| Payment Terms | T/T |
| Delivery Time | 15-30 days |
| Packaging Details | carton |
| MODEL | FP2 24V 7.2KW |
| Product family | FP2 24V 7.2KW |
| Voltage | 21.75 - 28.8 VDC |
| Max power, nominal input | 7200W |
| Max current | 75 A |
| Efficiency | 95 % |
| Frequency | 45 - 66 Hz, 15-18.5 Hz1) / 0 Hz |
| Current | 11.25 ADC |
| Brand Name | Eltek |
| Model Number | FP2 24V 7.2KW |
| Place of Origin | China |
View Detail Information
Explore similar products
Flatpack2 Big System 48Vdc 84KW Telecom Power Indoor Cabinet Oem
Eltek Rectiverter 2U 6kVA Integrated System 6 kVA AC & 4,8 kW DC with Smartpack
Flatpack2 24v Telecom Power System CIO20405
Mean Well 19 Inch Power Supply RCP-1000-12 RC0-1000-24 1000W-1800W
Product Specification
| Payment Terms | T/T | Delivery Time | 15-30 days |
| Packaging Details | carton | MODEL | FP2 24V 7.2KW |
| Product family | FP2 24V 7.2KW | Voltage | 21.75 - 28.8 VDC |
| Max power, nominal input | 7200W | Max current | 75 A |
| Efficiency | 95 % | Frequency | 45 - 66 Hz, 15-18.5 Hz1) / 0 Hz |
| Current | 11.25 ADC | Brand Name | Eltek |
| Model Number | FP2 24V 7.2KW | Place of Origin | China |
| High Light | Eltek FP2 24V ,Eltek FP2 7.2KW ,Eltek FP2 2U | ||
![]()
The Flatpack2 modular concept has a lot of benefits compared to traditional solutions in the industry. It has high efficiency; less power consumption and heat dissipation. The overall Size and footprint of cabinet is 50% of Thyristor Controlled Size. Modular Hot Plug-in Construction allows redundancy, n+1, n+2 configurations.
It's easy to do repairing with MTTR< 5 minutes.Very high MTBF > 350000 hours, wide input AC Voltage and frequency range.Possibility to build combined systems with rectifiers, DC/DC converters and inverters controlled by one controller.
| Model | 24/1800 HE |
| Part number | 241115.205 |
| INPUT DATA | |
| Voltage (nominal) | 185 - 275 VAC / 185 - 300 VDC |
| Voltage (range) | 85 - 300 VAC / 85 - 300 VDC |
| Frequency | 45 - 66 Hz, 15-18.5 Hz1) / 0 Hz |
| Current (maximum) @ nominal input, full load | 11.25 ADC |
| Power Factor | 0.99 (@ 50-100% load) |
| THD (@ 230 VAC) | < 4 % (@ full load) |
| Protection | Fuse in both lines, varistor for transient protection, shutdown when VIN is out of range |
| OUTPUT DATA | |
| Voltage (default) | 26.75 VDC |
| Voltage (adjustable range) | 21.75 - 28.8 VDC |
| Max power, nominal input | 1800 W |
| Max power, de-rated @VIN = 85 VDC | 750 W |
| Max current, @VOUT ≤ 24 VDC | 75 A |
| Hold-up time, default voltage and 1000 W load | 20 ms, VOUT > 21 VDC |
| Current sharing | ± 5% of maximum current from 10 to 100% load |
| Static voltage regulation (10-100% load) | ±0.5% from 10 - 100% load and supplied power not limited by PV panels |
| Dynamic voltage regulation | ±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms |
| Ripple | < 250 mVPP , 30 MHz bandwidth |
| Psophometric noise | < 2 mVRMS |
| Protection | Overvoltage shutdown, short circuit proof, high temperature, hot plug-in inrush current limiting |
| OTHER SPECIFICATIONS | |
| Peak Efficiency | 95 % |
| Isolation | 3 kVAC – input and output, 1.5 kVAC – input earth, 0.5 kVDC – output earth |
| Alarms (Red LED) | Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure |
| Warnings (Yellow LED) | Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of range, flashing at overvoltage |
| Normal (Green LED) | Input and output ok |
| MTBF (Telcordia SR-332 Iss.I method III (a)) | >300 000 (@ Tambient : 25 °C) |
| Operating temperature (5 - 95% RH non-cond.) | - 40 -75°C [-40 - 167°F ] |
| Max output power de-rates above temp / to | 45°C [+113°F] / 1200W |
| Storage temperature | -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing |
| Dimensions[WxHxD] / Weight | 109 x 41.0 x 327mm [4.25 x 1.61 x 13”] / 1.950 kg [4.3lbs] |
| DESIGN STANDARDS | |
| Electrical safety | EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, IEC 60950-1:2013 UL 60950-1:2014 |
| EMC | EN 61000-6-1:2007, -6-2:2005, -6-3:2007 + A1:2010, -6-4:2007 + A1:2010 IEC 61000-6-5:2015, EN 300 386:v2.1.1, FCC CFR 47 Part 15:2008 |
|
Environment | ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) 2011/65/EU (RoHS) & 2012/19/EU (WEEE) Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised |
| 1) Maximum power de-rated to 1000W @230Vac & 16 2/3Hz input | |
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
![]()
Company Details
Business Type:
Manufacturer,Distributor/Wholesaler,Agent,Trading Company
Year Established:
2017
Total Annual:
4,000,000-5,000,000
Employee Number:
20~30
Ecer Certification:
Verified Supplier
Beijing Ding Ding Future Technology Co., Ltd. was founded in 2017, specializ... Beijing Ding Ding Future Technology Co., Ltd. was founded in 2017, specializ...
Get in touch with us
Leave a Message, we will call you back quickly!