| Payment Terms | T/T, Western Union, Paypal |
| Supply Ability | 8,000 sets per month |
| Delivery Time | 20-30 working days |
| Packaging Details | Wooden case |
| DC Maximum capacity | 18kW |
| Installation mode | Installed on 19-inch rack, embedded in cabinet |
| Rectifier module | 3000W |
| AC input voltage | 220VAC single-phase |
| Output voltage | -43~-58VDC, rated value: -53.5VDC |
| Protection level | IP20 |
| Brand Name | ESTEL |
| Model Number | ET48300-005 |
| Certification | ISO9001, CE, 3C, FCC, TLC, IP55 |
| Place of Origin | China |
View Detail Information
Explore similar products
220VAC Rectifier System Up To 3.48kW With RS485 For Telecom Applications
Rack Mounted 4U CCC Rectifier Module Telecom
DIN Rail 5U Telecom Rectifier With 10 Way Circuit Breakers
1000VA Inverter DC48V Rectifier Used In Telecommunication
Product Specification
| Payment Terms | T/T, Western Union, Paypal | Supply Ability | 8,000 sets per month |
| Delivery Time | 20-30 working days | Packaging Details | Wooden case |
| DC Maximum capacity | 18kW | Installation mode | Installed on 19-inch rack, embedded in cabinet |
| Rectifier module | 3000W | AC input voltage | 220VAC single-phase |
| Output voltage | -43~-58VDC, rated value: -53.5VDC | Protection level | IP20 |
| Brand Name | ESTEL | Model Number | ET48300-005 |
| Certification | ISO9001, CE, 3C, FCC, TLC, IP55 | Place of Origin | China |
| High Light | Rectifier Power System With Battery Monitor ,Rectifier Power System With Power Distribution ,18kW Capacity Rectifier Power System | ||
18kW Capacity Rectifier Power System with Power distribution and Battery Monitor Function
18kW Capacity Rectifier Power System with Power distribution and Battery Monitor Function
ET48300-005 sub-rack power supply 5U height compact design to meet critical application needs of fiber and microwave transmission,
access device, switch. The system maximum power is 300A, with AC / battery / load MCBs.
The cables are front accessing with MCB and busbar.
> Standard 19-inch width which has the advantage of wide use
> 5U height compact design, space and installation cost can be saved
> Front operation and cable accessing, good-looking and safe maintenance
> Perfect battery management, prolongs the life of the battery well provide various communication ports,
RS485, internet port, dry contacts, etc. which enables flexible networking and remote monitoring
> Rectifier and controller are hot pluggable, easy and quick on-line maintenance
> Wide input voltage range(85-300Vac) the power grid is adaptable
ET48300-005 consists of distribution unit, rectifier module, conversion module, monitoring module.
The configuration is optional, as table below:
| Configuration | Rectifier module | Remark |
| Standard | GB 4943 | For details, please refer to the specifications of modules |
| Standard | IEC/EN 62368-1 | |
| Standard | EN 55032 Class A,GR1089 Issue 4 ,R3-10, R3-11, R3-12 Class B certified by North America | |
| Standard | EN300386,CLASSA |
18kW Capacity Rectifier Power System with Power distribution and Battery Monitor Function
System Configuration
![]()
Two operating methods:
(1) AC input: Startup rectifier module after AC powered-on, outputs -48Vdc, at the same time charge the battery and power the conversion module, conversion module outputs 220Vac.
Under normal conditions, the parameters of rectifier module and distribution unit are all under controll of the monitoring module, operating according to the preset parameters or user’s commands. If AC mains fault, the battery will power to the system, and continue outputing - 48 VDC and 220 vac, with the discharge of the battery, the voltage of the battery starts to descend, when the voltage is under 43.2 V + / - 0.5 V, the monitoring module send battery under-voltage signal and close the load output directly, then the power system will stop working. When external AC mains recovers, the system will normally work again. (All above monitoring data are system default values and can be reset by user)
(2) -48V input: No AC current or no AC be connected, access external power -48V to -48V load port, startup monitoring and conversion module, 220Vac output.
Temperature compensation function is on by default, which can be activated or forbiddened by user’s command if necessary. Operation temperature ≥55℃, the power output of the power supply will be linearly reduced (@65℃,output power will be 1300W).
Specifications
| Type | ET48300-005 | |
| System | Dimension | 482.0(W)*350.0(D)*5U(H) |
| Weight | ≤25kg(withoutrectifiers) | |
| Coolingmode | Naturalcooling | |
| Installationmode | Installedon19-inchrackorinsidethecabinet | |
| Cablingmode | Topinletandtopoutlet | |
| Maintenancemode | Frontmaintenance,supportmodulegradechange | |
| Protectionlevel | IP20 | |
| AC Distribution | Inputmode | 220VACsingle-phase |
| Inputcapacity | 1×100A/2P | |
| Inputfrequency | 45~65Hz,ratedvalue:50Hz/60Hz | |
| ACSPD | 20kA/40kA,8/20μs | |
| DC Distribution | Outputvoltage | -43~-58VDC,ratedvalue:-53.5VDC |
| Maximumcapacity | 18kW | |
| Batterybreakers | 2×125A/1P | |
| Loadbreakers | LLVD:32A/1P×2+40A/1P×2+63A/1P×3 | |
| BLVD:6A/1P×2+10A/1P×2+16A/1P×2 | ||
| DCSPD | 10kA/,8/20μs | |
| Rectifier | Inputvoltage | 85VAC~300VAC,rated220VAC |
| Efficiency | >96% | |
| Ratedpower | 3000W(176~300VAC) | |
| Workingtemperature | -40℃~+75℃(fullyoutputbelow50℃) | |
| Dimension | 106.5mm(W)×286mm(D)×41.5mm(1U/H) | |
| Weight | ≤2kg | |
| Coolingmode | Forcedcooling | |
| Powerfactor | ≥0.99 | |
| THD | ≤5% | |
| Controller | Signalinput | 4AI(3Batterytemp.,1ambienttemp),7DI(SPD,6commonDI) |
| Alarmoutput | 6drycontact | |
| Communicationport | RS485,SNMP | |
| Displaymode | LCD | |
| Environment | Operating | -40℃~+75℃(fullyoutputbelow50℃) |
| temperature | ||
| Storagetemperature | -40℃~+70℃ | |
| Operatinghumidity | 5%~95%(non-condensing) | |
| Altitude | 0~3000m(Ifthealtitudeiswithintherangeof2000mto3000m,themaximumoperating | |
| temperaturedecreasesby1℃asthealtitudeincreasesby200m.) | ||
Application
(1) Integration access
(2) Indoor distribution and extension system
(3) Mobile station and extension coverage system
(4) WLAN
(5) Satellite communication ground station and microwave communication station
(6) Weak current distribution room
(7) Other AC/DC uninterruptible power system
(1) Two outputs:-48Vdc, 220Vac
(2) Two inputs:-48Vdc, 220Vac
(3) Adoption of active power factor compensation technology, power factor >0.99
(4) Wide operating range of AC input voltage: 90~280Vac
(5) Wide operating temperature range:-5℃~+55℃
(6) Switch technology conducted,
(7) Perfect battery management prolongs battery lifetime: charge /discharge management, battery temperature compensation, low-voltage protection.
(8) Hot-swappable
(9) Input over/under voltage protection
(10) Output over-voltage protection, output over-current protection, output short-circuit protection
(11) Embedded / wall mounted
(12) RS485, RS232 communication interface
Payment & Shipping Terms:
| Minimum Order Quantity: | 1 set |
| Price: | negotiation |
| Payment Terms: | L/C, D/A, D/P,T/T, Western Union |
| Supply Ability: | 20,000 sets per month |
| Delivery Time: | 7-10 working days |
| Packaging Details: | carton/wooden case |
Company Details
Business Type:
Manufacturer,Distributor/Wholesaler,Exporter
Year Established:
2002
Total Annual:
15 Million-20 Million
Employee Number:
101~200
Ecer Certification:
Verified Supplier
Introduction Tianjin Estel Electronic Science and Technology Co., Ltd (ESTEL(GUANGDONG) TECHNOLOGY CO., LTD), located in China, is a professional supplier of integrated outdoor telecom cabinet and temperature control solutions for outdoor telecom base station. As a science and technolo... Introduction Tianjin Estel Electronic Science and Technology Co., Ltd (ESTEL(GUANGDONG) TECHNOLOGY CO., LTD), located in China, is a professional supplier of integrated outdoor telecom cabinet and temperature control solutions for outdoor telecom base station. As a science and technolo...
Get in touch with us
Leave a Message, we will call you back quickly!