| Payment Terms | T/T |
| Standard | AS60076 |
| Type | Substation Power Transformer |
| Supply Ability | 500set/month |
| Delivery Time | 35days |
| Secondary Voltage | 415 V |
| Primary Voltage | 1kV |
| Packaging Details | Plywood case |
| Operation | Step-down |
| Capacity | 1500kVA |
| Vector group | YNyn0 |
| Cooling Class | ONAN |
| Certification | AS60076 |
| Place of Origin | CHINA |
| Brand Name | WINLEY |
| Model Number | S-1500/1/0.415 |
View Detail Information
Explore similar products
2000kva Substation Power Transformer ONAF Step Down 34.5kv To 480v Electrical
40MVA Substation Power Transformer Oil Immersed High Voltage Step Down 44KV To
1000 KVA 3 Phase Power Distribution Substation Transformer 7200V To 480V IEEE
6500Kva Substation Power Transformer
Product Specification
| Payment Terms | T/T | Standard | AS60076 |
| Type | Substation Power Transformer | Supply Ability | 500set/month |
| Delivery Time | 35days | Secondary Voltage | 415 V |
| Primary Voltage | 1kV | Packaging Details | Plywood case |
| Operation | Step-down | Capacity | 1500kVA |
| Vector group | YNyn0 | Cooling Class | ONAN |
| Certification | AS60076 | Place of Origin | CHINA |
| Brand Name | WINLEY | Model Number | S-1500/1/0.415 |
| High Light | 1500kVA oil immersed power transformer ,three phase substation transformer 415V ,ONAN AS60076 power transformer | ||
| Item | Data |
|---|---|
| Product Type | Three-Phase Oil-Immersed Substation Power Transformer |
| Rated Capacity | 1500kVA |
| Primary Voltage | 1000 V |
| Secondary Voltage | 415 V |
| Phase | 3 Phase |
| Frequency | 50 Hz |
| Vector Group | YNyn0 |
| Cooling Method | ONAN |
| Standard | AS60076 |
| No-load Loss | 1685 W |
| No-load Current | 0.29% |
| Load Loss | 15805 W at 85°C |
| Short-circuit Impedance | 5.48% |
| Temperature Rise | 60/55 K |
| Service Condition | Indoor or outdoor |
| Ambient Temperature | -5°C to +45°C |
| Altitude | ≤1000 m |
| Dimensions | 2550 × 1900 × 1700 mm |
| Total Weight | 4475 kg |
Technical drawings
![]()
| Radiator cooling assembly | Supports heat dissipation under 1500kVA duty and helps buyers plan installation space and ventilation. |
| Radiator protection frame | Helps reduce the risk of radiator fin deformation during transport, lifting, and installation. |
| High-current LV terminal design | Helps buyers verify busbar, cable lug, and LV switchgear inlet design instead of checking voltage only. |
| Operation monitoring components | Enables operators to monitor oil level, oil temperature, and pressure status; pressure relief supports overpressure protection. |
| Drain valve / sampling arrangement | Supports future oil sampling, dielectric breakdown testing, and DGA; the tested oil DBV average value is 43.25kV. |
| Grounding pads, lifting plates, and jacking pads | Supports grounding, lifting, positioning, and foundation installation planning. |
![]()
Applications
| Sector | Applications |
|---|---|
| Industrial | Manufacturing plants, processing lines, workshops, motor control systems, and general plant power distribution |
| Commercial | Large buildings, service facilities, shopping centers, and building electrical rooms requiring 415 V distribution |
| Infrastructure | Water treatment plants, transport facilities, utility support systems, and public-service power systems |
| Energy & Site Power | Local distribution points, site substations, equipment power supply, and project-based electrical conversion systems |
Substation Transformer Specification
| kVA | HV | LV | Width(mm) | Length(mm) | Height(mm) |
| 315kVA | 11000V | 400V | 800 | 696 | 1336 |
| 500kVA | 27600V | 480GrdY/277V | 1730 | 2300 | 1510 |
| 500kVA | 11000V | 415V | 1700 | 1700 | 1650 |
| 750kVA | 11000V | 433V | 1850 | 1845 | 1465 |
| 1000kVA | 14400V | 415/240V | 1085 | 1860 | 1570 |
| 1200kVA | 13800V | 240V | 2450 | 1850 | 1820 |
| 1500kVA | 24940V | 600V | 1800 | 1880 | 1895 |
| 2000kVA | 7200V | 600GrdY/346 | 1766 | 2680 | 1982 |
| 2000kVA | 44000V | 600V | 1260 | 2090 | 1700 |
| 2500kVA | 24940V | 480GrdY/277V | 2400 | 2200 | 2060 |
| 3000kVA | 11000V | 415V | 1600 | 2330 | 1920 |
| 3000kVA | 22800V | 415/240V | 2130 | 3500 | 1910 |
| 3750kVA | 44000V | 600V | 2240 | 2650 | 2700 |
| 4000kVA | 33kV | 600Y/347 | 2150 | 3250 | 2290 |
| 5000kVA | 34500V | 7200V | 3780 | 1850 | 3450 |
| 5000kVA | 34500V | 4160V | 2799 | 2400 | 2938 |
| 6300kVA | 35000V | 400V | 3520 | 2820 | 3470 |
| 6800kVA | 34500V | 800V | 3400 | 2670 | 3400 |
| 7500kVA | 27600Y | 4160V | 3350 | 3290 | 2270 |
![]()
![]()
Company Details
Business Type:
Manufacturer,Seller
Year Established:
2007
Total Annual:
$45M-$60M
Employee Number:
150~210
Ecer Certification:
Verified Supplier
R&D and production capabilities Winley Electric boasts a team of dozens of experienced senior engineers who are well-versed in transformer standards of different countries including ANSI, IEEE, CSA, DOE2016, NEMA and IEC60076, and who can tailor cost-effective transformer solutions according to... R&D and production capabilities Winley Electric boasts a team of dozens of experienced senior engineers who are well-versed in transformer standards of different countries including ANSI, IEEE, CSA, DOE2016, NEMA and IEC60076, and who can tailor cost-effective transformer solutions according to...