Payment Terms | T/T |
Supply Ability | 1000 units per year |
Delivery Time | 5-8 work days |
Packaging Details | Wooden packaging |
Product name | Cable Sheath Fault Pre-locator |
No-load voltage | ≥7500V |
Short circuit current | ≥40mA |
Working power supply | AC 220V±10% 50Hz±1Hz |
Brand Name | XZH TEST |
Model Number | XHHG521A |
Certification | CE ISO |
Place of Origin | China |
View Detail Information
Explore similar products
Adjustable Voltage Frequency Underground Power Cable Sheath Fault Locator
10kV-500kV Cable Sheath Fault Locator for Inspection and Fault Location of Hv
Portable Power HV Underground Cable Sheath Fault Pinpoint Locator
Electronic No-Load Voltage 7500V High-Resistance Cable Fault Detection Sheath
Product Specification
Payment Terms | T/T | Supply Ability | 1000 units per year |
Delivery Time | 5-8 work days | Packaging Details | Wooden packaging |
Product name | Cable Sheath Fault Pre-locator | No-load voltage | ≥7500V |
Short circuit current | ≥40mA | Working power supply | AC 220V±10% 50Hz±1Hz |
Brand Name | XZH TEST | Model Number | XHHG521A |
Certification | CE ISO | Place of Origin | China |
Introduction
The cable outer sheath fault tester XHHG521A is designed based on the MURRAY bridge principle and can be used to locate the breakdown points of various wires and cables and the defect points that have no breakdown but low insulation resistance values.
The equipment uses an electric voltage regulator and an R-type transformer to form a high-voltage constant current source, and the button operation can increase or decrease the voltage. The no-load voltage is 7500V, the short-circuit current is 100mA, and a high-sensitivity amplifier and galvanometer are used to indicate balance. It forms a balanced bridge with a proportional potentiometer, and the whole is placed at a high potential. The measurement cable is a specially designed two-core high-voltage rubber cable. The four-terminal resistance measurement method is used to avoid errors caused by lead resistance. The entire panel is at low potential. One-touch operation, enter the cable length and automatically calculate the fault distance. The high voltage source and bridge are integrated in a portable protective box. Therefore, the device has high voltage, light weight, easy operation and safe use.
No load voltage | ≥7500V |
Short circuit current | ≥100mA (when adjusting balance, it is recommended to set it at 5~40mA); |
Positioning accuracy | ±(0.2%·L±1)m |
Weight | 25kg |
Power supply | AC 220V (±10%), 50Hz±1Hz; 8.4V built-in battery. |
Product feature
Company Details
Business Type:
Manufacturer
Year Established:
2013
Total Annual:
1000000-5000000
Employee Number:
50~100
Ecer Certification:
Verified Supplier
Xi'an Xu&Hui Electromechanical Technology Co., Ltd. /Xian XZH Electric Power Technology Co., Ltd. has found in 2013, located in Xi'an, China. which is a highly experienced team dedic... Xi'an Xu&Hui Electromechanical Technology Co., Ltd. /Xian XZH Electric Power Technology Co., Ltd. has found in 2013, located in Xi'an, China. which is a highly experienced team dedic...
Get in touch with us