| HV Output Current | 1–100 A |
| Test Voltage Range | 200–2,000 kV |
| Frequency Stability | ≤ 0.05% |
| Delivery Time | 30 Working Days |
| Waveform Distortion | ≤ 1% |
| Payment Terms | T/T,L/C |
| Packaging Details | Plywood Case |
| Frequency Range | 20–300 Hz |
| System Capacity | 300–20,000 kVA |
| Model Number | SXBP |
| Brand Name | Sansion |
| Certification | CE/SGS/EMS/ISO 9001 |
| Place of Origin | China |
View Detail Information
Explore similar products
Variable Frequency High Voltage Test System , On Site AC Withstand Hipot Test
High Capacity Variable Frequency 1000kV High Voltage Test Equipment For CVT /
300kVA–20000kVA High Voltage Test System For Transformer / GIS / Cable
Power System 200kV-2000kV High Voltage AC Hipot Tester For Substation / Cable On
Product Specification
| HV Output Current | 1–100 A | Test Voltage Range | 200–2,000 kV |
| Frequency Stability | ≤ 0.05% | Delivery Time | 30 Working Days |
| Waveform Distortion | ≤ 1% | Payment Terms | T/T,L/C |
| Packaging Details | Plywood Case | Frequency Range | 20–300 Hz |
| System Capacity | 300–20,000 kVA | Model Number | SXBP |
| Brand Name | Sansion | Certification | CE/SGS/EMS/ISO 9001 |
| Place of Origin | China | ||
| High Light | 220kV high voltage withstand test system ,AC withstand test system for transformers ,high voltage test system for GIS | ||
Product Description
The SXBP Variable Frequency Series Resonance Test System is engineered for high-voltage AC withstand testing of large-capacity electrical equipment and capacitive loads. Based on variable-frequency series resonance technology, the system combines a variable-frequency power supply, excitation transformer, resonant reactor and related compensation components to establish a controlled resonant circuit. By adjusting the operating frequency, the system can adapt to different test loads and generate the required high AC voltage.
Main System Components
| System Component | Purpose |
|---|---|
| Variable Frequency Power Supply | Provides adjustable-frequency excitation power |
| Excitation Transformer | Matches the excitation voltage and system requirements |
| Series Resonant Reactor | Establishes the resonant circuit with the test load |
| Protection Inductor | Provides additional circuit protection |
| Compensation Capacitor | Supports reactive compensation and resonance adjustment |
| Control & Protection Unit | Controls operation and monitors key test parameters |
Technical Specifications
| Technical Item | SXBP Series |
|---|---|
| System Type | Variable Frequency Series Resonance Test System |
| Rated Capacity | 300 kVA – 20,000 kVA |
| Rated Voltage | 200 kV – 2,000 kV |
| HV Rated Current | 1 A – 100 A |
| Input Power Supply | 380 V, 50/60 Hz |
| System Q Factor | ≥ 50 |
| Output Frequency | 20 – 300 Hz |
| Output Waveform | Sinusoidal |
| Waveform Distortion | ≤ 1% |
| Frequency Adjustment Resolution | 0.1 Hz |
| Frequency Stability | ≤ 0.05% |
| Applicable Standards | DL/T 849.6-2004; GB 50150-2016 |
Key Benefits
High-Voltage Capability Configurations from 200 kV to 2000 kV support a wide range of HV and EHV insulation testing applications.
Large-Capacity Testing The system covers 300 kVA–20,000 kVA, making it suitable for large-capacity test objects and demanding test projects.
Variable-Frequency Control The 20–300 Hz frequency range provides flexibility when working with different capacitive loads.
Efficient Resonant Operation Series resonance technology makes the system particularly suitable for high-capacitance electrical equipment.
High-Quality Output The specified waveform distortion is ≤1%, helping maintain consistent AC testing conditions.
Precise Frequency Adjustment With 0.1 Hz frequency adjustment resolution, the resonance point can be adjusted with high precision.
Typical Applications
| Application | Typical Test Objects |
|---|---|
| Power Cable Testing | 110 kV / 220 kV / 500 kV cables |
| GIS Testing | GIS, SF6-insulated switchgear |
| Transformer Testing | Power transformers |
| Switchgear Testing | HV switchgear and circuit breakers |
| Laboratory Testing | High-voltage electrical apparatus |
| Field Testing | Substations and power infrastructure |
FAQ
1.Can the SXBP system test 220 kV cables? Yes. The system can be configured for 220 kV power cable AC withstand testing. Cable length, capacitance, required test voltage and test duration should be provided for accurate configuration.
2.Can it be used for 500 kV cable testing? Yes. The SXBP series can be engineered for 500 kV cable testing and other EHV applications within the required technical range.
3.What is the output frequency? The output frequency range is 20–300 Hz.
4.Why is the frequency adjustable? Because different test objects have different capacitance values. Variable-frequency operation allows the system to adjust the resonant condition according to the electrical characteristics of the load.
![]()
Company Details
Business Type:
Manufacturer
Year Established:
2005
Ecer Certification:
Verified Supplier
Sansion Power Electric Co., Ltd was established in 2005, a technocrat who have rich experience of more than 10 years in R&D, manufacturing and marketing of power electrical testing products, which are widely used in the fields of power electric, railroad, energy conservation and environment prot... Sansion Power Electric Co., Ltd was established in 2005, a technocrat who have rich experience of more than 10 years in R&D, manufacturing and marketing of power electrical testing products, which are widely used in the fields of power electric, railroad, energy conservation and environment prot...
Get in touch with us
Leave a Message, we will call you back quickly!