China 10kV / 12kV High Voltage CT High Sensitivity Oil Immersed Current Transformers
China 10kV / 12kV High Voltage CT High Sensitivity Oil Immersed Current Transformers

  1. China 10kV / 12kV High Voltage CT High Sensitivity Oil Immersed Current Transformers

10kV / 12kV High Voltage CT High Sensitivity Oil Immersed Current Transformers

  1. MOQ: 1 piece
  2. Price: $120
  3. Get Latest Price
Payment Terms T/T
Supply Ability 5000 pcs
Delivery Time 20 days
Packaging Details wooden case
Name High Voltage CT
Rated Voltage 10/12kV
Structure Steel-Tank Oil-Immersed (Vacuum Treated)
Performance Thermal Stability ×187.5,-25~+40℃
Configuration Dual Winding/Ratio,0.2/0.5/3 Class
Compliance GB1208/IEC,Indoor/Outdoor,OEM/ODM
Brand Name MacweyTEK
Model Number LJWD-10.12
Certification IEC
Place of Origin Ningbo, China

View Detail Information

Inquiry by Email Get Latest Price
Chat online Now Ask for best deal
  1. Product Details
  2. Company Details

Product Specification

Payment Terms T/T Supply Ability 5000 pcs
Delivery Time 20 days Packaging Details wooden case
Name High Voltage CT Rated Voltage 10/12kV
Structure Steel-Tank Oil-Immersed (Vacuum Treated) Performance Thermal Stability ×187.5,-25~+40℃
Configuration Dual Winding/Ratio,0.2/0.5/3 Class Compliance GB1208/IEC,Indoor/Outdoor,OEM/ODM
Brand Name MacweyTEK Model Number LJWD-10.12
Certification IEC Place of Origin Ningbo, China
High Light 10kV High Voltage CT12kV High Voltage CTHigh Sensitivity Oil Immersed Current Transformers

LJWD-10.12 Oil-Immersed High Voltage Current Transformer High Sensitivity Current Transformer


Product descriptions
The LJWD-10.12 Oil-Immersed High Voltage Current Transformer is a steel-tank, oil-immersed device designed for 10kV and 12kV AC power systems (50Hz/60Hz). It is widely used for current measurement, energy metering, and relay protection in urban and rural power grids, substations, and industrial transformer stations. Built for reliability, it can operate continuously at 120% of rated current, withstand harsh outdoor conditions, and deliver long-term stable performance at altitudes up to 4000m and ambient temperatures from -25°C to +40°C.

Service conditon ·Installation: Indoor & outdoor ·Temperature: -25°C to +40°C ·Humidity: ≤95% relative humidity ·Altitude: ≤2000m (customizable up to 4000m) ·Pollution Class: Class II Construction & Features ·Oil Tank Design: Waterproof & snowproof cover, oiling valve, and diaphragm to reduce oxidation and extend service life. ·Vacuum Oil Treatment: Vacuum oil-filtering and oil-injection improve insulation and cooling efficiency. ·Thermal Stability: 187.5 times enhanced thermal stability for demanding power systems. ·Flexible Configurations: ·Single/Double secondary winding ·Single/Double ratio options ·Accuracy Classes: 0.2, 0.5, 1.3 (D) for both measurement and protection.
 
Technical Parameters ·Rated Primary Current: 5A – 1500A ·Rated Secondary Current: 5A ·Accuracy Class: 0.2, 0.5, 3 (customizable combinations) ·Rated Short-Time Thermal Current: Up to 30kA ·Rated Dynamic Current: Up to 50kA ·Rated Insulation Level: 12/42/75kV ·Standards: GB1208-1997, IEC standards

Technical Parameters Table 1
Class
Hz
Current
Ratio (A)
Secondary
Capacity
(kA)
Primary
Voltage
(kV)
Primary
Current &
Rated
Current (%)
Max.Error
Load Situation
Ratio
error%
difference
(min)
0.5
3
D
50
30/5, 40/5
50/5, 75/5
100/5, 150/5
200/5, 300/5
400/5, 600/5
1000/5, 1500/5
15
10
20
±0.75
±0.5
±50
±40
not be smaller than 15
ohms within the rated
capacity range of
25%-100%.
2. The load power factor
is Cosφ = 0.8.
Technical Parameters Table 2
Type
Class (KV)
Ratio (A)
0.2 Capacity (VA)
Continuous Protection
Weight (kg)
LJW-10,12
11,12
5 – 400/5
10 – 15
protection Without
monitoring
21
LJWD-10,12
11,12
5 – 400/5
10 – (15)
15 – (30)
28
Customization and Support: We provide tailored solutions for the LJWD-10.12 Oil-Immersed Current Transformer, including custom current ratios, accuracy classes, and output ratings to fit your specific requirements. Contact us to create a transformer designed for your operational needs.
Outline & Dimensions
·Compact single-phase, oil-immersed design for easy installation. ·Equipped with grounding bolts, oil level monitoring, and drain plug. ·Customizable tank dimensions and mounting options.
 
Customization & Support
We provide OEM / ODM customization. Please specify: ·Model & Current Ratio (e.g., LJWD-10, LJWD-12, 200/5A, 400/5A) ·Accuracy Class & Output (e.g., 0.2, 0.5, 3; 10–30VA) ·Insulation Level & Service Conditions (e.g., 12/42/75kV; temperature, altitude, pollution class) ·Additional Requirements (e.g., single/double secondary winding, grounding, customized tank design)

Company Details

Bronze Gleitlager

,

Bronze Sleeve Bushings

 and 

Graphite Plugged Bushings

 from Quality China Factory
  • Business Type:

    Manufacturer,Distributor/Wholesaler,Exporter

  • Year Established:

    2013

  • Total Annual:

    $31000000-$35000000

  • Employee Number:

    >218

  • Ecer Certification:

    Verified Supplier

Ningbo Macwey Industrial Technology Co., Ltd. is a manufacturer specializes in R&D ,manufacturing and sales of MV&HV switching equipment and electrical accessories,which applied in voltage range from 10kV to 40.5kV, widely used in power transmission and distribution.The company is lo... Ningbo Macwey Industrial Technology Co., Ltd. is a manufacturer specializes in R&D ,manufacturing and sales of MV&HV switching equipment and electrical accessories,which applied in voltage range from 10kV to 40.5kV, widely used in power transmission and distribution.The company is lo...

+ Read More

Get in touch with us

  • Reach Us
  • Ningbo Macwey Industrial Technology Co.,Ltd
  • No.218, Weier Road, Chongshou Industrial Park, Cixi City (Ningbo), China
  • https://www.mv-switchgears.com/

Leave a Message, we will call you back quickly!

Email

Check your email

Phone Number

Check your phone number

Requirement Details

Your message must be between 20-3,000 characters!

Submit Requirement