), automatic direction control
Baud rate 9600 / 19200 / 38400 / 57600 / 76800 / 115200 bps
Data format 7 or 8 data bits, no/odd/even parity, 1 or 2 stop bits
Defaults (Modbus) 9600 bps, 8 data bits, no parity, 1 stop bit, slave address 1
Defaults (BACnet) 76800 bps, 8 data bits, no parity, MAC 1, device instance 1000
Refresh / scan I/O refresh 10 ms; Function Block scan 100 ms; watchdog approx. 3.2 s
Electrical and Mechanical
Power supply DC 24 V (21-28 V DC); supply must be >= 24 V for full analog accuracy
Power consumption <= 3 W (24 V DC, no load); <= 5 W with all 3 relays energised
Dielectric withstand 500 V DC for 1 min (power to communication terminals)
Isolation Complete isolation between power supply, communication port and the 3 relay outputs
Operating / storage -20 ~ +60 degC / -40 ~ +85 degC, 5-95 % RH non-condensing
Protection / mounting IP20 (control cabinet), 35 mm DIN rail
Dimensions / weight 88 x 107 x 59 mm (W x H x D), approx. 220 g
Housing / terminals Flame-retardant ABS/PC (UL94-V0); screw terminals, 5.08 mm pitch, 0.2-2.5 mm2

Function Blocks

Block Function Main parameters
PID Closed-loop controller (P/I/D) SP, Kp, Ti (0 = off), Td, dead zone, output bias, direct/reverse action, Ymin/Ymax
Scale Linear range conversion Input low/high, output low/high
High / Low Select Selects the larger / smaller of two inputs -
Two-Position On/off control with threshold ON value, OFF value
Compare Threshold comparison, outputs 0/1 Greater-than / less-than, threshold
AND / OR / NOT Logic operations -
Delay On / off delay On delay (s), off delay (s)
Buffer Signal pass-through / relay -

Up to 16 blocks run in sequence on a 100 ms scan cycle; sources and targets can be universal inputs, internal points, analog outputs or relay outputs. When two blocks write the same output the interface raises a write-conflict warning before saving.

Web Configuration

  1. Connect the module RS485 terminals (A/B) to a PC through a USB-RS485 adapter.
  2. Double-click the RST key (or hold it while powering up) to enter Web configuration mode - the address LEDs flash all-on/all-off at 1 Hz.
  3. Set the PC network adapter to 192.168.5.1 / 255.255.255.0 and open http://192.168.5.2/ in a browser.
  4. Configure channel types and ranges, communication parameters, Function Blocks, then click Save to Flash.

All settings are written immediately and permanently stored by Save to Flash; firmware upgrade, configuration export/import and factory reset are performed from the same interface. The page supports English plus a second interface language, switchable in the top-right corner.

Installation and Wiring Highlights

Mount the module on a standard 35 mm DIN rail where the status LEDs and key are visible. Supply DC 24 V to terminals 24V+ / V- with correct polarity; connect the RS485 bus to B/A with shielded twisted pair and ground the shield at one point only. Universal input channels share the common terminals G1-G3 and each has a 3-pin jumper (J7-J12): pins 2-3 for 0-10 V / NTC-10K / dry contact, pins 1-2 for 4-20 mA - the jumper must match the configured channel type. Analog outputs M1-M3 use G3 as common; each relay output Dn/Qn is an isolated contact pair to be wired in series with the load and external supply.

Packing List

1 x PIOM-633 programmable I/O module (ordered model) | 1 x product certificate | 1 x user manual

OEM / ODM Customisation

As a manufacturer we support project-specific firmware: custom control logic and Function Block presets, PID defaults, protocol behaviour, channel naming, interface language packs, branding and packaging. Send us your I/O list and control sequence and we will come back with a configuration proposal.

FAQ

What is the difference between PIOM-633-M and PIOM-633-B? Both share the same hardware. PIOM-633-M works as a Modbus RTU slave (default 9600 bps, address 1); PIOM-633-B works as a BACnet MS/TP master node (default 76800 bps, MAC 1). The protocol is fixed at the factory per model.
Can it run PID control without an extra controller? Yes. The Function Block engine runs inside the module, so PID, scaling, selection and interlock logic execute locally; the master station only reads and writes points.
Can I connect 4-20 mA sensors directly? Yes - set the channel type to 4-20 mA and move that channel's jumper (J7-J12) to pins 1-2. Other channels stay at the factory position.
How do I configure and upgrade the module? Over the RS485 port in Web configuration mode, from a browser at http://192.168.5.2/. Configuration files can be exported/imported and firmware upgraded online.
Do you support OEM/ODM and sample orders? Yes. Sample orders, custom firmware, branding and packaging are all supported - please contact us with your application details.

Compliance and Warranty

Designed and manufactured in compliance with CE (EMC) and RoHS requirements. Warranty: 12 months from purchase for quality-related faults under normal use (subject to the sales contract).

P-IOM633 / PIOM-633 programmable I/O module - BACnet MS/TP and Modbus RTU, PID control, 6 AI 3 AO 6 DI 3 relay, 24 V DC DIN-rail mounted. Please contact us for a quotation or OEM/ODM project support.

Company Details

Bronze Gleitlager

,

Bronze Sleeve Bushings

 and 

Graphite Plugged Bushings

 from Quality China Factory
  • Business Type:

    Manufacturer,Exporter

  • Year Established:

    2024

  • Total Annual:

    $1M- $5M

  • Employee Number:

    10~30

  • Ecer Certification:

    Verified Supplier

Shenzhen Qingchen Telecommunications Co., Ltd. is a manufacturer of building automation and industrial control equipment based in Bao'an District, Shenzhen. We bring together research and development, production, sales and service, supplying environmental sensors, field controllers, protocol gateway... Shenzhen Qingchen Telecommunications Co., Ltd. is a manufacturer of building automation and industrial control equipment based in Bao'an District, Shenzhen. We bring together research and development, production, sales and service, supplying environmental sensors, field controllers, protocol gateway...

+ Read More

Get in touch with us

  • Reach Us
  • Shenzhen Qingchen Telecommunications Co., Ltd.
  • 313, Kunhong Building, 38 Xinhe Avenue, Xinqiao Community, Xinqiao Subdistrict, Bao'an District, Shenzhen, China 518104
  • https://www.matinal-tech.com/

Leave a Message, we will call you back quickly!

Email

Check your email

Phone Number

Check your phone number

Requirement Details

Your message must be between 20-3,000 characters!

Submit Requirement