| Conductor (×1, PE) | Bare annealed copper, Class 5 fine-stranded flexible, typical 475×∅0.63 mm (150 mm²), conductor Ø ≈ 15.5–17.5 mm |
| Metallic sheath | Continuous seam-welded corrugated copper tube; acts as armour + water barrier + PE |
| Approx. weight | 13.0 – 16.0 kg/m (13000–16000 kg/km) |
| Packaging Details | General Packaging or As Requirements |
| Number of cores | 5 (4+1) |
| Conductor diameter (approx., power) | 17.5–19.5 mm |
| Inner bedding | Mineral fire-resistant filler (MgO-based or mica tape wrap) |
| Design weight | ≈ 14500 kg/km |
| Diameter over insulated core (PE) | 18.7–20.7 mm |
| Cable shape | Round |
| Conductor diameter (approx., PE) | 15.5–17.5 mm |
| Supply Ability | 100000 meters per month |
| Conductor construction (power) | 925×∅0.50 mm (typical) |
| Insulation thickness | 1.8 mm (power cores, 185 mm²); 1.6 mm (PE core, 150 mm²) |
| Assembly | Five insulated cores with mineral fire-resistant fillers twisted together (round) |
| Outer covering | None required (copper sheath exposed); optional PVC/LSZH paint coating for corrosion protection |
| Conductor nominal area (power) | 185 mm² |
| Conductor (×4, power) | Bare annealed copper, Class 5 fine-stranded flexible, typical 925×∅0.50 mm (185 mm²), conductor Ø ≈ 17.5–19.5 mm |
| Sheath wall thickness | Copper tube wall ≈ 1.3–1.5 mm (corrugated) |
| Conductor nominal area (PE) | 150 mm² |
| Armour | Copper sheath provides equivalent of armour |
| Payment Terms | L/C,T/T |
| Conductor class | Class 5 flexible |
| Diameter over insulated core (power) | 21.1–23.1 mm |
| Screen | Copper sheath provides electromagnetic shielding |
| Overall cable diameter | 50 – 58 mm |
| Design outer diameter | ≈ 53.6 mm |
| Delivery Time | Less than 15 days |
| Conductor construction (PE) | 475×∅0.63 mm (typical) |
| Insulation (×5) | Fire-resistant mica tape + XLPE (or ceramic silicone rubber); colours: brown/black/grey (L1/L2/L3), blue (N), green/yellow (PE) |
| Model Number | BTTRZ 4x185mm²+1x150mm² |
| Certification | CE/ISO/CCC |
| Brand Name | TONGDU |
| Place of Origin | China |
View Detail Information
Explore similar products
BTTRZ X50mm2+1x25mm2 Fire Resistant Cable Mineral Emergency Power Copper
BTTRZ 0.6/1kV 4x50mm²+1x25mm² Fire-resistant Cable for Industrial Emergency
Fire Resistant Cable BTTRZ 4x50mm²+1x25mm² Mineral Insulated 0.6/1kV
4+1 Core BTTRZ 4x16mm²+1x10mm² Mineral Insulated Fire Resistant Cable 0.6/1kV
Product Specification
| Conductor (×1, PE) | Bare annealed copper, Class 5 fine-stranded flexible, typical 475×∅0.63 mm (150 mm²), conductor Ø ≈ 15.5–17.5 mm | Metallic sheath | Continuous seam-welded corrugated copper tube; acts as armour + water barrier + PE |
| Approx. weight | 13.0 – 16.0 kg/m (13000–16000 kg/km) | Packaging Details | General Packaging or As Requirements |
| Number of cores | 5 (4+1) | Conductor diameter (approx., power) | 17.5–19.5 mm |
| Inner bedding | Mineral fire-resistant filler (MgO-based or mica tape wrap) | Design weight | ≈ 14500 kg/km |
| Diameter over insulated core (PE) | 18.7–20.7 mm | Cable shape | Round |
| Conductor diameter (approx., PE) | 15.5–17.5 mm | Supply Ability | 100000 meters per month |
| Conductor construction (power) | 925×∅0.50 mm (typical) | Insulation thickness | 1.8 mm (power cores, 185 mm²); 1.6 mm (PE core, 150 mm²) |
| Assembly | Five insulated cores with mineral fire-resistant fillers twisted together (round) | Outer covering | None required (copper sheath exposed); optional PVC/LSZH paint coating for corrosion protection |
| Conductor nominal area (power) | 185 mm² | Conductor (×4, power) | Bare annealed copper, Class 5 fine-stranded flexible, typical 925×∅0.50 mm (185 mm²), conductor Ø ≈ 17.5–19.5 mm |
| Sheath wall thickness | Copper tube wall ≈ 1.3–1.5 mm (corrugated) | Conductor nominal area (PE) | 150 mm² |
| Armour | Copper sheath provides equivalent of armour | Payment Terms | L/C,T/T |
| Conductor class | Class 5 flexible | Diameter over insulated core (power) | 21.1–23.1 mm |
| Screen | Copper sheath provides electromagnetic shielding | Overall cable diameter | 50 – 58 mm |
| Design outer diameter | ≈ 53.6 mm | Delivery Time | Less than 15 days |
| Conductor construction (PE) | 475×∅0.63 mm (typical) | Insulation (×5) | Fire-resistant mica tape + XLPE (or ceramic silicone rubber); colours: brown/black/grey (L1/L2/L3), blue (N), green/yellow (PE) |
| Model Number | BTTRZ 4x185mm²+1x150mm² | Certification | CE/ISO/CCC |
| Brand Name | TONGDU | Place of Origin | China |
| High Light | 1x150mm2 fire resistant cable ,fire resistant cable 0.6kv ,1kv mineral insulated copper cable | ||
Super Fire Cable BTTRZ 4x185mm²+1x150mm² Mineral Insulated 0.6/1kV Fire Resistant
|
Code |
Meaning |
|---|---|
|
BTTRZ |
B = Wiring cable (fixed installation); T = Copper conductor (flexible); T = Copper sheath (corrugated welded tube); R = Flexible; Z = Heavy-duty (mineral insulated) |
|
0.6/1 kV |
Rated voltage U₀/U = 0.6/1 kV; Uₘ = 1.2 kV |
|
4×185 mm² + 1×150 mm² |
Four power cores 185 mm² + one protective earth core 150 mm² (5-core, 4+1 configuration) |
Construction: Flexible mineral-insulated fire-resistant cable, corrugated copper tube sheath, round profile (5-core)
Note: BTTRZ employs Class 5 fine-stranded flexible copper conductors. Each core is insulated with fire-resistant mica tape plus XLPE (or ceramic silicone rubber). Cores are assembled with mineral fillers and enclosed in a continuously welded corrugated copper tube sheath, which serves simultaneously as armour, water barrier, and PE conductor. The 4+1 configuration is designed for TN-S three-phase five-wire systems; the PE conductor is 150 mm². Per GB/T 16895 / IEC 60364, for phase conductor S > 35 mm², PE ≥ S/2. Since phase = 185 mm², S/2 = 92.5 mm², thus PE = 150 mm² exceeds the minimum requirement and is fully compliant (many projects specify PE = phase or PE ≈ 0.8×phase for added safety margin).
![]()
![]()
1. Product Overview & Rating Summary. BTTRZ 4×185+1×150 is a flexible mineral-insulated fire-resistant power cable rated 0.6/1 kV (Um = 1.2 kV) at 50 Hz, built around four 185 mm² tinned-copper Class 5 flexible phase conductors and one 150 mm² neutral/earth conductor. Unlike rigid magnesium-oxide mineral-insulated cables, BTTRZ uses mica-tape wrapped insulation enclosed in a continuously corrugated copper tube, then jacketed in a low-smoke zero-halogen (LSZH) outer sheath. The cable maintains circuit integrity for at least 90 minutes at 950 °C open-flame exposure (GB/T 19216.21 / IEC 60331-21). Finished diameter is about 60 mm and nominal mass about 5900 kg/km (≈ 590 kg per 100 m), supplied on 500 m or 1000 m wooden-steel drums. With four 185 mm² cores loaded, the cable carries about 425 A in free air at 25 °C (engineering estimate), making it the standard fire-rated main feeder for super-high-rise building main incoming fire-resistant cables, central emergency switchboard main bus ties and critical life-safety power circuits in major infrastructure.
2. Layer-by-Layer Construction (Conductor to Outer Jacket).
| Layer | Construction | Wall | Diameter |
|---|---|---|---|
| Conductor (Cu) ×5 | Tinned annealed Cu, Class 5 — 1500×0.40 mm (185 mm², ×4) + 1225×0.40 mm (150 mm², ×1) | — | ≈ 20.5 / ≈ 18.5 mm |
| Mica-tape insulation ×5 | Muscovite/phlogopite mica tape, overlapping wrap, glass-fibre reinforced | ≈ 0.7 mm | ≈ 21.9 / ≈ 19.9 mm per core |
| Filler & binder | Fire-resistant glass-fibre rope + glass-fibre binder tape | — | ≈ 54 mm bundle |
| Corrugated Cu sheath | Continuously corrugated (spiralled) copper tube, longitudinal welded | ≈ 0.5 mm | ≈ 55 mm |
| LSZH outer jacket | Low-smoke zero-halogen polyolefin, flame-retardant, orange/red | 2.6 mm | ≈ 60 mm (finished) |
3. Electrical Characteristics. Each 185 mm² phase conductor is held to a maximum DC resistance of 0.0991 Ω/km at 20 °C, rising to about 0.129 Ω/km at the 90 °C operating point. The 150 mm² neutral/earth conductor holds R ≤ 0.124 Ω/km at 20 °C. Every length survives the routine 3.5 kV AC power-frequency proof held for five minutes. Finished-cable insulation resistance remains above 36.7 MΩ·km (mica-rated, very high), and typical figures include per-core capacitance ≈ 0.75 μF/km and 50 Hz AC impedance ≈ 0.0991 Ω/km. With four 185 mm² cores energised, reference loading is about 425 A in free air at 25 °C.
|
Property |
Value |
|---|---|
|
Material |
XLPE (cross-linked polyethylene) or ceramic silicone rubber over mica tape |
|
Nominal thickness |
1.8 mm (power), 1.6 mm (PE) |
|
Long-term service temp. |
90 °C (XLPE) / 125 °C (ceramic silicone) |
|
Short-circuit temp. (≤5 s) |
250 °C (XLPE), 350 °C (ceramic) |
|
Emergency overload temp. |
130 °C |
|
Fire survival |
950 °C / 180 min (GB/T 19216.21, IEC 60331) |
|
Routine test voltage |
3.5 kV AC / 5 min |
|
Type-test voltage |
6.5 kV AC |
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
Uₘ = 1.2 kV |
|
Test voltage AC (5 min) |
3.5 kV |
Routine |
|
Type-test voltage |
6.5 kV |
— |
|
DC resistance @20 °C (power core) |
≤ 0.0991 Ω/km |
GB/T 3956 Class 5 max, 185 mm² |
|
DC resistance @20 °C (PE core) |
≤ 0.124 Ω/km |
GB/T 3956 Class 5 max, 150 mm² |
|
AC resistance @90 °C (est., power) |
≈ 0.127 Ω/km |
per core |
|
AC resistance @90 °C (est., PE) |
≈ 0.158 Ω/km |
per core |
|
Current rating in air (single-phase, 30 °C) |
≈ 370 – 440 A |
per core |
|
Current rating (design, per power core) |
≈ 390 A |
GB/T 16895 / manufacturer data |
|
Current rating (3-phase+N+PE, balanced) |
≈ 280 – 390 A per phase |
derated due to bundling |
|
Direct buried |
Applicable (copper sheath waterproof) |
— |
|
Short-circuit current (1 s, Cu, 250 °C) |
≈ 18.5 kA (18500 A) |
185 mm² |
|
Short-circuit current (1 s, Cu, 250 °C, PE) |
≈ 15.0 kA (15000 A) |
150 mm² |
|
Frequency |
50/60 Hz AC |
— |
Reference values: 185 mm² at 390 A, 3-phase 400 V → max balanced load ≈ 270.6 kW. Voltage drop at 390 A ≈ 1.5 V/km per core (≈0.38% per 100 m).
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C |
|
Emergency overload temp. |
130 °C |
|
Min. installation ambient temp. |
−20 °C (flexible construction) |
|
Service ambient range |
−20 °C to +90 °C |
|
Fire survival |
950 °C / 180 min (circuit integrity maintained) |
4. Thermal Response & Flame Behaviour. Mica insulation sustains a 90 °C continuous conductor temperature, with short-circuit capability up to 250 °C for ≤ 5 s. The cable is rated for service ambients between −15 and +70 °C. The defining property is fire resistance: under GB/T 19216.21 / IEC 60331-21, the cable maintains circuit integrity at rated voltage for at least 90 minutes when directly exposed to a 950 °C open flame. The corrugated copper sheath provides both a fire barrier and a mechanical shield against flame penetration. The LSZH outer jacket emits low smoke and no acid gas (halogen-free), meeting the requirements for tunnels, metro systems, hospitals and high-rise public buildings.
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
GB/T 18380.33 Category B (ZB available) |
|
Halogen content |
Zero halogen (IEC 60754-1) |
|
Smoke density |
Low smoke (IEC 61034, light transmittance >60%) |
|
Corrosivity |
Non-corrosive (IEC 60754-2) |
|
Fire survival (circuit integrity) |
950 °C / 180 min (IEC 60331) |
|
Toxicity |
Low toxicity (IEC 62821) |
5. Installation Practice & Handling. Bends must not fall below 15 times the actual outer diameter — about 900 mm for this size. The corrugated copper sheath must be earthed at both ends to provide protective-earth continuity. Special sealing glands and termination kits are required at both ends to keep moisture out of the hygroscopic mica layer — improperly terminated ends are the most common failure point on mineral-insulated cables. Reels held below 0 °C in storage must be warmed indoors before uncoiling. The 425 A reference requires derating whenever ambient temperature, grouping or burial depth deviates from reference conditions. At about 590 kg per 100 m, the cable requires drum jacks, rated pulling gear and at least six fitters.
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 6 × OD → ≈ 322 mm at Ø53.6 mm |
flexible installation |
|
Max. pulling tension |
11500 N |
use proper grips on copper sheath |
|
Direct burial |
Suitable |
copper sheath waterproof; add PVC paint for soil corrosion protection |
|
Conduit ID |
≥ 1.5 × OD → ≥ 80 mm; use 100 mm or 110 mm |
— |
|
Fixing |
heavy-duty cable clamps, stainless steel ties (compatible with copper sheath) |
— |
|
Flexing |
suitable for fixed installation with limited flexing during installation |
not for continuous flexing |
|
Impact resistance |
High |
corrugated copper tube absorbs mechanical shock |
|
Water resistance |
Excellent |
continuous welded copper tube |
6. Typical Service Applications. This 4×185+1×150 BTTRZ cable is the fire-rated main feeder for very large emergency and safety-critical circuits: main fire-pump and sprinkler-pump feeds up to about 108 kW, main smoke-exhaust and pressurisation fan feeds up to about 28 kW, central emergency switchboard main incoming cables, fire-alarm system main power bus ties, emergency elevator main power supply, hospital central emergency switchboard main feeders, metro and tunnel emergency power main distribution, super-high-rise building fire-fighting main risers, data-centre UPS main emergency feeders, oil and gas platform fire-resistant power cables, stadium and large-venue emergency main distribution, industrial furnace and oven emergency main power, and any circuit where continued operation during a 90-minute fire event is mandated by building code. Approved installation methods include heavy-duty cable tray, direct tray in fire-protected zones, and fire-rated conduit.
![]()
7. Testing & Quality Assurance Regime. Routine tests on every length include conductor DC resistance verification (185 mm² ≤ 0.0991; 150 mm² ≤ 0.124 Ω/km) at 20 °C, the 3.5 kV AC / 5 min withstand, insulation resistance ≥ 36.7 MΩ·km, conductor continuity across all five cores, corrugated copper sheath electrical continuity, and dimensional inspection covering mica ≈ 0.7 mm, Cu sheath ≈ 0.5 mm, LSZH jacket ≥ 2.6 mm and overall diameter ≈ 60 mm. Sample and type tests comprise the 950 °C / 90 min fire-resistance test (GB/T 19216.21), vertical flame spread GB/T 18380.34 class A, smoke density GB/T 17651, halogen acid gas content GB/T 17650, sheath moisture-tightness / water-immersion leak test, bending at ≥ 15 × OD, short-circuit to 250 °C, and voltage re-test after fire exposure. A factory test certificate accompanies each drum.
Cable Parameters
![]()
Cable Test Parameters
![]()
Cable Cross Section Structure
![]()
![]()
Cable Construction Description
![]()
8. Standards & Conformity. Design and production are governed by GB/T 19216.21 / IEC 60331-21 for fire-resistance (950 °C / 90 min), GB/T 19666-2019 for flame-retardant and fire-resistant cable classification, and GB/T 12706.1-2020 for low-voltage power cables at 0.6/1 kV. Conductors satisfy GB/T 3956 Class 5. General test methods follow GB/T 19216 series and GB 5023. Surface marking complies with GB/T 6995. The LSZH jacket meets halogen-free requirements per GB/T 17650. Cables can also be supplied to IEC 60331, BS 5839, BS 7621 or NEK 606 requirements on request.
9. Packaging, Storage & Logistics. Standard delivery is 500 m or 1000 m per wooden-steel drum, with bespoke cut lengths available on request. Each drum carries type, voltage, size, supplier identity, production year and sequential metre marking per GB/T 6995. Storage should be in dry, covered premises at −15 to +40 °C, shielded from direct sunlight, moisture, oils and sharp objects; drum end seals must remain intact until installation. Because mica is hygroscopic, any drum whose end seal has been damaged must be re-tested for insulation resistance before use. During transit, drums must be secured against rolling and impact.
10. Procurement Specification. State "BTTRZ 0.6/1 kV 4×185+1×150" together with the required length or drum arrangement, and specify whether the corrugated copper sheath is to be used as the protective earth (PE) or whether a separate green-yellow 150 mm² conductor is required. Always order the matching sealing gland and termination kit at both ends. Always request the factory test certificate, which must include the 950 °C / 90 min fire-resistance report, to confirm the actual diameter (≈ 60 mm), weight (≈ 5900 kg/km) and conductor resistances for the production batch.
11. Cable Industry FAQ.
Company Details
Business Type:
Manufacturer,Exporter,Trading Company
Year Established:
2009
Total Annual:
50000000-100000000
Employee Number:
260~300
Ecer Certification:
Verified Supplier
Company Profile — Anhui Tongdu Cable Co., Ltd. Company Overview Anhui Tongdu Cable Co., Ltd. (hereinafter "Tongdu Cable") is a professional wire and cable manufacturer headquartered in Zongyang Economic Development Zone, Anhui Province, China. Founded in 2009, the company has grown into one of... Company Profile — Anhui Tongdu Cable Co., Ltd. Company Overview Anhui Tongdu Cable Co., Ltd. (hereinafter "Tongdu Cable") is a professional wire and cable manufacturer headquartered in Zongyang Economic Development Zone, Anhui Province, China. Founded in 2009, the company has grown into one of...
Get in touch with us
Leave a Message, we will call you back quickly!