| DC charge/discharge power | 1.56 MW / 1.56 MW (0.25P) |
| Weight | 46 t +/-1 t |
| Rated battery energy | 6.26 MWh |
| Operating ambient | -20 to +50 C |
| Packaging Details | 20-foot high-cube battery container. Transport, lifting and securing plan to be agreed for 46 t +/-1 t. |
| Cell chemistry / capacity | LFP / 392 Ah / 3.2 V |
| Thermal management | Liquid cooling; 30 kW cooling / 12 kW heating capacity |
| Dimensions L x W x H | 6058 x 2438 x 2896 mm (+/-10 mm) |
| System configuration | 12P416S / 4704 Ah |
| Protection ratings | Container IP55 / module IP67 / BPU IP65 |
| Corrosion / impact | C4 / IK10 |
| Battery modules | 48 x 1P104S; 130.45 kWh each |
| BMS / communication | 3-level BMS; RS485 / Ethernet / CAN 2.0 |
| Container format | 20 ft high cube |
| Supply scope | DC battery container; external PCS and project controls |
| Battery racks | 12 x 1P416S; 521.8 kWh each |
| Cell cycle life | At least 8000 cycles at 25 +/-2 C, 0.25P, 70% end-of-life capacity |
| Source-rated RTE | At least 95% at 0.25P; AC efficiency project-specific |
| Rated DC voltage | 1331.2 Vdc |
| Delivery Time | To be confirmed for each project |
| DC operating range | 1123.2-1497.6 Vdc |
| Solution provider | YINTU |
| Model Number | YT-Container ESS-6.26MWh |
| Brand Name | YINTU |
View Detail Information
Explore similar products
5.016 MWh Utility Scale Energy Storage Systems Liquid Cooled Utility ESS IP54
3290 kWh Utility Scale Battery Energy Storage Systems Modular 20 Foot Battery
3.85 MWh Liquid Cooled Utility Scale ESS With 2 MW Rated Power IP54 Protection
5017 KWh Utility Scale Energy Storage Systems Liquid Cooled For Large Solar
Product Specification
| DC charge/discharge power | 1.56 MW / 1.56 MW (0.25P) | Weight | 46 t +/-1 t |
| Rated battery energy | 6.26 MWh | Operating ambient | -20 to +50 C |
| Packaging Details | 20-foot high-cube battery container. Transport, lifting and securing plan to be agreed for 46 t +/-1 t. | Cell chemistry / capacity | LFP / 392 Ah / 3.2 V |
| Thermal management | Liquid cooling; 30 kW cooling / 12 kW heating capacity | Dimensions L x W x H | 6058 x 2438 x 2896 mm (+/-10 mm) |
| System configuration | 12P416S / 4704 Ah | Protection ratings | Container IP55 / module IP67 / BPU IP65 |
| Corrosion / impact | C4 / IK10 | Battery modules | 48 x 1P104S; 130.45 kWh each |
| BMS / communication | 3-level BMS; RS485 / Ethernet / CAN 2.0 | Container format | 20 ft high cube |
| Supply scope | DC battery container; external PCS and project controls | Battery racks | 12 x 1P416S; 521.8 kWh each |
| Cell cycle life | At least 8000 cycles at 25 +/-2 C, 0.25P, 70% end-of-life capacity | Source-rated RTE | At least 95% at 0.25P; AC efficiency project-specific |
| Rated DC voltage | 1331.2 Vdc | Delivery Time | To be confirmed for each project |
| DC operating range | 1123.2-1497.6 Vdc | Solution provider | YINTU |
| Model Number | YT-Container ESS-6.26MWh | Brand Name | YINTU |
| High Light | 20ft container battery storage ,liquid-cooled battery energy storage ,utility scale energy storage system | ||
UTILITY-SCALE DC BATTERY STORAGE
YT-Container ESS-6.26MWh provides a 6.26 MWh LFP battery block with 1.56 MW rated DC charge and discharge power. The 1500 V class system combines 392 Ah cells, three-level battery management and liquid cooling within a standard 20-foot high-cube enclosure. It is intended for integration into utility storage plants, renewable-energy projects and specifically engineered microgrids.
The listed equipment is a DC-side battery container. The specified configuration includes the battery modules and racks, battery protection units, DC protection, system BMS, thermal management, monitoring and the stated fire-protection functions. A compatible bidirectional PCS, project EMS/SCADA, transformer, switching and grid-connection equipment are external integration items unless separately included in the agreed scope.
YINTU is an energy storage solution provider. We work with manufacturing partners to match battery equipment with project requirements, coordinate technical interfaces and define the supply boundary. The container rating does not by itself establish a complete AC plant output, grid-service qualification or site backup performance.
Store selected renewable generation when production exceeds the desired delivery schedule, then discharge through the chosen PCS when energy is needed later. The battery block provides energy capacity for this operating plan. Renewable output, charging availability, export limits and auxiliary demand determine how much energy can actually be shifted.
The 20-foot format gives project designers a repeatable DC battery building block. Plant power and energy can be assessed separately by selecting the number of containers and the compatible conversion equipment. At the stated nameplate ratings, 6.26 MWh divided by 1.56 MW is approximately four hours. Delivered AC duration depends on usable SOC, losses, auxiliaries, aging and the agreed dispatch conditions.
A project EMS can coordinate battery dispatch around defined grid-demand peaks or an operating schedule. Useful peak support requires both sufficient converter power and usable energy over the relevant period. The design should also include reserve allocation and recovery between repeated peaks. Any savings or infrastructure-deferral assessment must use the actual connection and operating profile.
The container can form the battery section of a specifically engineered microgrid or backup system. Island operation, black start and grid-support functions depend on a suitable PCS, controls, switching, protection and operating sequence. Frequency-response performance or grid-forming capability is not guaranteed by the DC enclosure alone.
The source configuration contains 4,992 LFP cells. Each 1P104S module is rated at 130.45 kWh and 332.8 V. Four modules form a 1P416S rack, rated at 521.8 kWh and 1331.2 V. Twelve racks in parallel form the 12P416S system. Six BPUs provide the specified circuit protection and rack-management functions, while the electrical cabin houses DC protection, system BMS and a 3 kVA UPS.
Match the external PCS to the complete 1123.2-1497.6 Vdc operating window and the 1.56 MW rated charge/discharge power, including the intended current limits and communications. The PCS converts DC battery power to and from the AC system. Project EMS/SCADA supervises dispatch while the BMS supplies battery limits and protection information. The electrical-cabin UPS rating does not define an AC backup supply for site loads.
| Parameter | Specification |
|---|---|
| Model | YT-Container ESS-6.26MWh |
| Rated battery energy | 6.26 MWh |
| Rated DC charge / discharge power | 1.56 MW / 1.56 MW (0.25P) |
| Rated DC voltage | 1331.2 Vdc |
| DC operating voltage | 1123.2-1497.6 Vdc |
| Rated capacity / configuration | 4704 Ah / 12P416S |
| Cell chemistry / capacity / voltage | LFP / 392 Ah / 3.2 V |
| Source-rated round-trip efficiency | ≥95% at 0.25P |
| Cell cycle life | ≥8,000 cycles under the source test conditions |
RTE is a source-rated value at 0.25P. Delivered AC efficiency also depends on the selected PCS, auxiliary consumption and operating conditions. Cell-life conditions are 25 ±2°C, 0.25P charge/discharge and 70% end-of-life capacity. This cell-level result is not a system warranty term.
| Parameter | Specification |
|---|---|
| Cells | 4,992 x 392 Ah LFP cells |
| Battery modules | 48 x 1P104S; 130.45 kWh / 332.8 V each |
| Battery racks / clusters | 12 x 1P416S; 521.8 kWh / 1331.2 V each |
| Battery protection units | 6 BPUs |
| Electrical cabin / UPS | 1 cabin with DC protection, system BMS and 3 kVA UPS |
| Liquid-cooling equipment | 30 kW cooling / 12 kW heating capacity |
| Coolant / chiller supply | 50% glycol solution / 380-415 Vac, 3N~, 50 Hz |
| Electrical-cabin air conditioner | 1 kW cooling; 230 Vac ±15%, 50 Hz |
| Battery-cabin dehumidifier | 7 L/day at 35°C, 95% RH; 220 Vac, 50/60 Hz |
Cooling and heating capacities describe thermal performance rather than the chiller’s electrical input demand. The chiller and electrical-cabin air conditioner are specified for 50 Hz. Confirm auxiliary-supply compatibility for the destination project and include auxiliary energy in the plant operating model.
| Parameter | Specification |
|---|---|
| Container format | 20-foot high-cube container |
| Dimensions (L x W x H) | 6058 x 2438 x 2896 mm (±10 mm) |
| Weight | 46 t ±1 t |
| Container / module / BPU protection | IP55 / IP67 / IP65 |
| Enclosure corrosion / impact | C4 / IK10 |
| Operating ambient temperature | -20 to +50°C |
| Storage temperature | -30 to +55°C |
| Relative humidity | 0-95%, non-condensing |
| Operating altitude | ≤3000 m; derating above 3000 m as stated in source |
| Parameter | Specification |
|---|---|
| BMS architecture | Module BMS + Rack BMS + System BMS |
| Communication | RS485 / Ethernet / CAN 2.0 |
| Cell balancing | Passive balancing, 100 mA |
| Electrical protection | Short circuit, overcharge, overdischarge, overtemperature, surge protection and emergency stop |
| Monitoring | Temperature, humidity, CO, H₂ and water ingress |
| Fire protection | Condensed aerosol suppression and water fire protection |
| Detection and alarms | Smoke / heat detection and audible / visual alarms |
| Ventilation and pressure management | Explosion-proof exhaust and pressure relief |
The safety configuration combines battery monitoring, protective control and the listed suppression functions. Final fire-system design, interfaces and installation requirements must match the supplied configuration and the site. No single protection feature substitutes for a complete project design.
The source lists UL 1973, UL 9540, UL 9540A, IEC 62619, IEC 63056, IEC 62933-5-2 and IEC 62933-2-1 as battery/system references. It also lists UN 38.3 and UN 3536 for transport, and IEC 60529 (IP55), NFPA 855/68/69, NFPA 70E and GR-63-CORE Zone 4 as enclosure or installation references. Applicable certificates, test reports and model coverage must be confirmed for the offered configuration. A reference list is not a claim that every certification has been issued for every supplied model.
The listed equipment is the DC battery container. PCS, project EMS and grid-connection equipment are external integration items. PV integration requires the appropriate PV conversion architecture and plant controls. Direct connection of PV strings to the battery enclosure is not specified.
Approximately four hours is the ratio of the nameplate energy to the rated DC power. The usable AC duration depends on SOC limits, conversion and auxiliary losses, temperature, aging and reserve settings. Agree the required delivery test and end-of-life criteria for the project.
It is a cell-level test reference under the stated temperature, charge/discharge rate and remaining-capacity conditions. Warranty duration, throughput, operating limits and system performance commitments require a separate written agreement.
Those are functions of a complete engineered system. They require compatible PCS controls, the necessary power and energy reserve, metering, protection and any applicable connection or service approvals. They cannot be confirmed from the battery enclosure rating alone.
Share required AC power and usable energy, the renewable-generation or load profile, grid voltage, operating schedule, site climate and available layout. YINTU can coordinate battery selection, PCS matching and technical clarification with manufacturing partners for a defined supply scope.
For related planning topics, read our PCS control-mode guide and air-cooled versus liquid-cooled BESS guide.
Data are based on the supplied YT-Container ESS-6.26MWh datasheet, V1.0, October 2026, which references a Rev.3 technical specification. Final scope, drawings, operating limits and documentation follow the agreed project configuration. Images show a product rendering and application concepts.
Company Details
Business Type:
Distributor/Wholesaler,Exporter,Trading Company
Year Established:
2016
Total Annual:
$ 10 million-$ 20,million
Employee Number:
50~100
Ecer Certification:
Verified Supplier
Your Partner for Energy Storage Product Sourcing YINTU Energy is the energy storage business of Hunan Yintu New Materials Co., Ltd. Established in 2016, our company has 10-50 employees and an export share of 100%. We connect overseas distributors, installers, EPC companies and project buyers with... Your Partner for Energy Storage Product Sourcing YINTU Energy is the energy storage business of Hunan Yintu New Materials Co., Ltd. Established in 2016, our company has 10-50 employees and an export share of 100%. We connect overseas distributors, installers, EPC companies and project buyers with...
Get in touch with us
Leave a Message, we will call you back quickly!