| Output Current | 1.0A, 0.5A, 0.2A |
| Customization | Available |
| Payment Terms | T/T |
| Supply Ability | 2000 units/year |
| Delivery Time | 5-8 work days |
| Open Circuit Voltage | 24V |
| Data Storage | 500 groups built-in |
| Warranty | 12 Months |
| Sampling Rate | 20kHz |
| Weight | Main unit 6.15kg; cable box 4.55kg |
| Power Supply | AC220V±10%, 50±1Hz |
| Model NO. | XHYZ1668T |
| Test Connections | YN, Y, Delta; with/without winding |
| Measurement Accuracy | Resistance ±(5% reading ±0.1Ω); Time ±(0.1% reading ±0.2ms) |
| Working Temperature | -10℃~50℃ |
| Display | 7-inch high-brightness LCD |
| Dimensions | Main unit 360×290×170mm; cable box 360×290×170mm |
| Transition Resistance Range | 0.3Ω~20Ω (1.0A); 5Ω~40Ω (0.5A); 20Ω~100Ω (0.2A) |
| Packaging Details | Wooden box |
| Working Humidity | ≤85%RH |
| Transition Time Range | 0~320ms |
| Place of Origin | Xi'an, Shaanxi, China |
| Certification | CE/ISO |
| Brand Name | XZH TEST |
| Model Number | XHYZ1668T |
View Detail Information
Explore similar products
On-Load Tap Switch Tester Action Sequence Switching Time Three-Phase Synchroniza
Portable Transformer Winding Deformation Tester Transformer Tester SFRA Sweep
Transformer Low Voltage Short Circuit Impedance Tester for Winding Deformation
Lab Gas Chromatograph Transformer Tester Dissolved Gas Analysis FID TCD ECD FPD
Product Specification
| Output Current | 1.0A, 0.5A, 0.2A | Customization | Available |
| Payment Terms | T/T | Supply Ability | 2000 units/year |
| Delivery Time | 5-8 work days | Open Circuit Voltage | 24V |
| Data Storage | 500 groups built-in | Warranty | 12 Months |
| Sampling Rate | 20kHz | Weight | Main unit 6.15kg; cable box 4.55kg |
| Power Supply | AC220V±10%, 50±1Hz | Model NO. | XHYZ1668T |
| Test Connections | YN, Y, Delta; with/without winding | Measurement Accuracy | Resistance ±(5% reading ±0.1Ω); Time ±(0.1% reading ±0.2ms) |
| Working Temperature | -10℃~50℃ | Display | 7-inch high-brightness LCD |
| Dimensions | Main unit 360×290×170mm; cable box 360×290×170mm | Transition Resistance Range | 0.3Ω~20Ω (1.0A); 5Ω~40Ω (0.5A); 20Ω~100Ω (0.2A) |
| Packaging Details | Wooden box | Working Humidity | ≤85%RH |
| Transition Time Range | 0~320ms | Place of Origin | Xi'an, Shaanxi, China |
| Certification | CE/ISO | Brand Name | XZH TEST |
| Model Number | XHYZ1668T | ||
| High Light | on-load tap changer tester 20kHz sampling ,oltc analyzer transformer preventive testing ,plant transformer tap changer tester | ||
The on-load tap changer is the only moving part connected to the transformer circuit, and OLTC faults are a leading cause of transformer unplanned outages. The XHYZ1668T lets plant electrical teams measure the transition waveform, transition time, instantaneous transition resistance and three-phase synchronization of transformer on-load tap changers during routine preventive maintenance, without sending the transformer to a workshop. The instrument is intelligent, compact and light (6.15kg main unit), with a 7-inch screen, 20kHz sampling and storage for 500 groups of data so that maintenance history can be compared over time.
| Parameter | Specification |
|---|---|
| Output Current | 1.0A / 0.5A / 0.2A |
| Transition Resistance Range | 0.3Ω ~ 20Ω (1.0A) 5Ω ~ 40Ω (0.5A) 20Ω ~ 100Ω (0.2A) |
| Transition Time Range | 0 ~ 320ms |
| Open Circuit Voltage | 24V |
| Measurement Accuracy | Transition resistance: ±(5% reading ±0.1Ω) Transition time: ±(0.1% reading ±0.2ms) |
| Sampling Rate | 20kHz |
| Data Storage | 500 groups built-in |
| Display | 7-inch high-brightness LCD |
| Output Interfaces | High-speed printer, USB port, RS232 serial port |
| Dimensions | Main unit: 360 × 290 × 170 mm Cable box: 360 × 290 × 170 mm |
| Weight | Main unit: 6.15kg Cable box: 4.55kg |
| Ambient Temperature | -10°C ~ +50°C |
| Ambient Humidity | ≤85% RH |
| Working Power Supply | AC 220V±10%, 50±1Hz |
The XHYZ1668T adapts to the connection of the regulating winding under test, so plant teams can follow the correct wiring and conversion rules:
| Connection Type | Method & Conversion |
|---|---|
| YN / Y with neutral led out | Three-phase test; resistance displayed directly without conversion |
| Y type, neutral not led out | Two-phase method using the third phase as neutral, R = 1/3 R' (single-phase method R = 1/2 R') |
| Delta type winding | Two-phase method, R = R'; single-phase method R = 2/3 R' |
| Without-winding test | Test leads connected to X1/Y1/Z1 (A1/B1/C1) with short-circuit links to X2/Y2/Z2 (A2/B2/C2) |
When testing with the winding connected, the non-tested side of the transformer must be three-phase short-circuited and grounded, and the instrument ground terminal must be reliably earthed before any voltage is applied. Note that with-winding action time is approximately 3-7ms longer than without-winding action time — a normal difference, not a fault.
Company Details
Business Type:
Manufacturer
Year Established:
2013
Total Annual:
1000000-5000000
Employee Number:
50~100
Ecer Certification:
Verified Supplier
Xi'an Xu&Hui Electromechanical Technology Co., Ltd. /Xian XZH Electric Power Technology Co., Ltd. Has found in 2013, located in Xi'an, China. which is a highly experienced team dedicated to developing electrical... Xi'an Xu&Hui Electromechanical Technology Co., Ltd. /Xian XZH Electric Power Technology Co., Ltd. Has found in 2013, located in Xi'an, China. which is a highly experienced team dedicated to developing electrical...
Get in touch with us
Leave a Message, we will call you back quickly!