HXGN customized economic medium voltage 6kv ring main unit panel
- Compact modular design
 - Simple structure, small volume and light weight
 - Ease and flexible for installation
 - Reliable and safe to operate
 - Low operating cost
 
It is a new product self-designed and self-developed by introducing oversea advanced techniques and the requirements of rural and urban power network reform. The core parts are load switch, switch-fuse combinations or circuit breaker.
It is applicable to the ring network or terminal power supply system with three-phase AC 50Hz, rated voltage of 12kV, rated current of up to 630A. It is widely used in the load center powder distribution station of urban residential area, high-rise building, large public buildings, factories and enterprises as power receiving and distribution or overload protection, short circuit protection; As a ring network power supply unit and terminal equipment, it plays role in the power distribution, power controlling and electrical equipment protection, so it is widely installed in prefabricated substations.
- Ambient air temperature : -5°C ~ +40°C;
 - Daily average temperature(Within 24h): ≤+35℃
 - Altitude:≤1000m;
 - Relative humidity: within 24h, daily average value ≤ 95% , daily average vapor pressure≤ 2.2KPa; monthly average value ≤ 90%, monthly average vapor pressure≤ 1.8KPa
 - Ambient air is not significantly polluted by dust, smoke, corrosive and / or flammable gas, vapor or salt contamination.
 
If the switchgear will be used in conditions that exceed the normal environmental conditions, users should consult with the manufacturer.
Item(Unit)  | Data  | |
Load Switch  | Switch-fuse Combinations  | |
Rated Voltage(kV)  | 12  | |
Rated Current(A)  | 630  | 125  | 
Rated Frequency(Hz)  | 50  | |
Rated Short-time Power Frequency Withstand Voltage(kV)  | 42  | |
Rated Lightning Impulse Withstand Voltage(kV)  | 75  | |
Rated Peak Withstand Current(kA)  | 20  | 
  | 
4S Rated Short-time Withstand Current(kA)  | 50  | 
  | 
Rated Short-circuit Making Current(kA)  | 50  | 80  | 
Rated Power load Drop-out Current(A)  | 630  | 
  | 
Rated Short-circuit Drop-out Current(kA)  | 
  | 31.5  | 
Rated Transfer Current(A)  | 
  | 1700  | 
Standard  | GB3906,GB3804  | GB3906,GB12926  | 
Protection Degree  | ≤IP3X  | |
![]()
![]()
![]()