| Payment Terms | T/T |
| Supply Ability | 100pcs per month |
| Delivery Time | on request |
| Packaging Details | standard carton packing |
| Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) |
| Labeling | space for labeling at the front |
| Safety Integrity Level (SIL) | SIL 3 |
| Degree of protection | IEC 60529:2001 |
| Supply Connection | via 14-channel flat cable form master KFD2-HMM-16 |
| Output resistance | 100 Ω or smaller, capacitive coupling |
| Ambient temperature | -20 ... 65 °C (-4 ... 149 °F) |
| Dimensions | 20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) (W x H x D) , housing type B1 |
| Brand Name | P+F |
| Model Number | KFD0-HMS-16 |
| Certification | PF 07 CERT 1143 X |
| Place of Origin | Germany |
View Detail Information
Explore similar products
P+F KFD2-SR2-Ex1.W Switch Amplifier SIL 2 35mA 10Hz
P+F LFL2-BK-U-PUR5-EMS Float Switch 250VAC IP68
P+F RL28-8-H-2000-IR Background Suppression Sensor 880nm IP67
P+F Z787 Zener Barrier 50mA DC Positive Polarity
Product Specification
| Payment Terms | T/T | Supply Ability | 100pcs per month |
| Delivery Time | on request | Packaging Details | standard carton packing |
| Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) | Labeling | space for labeling at the front |
| Safety Integrity Level (SIL) | SIL 3 | Degree of protection | IEC 60529:2001 |
| Supply Connection | via 14-channel flat cable form master KFD2-HMM-16 | Output resistance | 100 Ω or smaller, capacitive coupling |
| Ambient temperature | -20 ... 65 °C (-4 ... 149 °F) | Dimensions | 20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) (W x H x D) , housing type B1 |
| Brand Name | P+F | Model Number | KFD0-HMS-16 |
| Certification | PF 07 CERT 1143 X | Place of Origin | Germany |
| High Light | SIL 3 P+F Sensors ,SIL 3 P+F hart multiplexer ,p&f hart multiplexer KFD0-HMS-16 | ||
16-channel, No external power required, HART field device input (revision 5 to 7), Used with HART Multiplexer Master KFD2-HMM-16, Up to SIL 3 acc. to IEC/EN 61508
Technical Data
| Functional safety related parameters | ||
|---|---|---|
| Safety Integrity Level (SIL) | SIL 3 | |
| Supply | ||
| Connection | via 14-channel flat cable form master KFD2-HMM-16 | |
| HART signal channels (non-intrinsically safe) | ||
| Conformity | HART field device input (revision 5 to 7) | |
| Connection | 26-pin flat cable for analog connections | |
| Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) | |
| Terminating resistor | external 230 ... 500 Ω standard (up to 1000 Ω possible) | |
| Output voltage | ≥ 400 mV ss (with the terminator resistance specified above) | |
| Output resistance | 100 Ω or smaller, capacitive coupling | |
| Input impedance | according to HART specification | |
| Input voltage range | 0.08 ... 4 V ss ; typ. ± 5.2 V as local reference | |
| Indicators/settings | ||
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility |
| |
|
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 65 °C (-4 ... 149 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 100 g | |
| Dimensions | 20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) (W x H x D) , housing type B1 | |
|
| Height | 93 mm |
|
| Width | 20 mm |
|
| Depth | 115 mm |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 07 CERT 1143 X | |
|
| Marking |
|
| Directive conformity |
| |
|
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
Related Models:
| KCD2-SCD-EX1 | KFU8-UFT |
| KCD2-STC-EX1.20 | K-HM26-2M-261533 |
| KFD2-SR2-Ex1.W.LB | NBB15-U1-E2 |
| KFD2-SR2-2.W.SM | NBB1,5-5GM25-E2 |
| KFD2-SR2-Ex2.W.SM | NBB1,5-5GM25-E2-V3 |
| KFD2-SR2-Ex2.2S | NBB1,5-F79-E0 |
| KFD2-SR2-2.2S | NBB1,5-F79-E2 |
| KFA6-DWB-EX1.D | NBB15-U1-Z2 |
| KFA6-SR2-Ex2.W | NBB5-18GM50-E2-V1 |
| KFA6-SR-2.3L.FA | NBB15-30GM30-E2-V1 |
| KFA6-ER-1.5 | NBB15-30GM50-A2-V1 |
| NBB15-30GM50-E2 | |
| KFA6-ER-1.W.LB | NBB15-30GM50-E2-M |
| KFA6-ER-2.W.LB | NBB15-30GM50-E2-V1 |
| NBB15-30GM50-E2-V1-M | |
| KFA6-SR-2.3L.FA | NBB8-18GM30-E2 |
| KFA6-STR-1.24.4 | NBB8-18GM30-E2-V1 |
| KFD0-CS-Ex1.50P | NBB8-18GM60-A2-V1 |
| KFD2-SH-Ex1.T.OP | NJ4-12GK-SN |
| KFD2-SL2-EX2.B | NJ5-18GK-N |
| KFD2-SR2-EX1.W | NJ5-18GK-N-150 |
| KFD2-SR2-Ex2.W | NJ5-18GM-N |
| KFD2-STC5-1.2O | NJ8-18GK-N |
| KFD2-STC5-Ex1 | RD0-FB-EX4 |
| KFD2-STC5-Ex1.H | RD0-TI-Ex8.FF.* |
| HIC2031 | Z787.F |
![]()
![]()
![]()
Company Details
Business Type:
Trading Company
Year Established:
2010
Total Annual:
5000000-8000000
Employee Number:
100~150
Ecer Certification:
Verified Supplier
SC Automation Limited (hereinafter referred to as SC) was established in 2010 and is a company focused on international trade. We are committed to serving customers worldwide based on the principle of integrity. After years of experience, we have formed good co... SC Automation Limited (hereinafter referred to as SC) was established in 2010 and is a company focused on international trade. We are committed to serving customers worldwide based on the principle of integrity. After years of experience, we have formed good co...
Get in touch with us
Leave a Message, we will call you back quickly!