| Payment Terms | T/T or Western Union |
| IP Rating | IP20 |
| Emergency power | 2W(Can be customized) |
| Delivery Time | 1, Sample and small order: Within 5 working days after receiving your payment. 2, Bulk order: 3-4 weeks after receiving deposit. |
| Load output voltage | 20-60Vdc |
| Packaging Details | Packed in bubble bag firstly, and then reinforced with carton for outer packing |
| Working temprature | 0℃~50℃ |
| Supply Ability | 10,000pcs per month |
| Battery type | LifePO4 6.4V 1800mAh |
| Emergency Time | 180min (Can be customized) |
| Rated Input Voltage | 220-240Vac 50Hz /60Hz |
| Warranty | 5 Years( battery is included) |
| Model Number | KE004-02Dii180HE |
| Certification | CE, UKCA, UN38.3, MSDS |
| Brand Name | Merrytek |
| Place of Origin | China |
View Detail Information
Explore similar products
5 Years Warranty 2W 3-hour LED Emergency converter With LiFePO4 Battery self
5W LED Emergency Pack with 3 hours duration and manual test button for 5 years
3W Standard and Self Test emergency packs with 3 hours duration time and 80
High Voltage Output Power Supply Driver 50-180V LifePO4 1W Emergency Pack With 5
Product Specification
| Payment Terms | T/T or Western Union | IP Rating | IP20 |
| Emergency power | 2W(Can be customized) | Delivery Time | 1, Sample and small order: Within 5 working days after receiving your payment. 2, Bulk order: 3-4 weeks after receiving deposit. |
| Load output voltage | 20-60Vdc | Packaging Details | Packed in bubble bag firstly, and then reinforced with carton for outer packing |
| Working temprature | 0℃~50℃ | Supply Ability | 10,000pcs per month |
| Battery type | LifePO4 6.4V 1800mAh | Emergency Time | 180min (Can be customized) |
| Rated Input Voltage | 220-240Vac 50Hz /60Hz | Warranty | 5 Years( battery is included) |
| Model Number | KE004-02Dii180HE | Certification | CE, UKCA, UN38.3, MSDS |
| Brand Name | Merrytek | Place of Origin | China |
2W 3hours DALI-2 LED Emergency remote Pack Auto Testing With 5 Years Warranty
1. Description
2. Parameters
| Charge Part | KE004 | 02Dii180HE | |
| Rated input voltage | 220-240Vac 50Hz/60Hz | ||
| Rated input current | 0.06A Max. @230Vac | ||
| Input inrush current | <10A (Half current pulse width100μs) @230Vac | ||
| Power factor | ≥ 0.5@230Vac | ||
| Input power | < 4W@230Vac | ||
| Battery charging current | 250mA Max. | ||
| Battery charging time | 24 hours Max. | ||
| Emergency Part | Operating mode | Emergency mode | |
| Load type | LED | ||
| Emergency power | 2W | ||
| Emergency time | 3 hours or 1.5 hours (Set via jumper caps) | ||
| Load output current | 100-33mA | ||
| Load output voltage | 20-60Vdc | ||
| Battery | LifePO4 (The battery capacity meets the emergency time at 25℃) | 6.4V 1.8Ah | |
| Battery warranty | Warranty 5 years @25℃. | ||
| Exception Driver Requirements | Surge current | 8A | |
| Input current | 3A Max. | ||
| Output current | 2A Max. | ||
| Emergency Function Test | Auto test | Self-test function. | |
| LED Indication | Fault/ test / Status | Reason | Charge Indicator Status |
| The battery is fully charged and operational | Standard daily use | ||
| solid green | |||
| LED Indication | Fault / test / Status | Reason | Charge Indicator Status |
| Emergency mode | Battery operation | ||
| Green and red off | |||
| Function test | Periodic self-test | ||
| Flashing Green 0.3 sec on 0.3 sec off | |||
| Duration test | Periodic self-test | ||
| Flashing Green 1 sec on 1 sec off | |||
| Charging fault | Incorrect charging current | ||
| Flashing Red 0.3 sec on 0.3 sec off | |||
| Battery failure / disconnected | The battery failed the duration test or function test | ||
| Flashing Red 1 sec on 1 sec off | |||
| LED fault | Not plugged in or damaged / faulty | ||
| solid red | |||
| Inhibit mode | Inhibit mode active | ||
| Double pulsing green | |||
| Abnormal protection | Battery over-charge/deep discharge protection | Yes | |
| Output over-voltage protection | Yes | ||
| Output overload protection | Yes | ||
| Output short circuit protection | Yes | ||
|
Operating Environment |
Operating temperature/humidity | 0℃…+50℃;Humidity:20%-75%(without condensation) | |
| Storage temperature/humidity | -5℃-35℃ | ||
| Case Max. Temp(Tc) | 75℃ | ||
|
Safety & EMC
|
Withstand voltage | 3000Vac 5mA 60s (Input “L N” – output “SEC+ SEC-) | |
| Safety standard | EN61347-1, 60598-2-22, 61347-2-7, 62034 | ||
| EMC standard | EN55015, EN61000-3-2, EN61000-3-3 | ||
| DALI protocol standard | IEC62386-101 / 102 / 202 DT1 | ||
| Battery standard | UN38.3 | ||
| Environmental protection requirements | Compliant with RoHS | ||
| Certification | CE | ||
| Others | (Terminal/wiring) specification | Press terminal, wire diameter: 0.5-0.75mm2 | |
| IP rating | IP20 | ||
| Type of protection | Class II | ||
| Installation type | Built-in installation | ||
| Dimension (driver) | 146*30*22.5mm | ||
| Packaging requirement | White box+Instruction manual+clapboard+outer carton(K=A) | ||
| Weight | 80g (driver) | ||
| Lifespan | 5 Year @Ta | ||
|
Notes: All parameters are tested on the input voltage 230Vac, the environment temperature 25℃, unless otherwise specified. |
|||
3. Dimension (Unit:mm)
LED Converter:
![]()
Battery:
![]()
![]()
Fig.1: Straight-line for IFR18650 Fig.2: Parallel for IFR18650
4. Wiring Diagram
Fig.A: With LED driver(Switched) and LED module for mains and emergency operation
![]()
Fig.B: With LED driver(Unswitched) and LED module for mains and emergency operation
![]()
Fig.C: With LED driver(Switched) and separated LED modules for mains and emergency operation
![]()
Fig.D: With the LED module for non-maintained emergency operation
![]()
5. Emergency Time Setting
![]()
6. Wire Preparation
![]()
7. Automatic Test & Operation Instructions
1) Connect the wire according to the wiring diagram.
2) L,N power on, start the clock, and periodic self-test. These default times are factory pre-set, in accordance with the DALI standard EN 62386-202, to conduct an automatic function test every 7 days and a duration test every 52 weeks. Since the DELAY time is factory pre-set to Zero, all units are tested at the same time. Test times can be changed with a command over the DALI bus.
1) DALI command from a suitable control unit can be used to initiate function and duration tests at individually selected times. Status flags are set for report back and data logging of results.
2) The DELAY and INTERVAL time values must be re-set when the emergency system test times are to be scheduled by a DALI control and monitoring system.
C. Clock
1) AC power is off, and the clock lasts for 7 days, Power on and re-time. Turn off the power supply, replace the battery. The clock will Re-time.
8. Battery Application Notice
1) The battery should be recharged and discharged semiannually in normal use conditions.
2) Do not connect to the circuit when the battery is not in use to prevent over-discharge of the battery due to self-consumption of the circuit board.
3) Please keep the battery away from the heat source when installing and using, and only allowed to be used in a certain working temperature range.
4) The battery should be stored in a dry place with a moderate, stable temperature.
5) After a long-time storage, the battery is cycled every 6 months as required.
Company Details
Business Type:
Manufacturer,Exporter,Seller
Employee Number:
200~300
Ecer Certification:
Verified Supplier
Focus on intelligent lighting control and innovate constantly! About Merrytek Shenzhen Merrytek Technology Co. Ltd, founded in 2011 in Shenzhen China. For more than 13 years, we have been dedicated to research electronical products for professional lighting & smart co... Focus on intelligent lighting control and innovate constantly! About Merrytek Shenzhen Merrytek Technology Co. Ltd, founded in 2011 in Shenzhen China. For more than 13 years, we have been dedicated to research electronical products for professional lighting & smart co...
Get in touch with us
Leave a Message, we will call you back quickly!