China High Voltage Partial Discharge Testing System 150kV 20kVA for Transformer
China High Voltage Partial Discharge Testing System 150kV 20kVA for Transformer

  1. China High Voltage Partial Discharge Testing System 150kV 20kVA for Transformer
  2. China High Voltage Partial Discharge Testing System 150kV 20kVA for Transformer
  3. China High Voltage Partial Discharge Testing System 150kV 20kVA for Transformer

High Voltage Partial Discharge Testing System 150kV 20kVA for Transformer

  1. MOQ: 1
  2. Price:
  3. Get Latest Price
Delivery Time 30 work days
Applicable Voltage Level 10kV‑35kV
Measurement Sensitivity 0.01pC
System Partial Discharge Level ≤2pC at 100% rated voltage
Rated Capacity 20kVA
Payment Terms T/T,L/C
Rated Output Voltage 150kV
Packaging Details plywood case
Operating Frequency 45‑200Hz
Model Number SXJFT
Brand Name Sansion
Place of Origin China
Certification CE SGS ISO9001

View Detail Information

Inquiry by Email Get Latest Price
Chat online Now Ask for best deal
  1. Product Details
  2. Company Details

Product Specification

Delivery Time 30 work days Applicable Voltage Level 10kV‑35kV
Measurement Sensitivity 0.01pC System Partial Discharge Level ≤2pC at 100% rated voltage
Rated Capacity 20kVA Payment Terms T/T,L/C
Rated Output Voltage 150kV Packaging Details plywood case
Operating Frequency 45‑200Hz Model Number SXJFT
Brand Name Sansion Place of Origin China
Certification CE SGS ISO9001
High Light High Voltage Partial Discharge Testing System ,150kV Partial Discharge Test Equipment ,Transformer Insulation Testing System

Product Description

The Digital Partial Discharge (PD) Testing System is designed for detecting and measuring partial discharge in high-voltage electrical equipment and insulation systems. With a rated output voltage of 150kV and a rated capacity of 20kVA, it integrates digital PD measurement, variable-frequency high-voltage testing, signal filtering, and intelligent control in one coordinated system.

Featuring a detection sensitivity of 0.01pC, a measurement range of 0.1pC to 10,000nC, and a low partial discharge level of ≤2pC at rated voltage under no-load conditions, the system supports insulation assessment, PD pattern observation, test data storage, and automatic report generation.

Advantage

  • Integrated Testing Solution
    Combines high-voltage AC test equipment, digital PD measurement, signal filtering, and control software to support coordinated insulation testing.
  • Sensitive PD Measurement
    Provides 0.01pC detector sensitivity and a broad measurement range for evaluating partial discharge signals.
  • Adjustable Test Frequency
    Supports variable-frequency operation from 45Hz to 200Hz, allowing the test frequency to be adjusted within the specified operating range.
  • Digital Test Records
    Enables test data storage, signal playback, printing, and standard test report generation.
  • Automated Test Control
    Supports manual and automatic operation, programmable test sequences, voltage monitoring, withstand-time control, and automatic return to zero.
  • Configurable System Integration
    Standard communication interfaces support system expansion and potential connection with MES or ERP platforms, subject to interface and software requirements.

Key Specifications

  • Rated output voltage: 150kV
  • Rated capacity: 20kVA
  • Rated output current: 0.13A
  • Operating frequency: 45–200Hz
  • PD detector sensitivity: 0.01pC
  • PD measurement range: 0.1pC–10,000nC
  • PD level of the complete system: ≤2pC at rated voltage under no-load conditions
  • Voltage and current measurement accuracy: <1%
  • Test data storage and report generation
  • Computer-based control with potential MES/ERP data integration, subject to interface configuration

FAQ

Q1: What is a partial discharge testing system used for?

A: A partial discharge testing system is used to measure and observe partial discharge activity in electrical insulation under high-voltage test conditions. The results help evaluate insulation performance and identify potential insulation defects.

Q2: What is the maximum rated output voltage of this system?

A: The system specification lists a rated output voltage of 150kV and a rated capacity of 20kVA.

Q3: What is the detection sensitivity of the digital PD detector?

A: The specified detection sensitivity is 0.01pC. The measurement range is 0.1pC to 10,000nC.

Q4: What operating frequency does the system support?

A: The variable-frequency power supply operates from 45Hz to 200Hz, with a frequency adjustment step of 0.1Hz.

Company Details

Bronze Gleitlager

,

Bronze Sleeve Bushings

 and 

Graphite Plugged Bushings

 from Quality China Factory
  • Business Type:

    Manufacturer

  • Year Established:

    2005

  • Total Annual:

    50000000-80000000

  • Employee Number:

    120~150

  • Ecer Certification:

    Verified Supplier

Sansion Power Electric Co., Ltd was established in 2005, a technocrat who have rich experience of more than 10 years in R&D, manufacturing and marketing of power electrical testing products, which are widely used in the fields of power electric, railroad, energy conservation and environment prot... Sansion Power Electric Co., Ltd was established in 2005, a technocrat who have rich experience of more than 10 years in R&D, manufacturing and marketing of power electrical testing products, which are widely used in the fields of power electric, railroad, energy conservation and environment prot...

+ Read More

Get in touch with us

  • Reach Us
  • Sansion Power Electric Co., Ltd.
  • Building 8, Yuanyuanxin Industrial Park, No. 8 Huanhu Middle Road, Dongxihu District, Wuhan, Hubei, China 43004
  • https://www.sansionpower.com/

Leave a Message, we will call you back quickly!

Email

Check your email

Phone Number

Check your phone number

Requirement Details

Your message must be between 20-3,000 characters!

Submit Requirement