| Phase Conductor | Electrolytic copper 99.95 percent, silver plated joints |
| Supply Ability | 20000 Meters per Month |
| Peak Withstand Current (Ipk) | 220kA |
| Delivery Time | 15-25 working days after drawing approval |
| Payment Terms | T/T, L/C at sight, Western Union |
| Rated Insulation Voltage | 1000V AC |
| Dielectric Withstand | 3.5kV 1min power frequency |
| Packaging Details | Seaworthy plywood case with moisture barrier film, joint kits and end covers packed separately |
| Rated Working Voltage | 690V AC |
| Temperature Rise | Less than or equal to 30K at rated current |
| Protection Degree | IP54 indoor, IP68 option |
| Rated Current Range | 1250A - 6300A |
| Conditional Short-Circuit Withstand (Icw) | 100kA / 1s |
| Test Standard | IEC 61439-6 / UL 857 / GB 7251.6 |
| Rated Frequency | 50 / 60 Hz |
| Conductor Insulation | Epoxy powder coated, Class F 155 C |
| Integral Earth Conductor | 50 percent of phase cross section, full length continuity |
| Certification | ISO 9001 / UL 857 / IEC 61439 / CNAS / CMA |
| Place of Origin | Guangdong, China |
| Brand Name | ohory |
| Model Number | OH-DCB-ICW100 |
View Detail Information
Explore similar products
2000A-6300A Low Temperature Rise Busway System with High-Conductivity Copper for
Vertical Riser Busway System 800A-3200A Main Feeder with High-Conductivity
AI+ Intelligent Busway System with Low Temperature Rise ≤ 30K and Molecular
Fire Resistant Busway System with Low Smoke Halogen Free Insulation for AI Data
Product Specification
| Phase Conductor | Electrolytic copper 99.95 percent, silver plated joints | Supply Ability | 20000 Meters per Month |
| Peak Withstand Current (Ipk) | 220kA | Delivery Time | 15-25 working days after drawing approval |
| Payment Terms | T/T, L/C at sight, Western Union | Rated Insulation Voltage | 1000V AC |
| Dielectric Withstand | 3.5kV 1min power frequency | Packaging Details | Seaworthy plywood case with moisture barrier film, joint kits and end covers packed separately |
| Rated Working Voltage | 690V AC | Temperature Rise | Less than or equal to 30K at rated current |
| Protection Degree | IP54 indoor, IP68 option | Rated Current Range | 1250A - 6300A |
| Conditional Short-Circuit Withstand (Icw) | 100kA / 1s | Test Standard | IEC 61439-6 / UL 857 / GB 7251.6 |
| Rated Frequency | 50 / 60 Hz | Conductor Insulation | Epoxy powder coated, Class F 155 C |
| Integral Earth Conductor | 50 percent of phase cross section, full length continuity | Certification | ISO 9001 / UL 857 / IEC 61439 / CNAS / CMA |
| Place of Origin | Guangdong, China | Brand Name | ohory |
| Model Number | OH-DCB-ICW100 | ||
| High Light | 100kA busway system ,1250A-6300A busway with integral earth ,AI data center power backbone | ||
The OH-DCB-ICW100 series is built for AI data centers where available fault current at the main distribution board exceeds the withstand rating of conventional busway. A verified 100kA conditional short-circuit withstand and a 220kA peak withstand let the run hold selectivity with upstream breakers without oversizing the power train, while the integral earth conductor keeps fault return paths continuous through every joint.
| Rated Current Range | 1250A - 6300A |
|---|---|
| Conditional Short-Circuit Withstand (Icw) | 100kA / 1s |
| Peak Withstand Current (Ipk) | 220kA |
| Rated Insulation Voltage | 1000V AC |
| Rated Working Voltage | 690V AC |
| Rated Frequency | 50 / 60 Hz |
| Phase Conductor | Electrolytic copper 99.95 percent, silver plated joints |
| Integral Earth Conductor | 50 percent of phase cross section, full length continuity |
| Conductor Insulation | Epoxy powder coated, Class F 155 C |
| Temperature Rise | Less than or equal to 30K at rated current |
| Dielectric Withstand | 3.5kV 1min power frequency |
| Protection Degree | IP54 indoor, IP68 option |
| Test Standard | IEC 61439-6 / UL 857 / GB 7251.6 |
Each production batch undergoes power frequency dielectric tests, insulation resistance measurement and contact resistance verification. Type test reports covering short circuit withstand, temperature rise and fire performance are available for consultant submittals.
Please specify rated current, run length, number of tap off positions, protection degree, earth conductor requirement and the fault level from your coordination study.
Company Details
Business Type:
Manufacturer,Exporter
Year Established:
2015
Total Annual:
800000-1000000
Employee Number:
100~200
Ecer Certification:
Verified Supplier
OHORY ELECTRIC, established in 2009, is a large-scale, high-tech enterprise specializing in research and development, production, sales, and service. The industrial base spans 40,000 square meters, with 12,000 square meters dedicated to the production facility. Our corporate ... OHORY ELECTRIC, established in 2009, is a large-scale, high-tech enterprise specializing in research and development, production, sales, and service. The industrial base spans 40,000 square meters, with 12,000 square meters dedicated to the production facility. Our corporate ...
Get in touch with us
Leave a Message, we will call you back quickly!