| Payment Terms | L/C,T/T |
| Supply Ability | 400 sets /month |
| Delivery Time | 8-10 weeks |
| Packaging Details | wooden cartons |
| Brand | Eltek |
| Produft name | Indoor Rectiverter scable cabinet |
| Protection level | SPD , LLVD. BLVD |
| Input current | 1152 ADC |
| Max input AC | 320 - 475 VAC |
| Max input DC | 58 VDC |
| Mains configuration | 230/400VAC 3 phase (Y) |
| Max AC output | 415 VAC |
| Max output power | 54kva / 43,2kw |
| DC output power | 43,2 kW |
| DC output current | 900 ADC |
| DC max voltage | 58 VDC |
| IP grade | IP20/IP21 |
| Brand Name | Eltek |
| Model Number | CIEJ3642.xxxx |
| Certification | CE.UL |
| Place of Origin | CN |
View Detail Information
Explore similar products
Eltek Rectiverter 2U 6kVA Integrated System 6 kVA AC & 4,8 kW DC with Smartpack
Flatpack2 24v Telecom Power System CIO20405
Mean Well 19 Inch Power Supply RCP-1000-12 RC0-1000-24 1000W-1800W
Netsure 801 Telecom Power System 1000A 1500A 2000A Power Cabinet
Product Specification
| Payment Terms | L/C,T/T | Supply Ability | 400 sets /month |
| Delivery Time | 8-10 weeks | Packaging Details | wooden cartons |
| Brand | Eltek | Produft name | Indoor Rectiverter scable cabinet |
| Protection level | SPD , LLVD. BLVD | Input current | 1152 ADC |
| Max input AC | 320 - 475 VAC | Max input DC | 58 VDC |
| Mains configuration | 230/400VAC 3 phase (Y) | Max AC output | 415 VAC |
| Max output power | 54kva / 43,2kw | DC output power | 43,2 kW |
| DC output current | 900 ADC | DC max voltage | 58 VDC |
| IP grade | IP20/IP21 | Brand Name | Eltek |
| Model Number | CIEJ3642.xxxx | Certification | CE.UL |
| Place of Origin | CN | ||
| High Light | BLVD rectiverter scalable system IP20 ,telecom dc power 1152 ADC IP20 ,BLVD IP21 telecom dc power | ||
![]()
Eltek Rectiverter Indoor system Scalable system 18-54 kVA with optional A & B, AC input(CIEJ3642.xxxx )
The scalable Rectiverter indoor system provides backup power for 400 VAC 3-phase or 230 VAC 1-phase loads, and 48 VDC power for DC loads and battery charging.
The scalable Rectiverter indoor system provides AC backup power for 400 VAC 3-phase or 230 VAC 1-phase loads, and 48 VDC power for battery charging and optional DC loads
In combination with the optional B-input (dual AC input) eliminates the need for a traditional ATS (Automatic Transfer Switch).Where the switch from A to B input, is a seamless operation with no interruption on the AC load.
When configured with dual AC input for use as an AC UPS, it classifies as - VFI SS 111 according to EN 62040-3
Parameters :
| Models / ordering information | 54 kVA + 72 kW B-Input | ||
| Product family | CIEJ3642.xxxx | ||
| AC OUTPUT DATA | |||
| Voltage (default) / (adjustable range)1) | 400 VAC 3 phase (Y) / 346-415 VAC | ||
| Frequency (default inverter mode) | 50 Hz (adaptive) | ||
| Frequency (set-able inverter mode) | 50Hz, 60Hz or last synced 50/60Hz (adaptive) | ||
| Power maximum (continuous / overload (<15s) ) | 43,2 kW (54 kVA) / 72 kVA | ||
| Current maximum/phase (continuous / overload (<15s) ) | 78ARMS / 104,4ARMS | ||
| Current (maximum) Quick trip/phase (20ms) | 380A (6 x nominal) | ||
| Hold up (Voltage dips) (before switching to battery) | > 5 ms @ 43,2 kW load | ||
| THD | < 1.5 % at resistive load | ||
| Output features | Module: Fuse in L and N , Hot pluggable 100 A MCCB, AC output individual screw terminals 70 mm2 for L1-L3, N & PE | ||
| DC OUTPUT DATA | |||
| Voltage (default) / (adjustable range) | 53.5 VDC / 43 - 58 VDC | ||
| Power (maximum @nominal input) | 43,2 kW 2) | ||
| Current (maximum @VOUT ≤ 48 VDC) | 900 A 2) | ||
| Hold up time, maximum output power | >10ms; VOUT > 41 VDC | ||
| Output features | Short circuit proof, Over voltage Shutdown Battery input /output connection to M10 bolt | ||
| INPUT DATA | |||
| AC Mains Input Voltage(3 phase Y) | 320-475 VAC, | ||
| AC Current/phase(at nominal output voltage) (depending on module type) | 92-138 ARMS 4) | ||
| Frequency (default: sync range) | 47-53 & 57-63 Hz | ||
| Frequency (set-able: sync range) | 47-53 Hz, 57-63 Hz or both (adaptive) | ||
| Power Factor / THD | > 0.99 at 50% load or more / < 3.5% | ||
| DC Voltage nominal / extended range (no overload)3) | 45 - 58 VDC / 40 - 45 VDC | ||
| DC Current (maximum) | 1152 A / 1620 A during overload (15s) | ||
| Input features | Module : Fuse in L and N, Hot pluggable, Varistor, Hot pluggable 160 A MCCB, AC input individual screw terminals 70 mm2 for L1-L3, N & PE | ||
| DC LOAD AND BATTERY BREAKER OPTIONS | BATTERY BREAKER | DC LOAD BREAKER | |
| Possible configurations (2 pole breaker) | 2*1600 A (4*TPS 2 holder 800-1600 A) | - | |
| Possible configurations (2 pole breaker) | 4*600 A (8*TPS 00 holder 250-600 A) | - | |
| Possible configurations (2 pole breaker) | 2*600 A (4*TPS 00 holder 250-600 A) | 2*600 A (4*TPS 00 holder 250-600 A) | |
| OPTIONS | |||
| B-Input maximum power (with FP2 HE, 3 kW rectifiers) | 72 kW | ||
| Manual Bypass switch | 2*160 A | ||
| LVBD (1-pole) | 1800 A | ||
| OTHER SPECIFICATION | |||
| Efficiency | >96% (mains mode (AC/AC and AC/DC)), >94% (inverter mode (DC/AC)) | ||
| Protection Class | IP 20 | ||
| Operating temperature | -40 to +55°C (-40 to +131°F), humidity 5 - 95% RH non-condensing | ||
| Storage temperature | -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing | ||
| Dimensions[WxDxH] / Weight | 600 x 600x 2000mm (23,7 x 23,7 x 78,8”) / 300 kg (1100 lbs) | ||
| DESIGN STANDARDS | |||
| Electrical safety | EN 60950-1, EN 62040-1 UPS safety | ||
| EMC | ETSI EN 300 386 V.1.6.1, FCC CFR 47 Part 15 EN 61000-6-1 /-2/-3/-4, EN 62040-2 | ||
| Environment | ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) Normal operating conditions to be as per IEC/EN 62040-3:2011 clause 4.1 RoHS (2011/65/EU) and WEEE (2002/96/EC) compliant | ||
| 1) Output voltage ranges configured in factory and have individual keying in top chassis 3) 40 - 45 VDC: reduced performance - no power boost and increased voltage THD on AC output. | 2) AC load has priority. Maximum available DC output power and current is dependent on instant AC load and AC input voltage; i.e maximum 28 ,8kW/600 A at full AC power and nominal input for 230VAC. 4) If DC voltage is pulled below 43V the input current may increase above this level | ||
Option 1![]()
Option 2
![]()
* The indoor Rectiverter Cabinet with AC &DC feed in one cabinet
![]()
![]()
![]()
Related Products :
![]()
![]()
![]()
![]()
Solutions
Telecom companies both within and outside China can enjoy a complete service package from us. This includes a thorough on - site survey to obtain accurate information, the customization of professional plans according to customer wishes, 24/7 technical support, and regular maintenance and upkeep. We have an experienced and capable team and numerous reliable partners around the globe to safeguard our services.
FAQ :
1.Can I ask for samples and get a price quotation?
2.How does your company respond to quality - related problems?
3.How good is the quality of your products?
4.What's the duration of the quality guarantee?
5.What's the solution for poor - quality goods?
![]()
Company Details
Business Type:
Manufacturer,Distributor/Wholesaler,Agent,Trading Company