| Cooling method | Liquid cooling |
| Approximate weight | 41 t |
| Corrosion protection | C4; C5 optional |
| Installation | Outdoor; non-walk-in external maintenance |
| Supply scope | DC-side battery container |
| Communication interfaces | CAN / Ethernet / RS485 |
| Delivery Time | Confirmed after configuration approval |
| Battery voltage range | 1164.8–1497.6 V |
| BMS architecture | 3-level |
| Auxiliary supply | Approx. 40 kW; 400 V / 50 Hz; 3N + PE |
| System operating temperature | −20 to +50°C; derating above 45°C |
| Cell specification | LFP / 3.2 V / 314 Ah |
| Charge / discharge rate | ≤0.5 CP |
| Ingress protection | IP55 |
| Temperature difference | <2.5°C (battery cells) |
| Dimensions W × D × H | 6058 × 2438 × 2896 mm |
| Container format | 20 ft |
| Rated battery energy | 5015.96 kWh |
| External protocol | Modbus TCP |
| Nominal DC voltage | 1331.2 V |
| Altitude | ≤3000 m |
| Packaging Details | Container transport, lifting plan and shipping arrangements confirmed for the project. |
| Brand Name | YINTU |
| Model Number | YT-Utility ESS-5015kWh |
View Detail Information
Explore similar products
3.44 MWh Liquid-Cooled Utility ESS with 1.725 MW Rated Power
5.016 MWh Utility Scale Energy Storage Systems Liquid Cooled Utility ESS IP54
3290 kWh Utility Scale Battery Energy Storage Systems Modular 20 Foot Battery
3.85 MWh Liquid Cooled Utility Scale ESS With 2 MW Rated Power IP54 Protection
Product Specification
| Cooling method | Liquid cooling | Approximate weight | 41 t |
| Corrosion protection | C4; C5 optional | Installation | Outdoor; non-walk-in external maintenance |
| Supply scope | DC-side battery container | Communication interfaces | CAN / Ethernet / RS485 |
| Delivery Time | Confirmed after configuration approval | Battery voltage range | 1164.8–1497.6 V |
| BMS architecture | 3-level | Auxiliary supply | Approx. 40 kW; 400 V / 50 Hz; 3N + PE |
| System operating temperature | −20 to +50°C; derating above 45°C | Cell specification | LFP / 3.2 V / 314 Ah |
| Charge / discharge rate | ≤0.5 CP | Ingress protection | IP55 |
| Temperature difference | <2.5°C (battery cells) | Dimensions W × D × H | 6058 × 2438 × 2896 mm |
| Container format | 20 ft | Rated battery energy | 5015.96 kWh |
| External protocol | Modbus TCP | Nominal DC voltage | 1331.2 V |
| Altitude | ≤3000 m | Packaging Details | Container transport, lifting plan and shipping arrangements confirmed for the project. |
| Brand Name | YINTU | Model Number | YT-Utility ESS-5015kWh |
| High Light | 5015 kWh Liquid Cooled Utility BESS ,314 Ah LFP Utility ESS Container ,C4 Corrosion Protected Utility BESS | ||
UTILITY-SCALE DC BATTERY STORAGE
A compact 5015.96 kWh LFP battery platform using 314 Ah cells and liquid cooling for large solar and grid storage projects. Narrow cold plates and 314 Ah cells provide approximately 5 MWh in a 20 ft high-cube container. The stated container footprint is below 15 m²; the complete plant still needs service clearances, fire separation, PCS equipment and access roads.
This listing covers the DC-side battery container, including LFP batteries, battery management, thermal management, DC distribution and the specified protection systems. It is not a complete AC-connected power station. PCS, plant EMS/PPC, transformers, switchgear and grid connection equipment are separate project items unless expressly included in the agreed supply scope.
YINTU is an energy storage solution provider. We work with manufacturing partners to select battery equipment and coordinate the interfaces required for each project.
Use a compact battery block to plan energy storage beside a solar collector station. Stored solar energy can be dispatched after the production peak through the separately selected PCS. Container density supports layout planning, but does not replace a full fire, foundation, lifting and maintenance-access study.
A coordinated PCS and plant EMS can charge or discharge the battery to moderate short-term variations in photovoltaic or wind output and follow an export schedule. The achievable ramp rate and response depend on converter capability, communications, available state of charge and the grid operator’s requirements.
The battery supplies or absorbs active energy when the selected PCS and controller respond to a regulation signal. Reserve availability must respect battery voltage, temperature, charge/discharge limits and state of charge. Frequency response is a complete-system function, not a standalone guarantee from the battery enclosure.
Discharging during defined high-load intervals can reduce the peak power requested from a connection or support a constrained node. Suitability depends on the local load profile, connection limit and required duration. Any infrastructure-deferral or revenue case needs a project study; the battery rating alone does not establish the result.
Narrow cold plates and 314 Ah cells provide approximately 5 MWh in a 20 ft high-cube container. The stated container footprint is below 15 m²; the complete plant still needs service clearances, fire separation, PCS equipment and access roads.
Water-and-glycol cooling is specified with a temperature difference of <2.5°C (battery cells). Narrow cold plates and active balancing support the compact architecture. Thermal performance contributes to consistent operation; it does not eliminate degradation or replace operating limits.
Pack, cluster, battery-bank and system-level fuse protection is described, together with cell-to-cluster insulation, pack/container sensing, gas and water suppression, active exhaust and explosion venting. Final equipment, water interfaces and fire strategy are confirmed with the manufacturing partner and site designers.
AI-based remaining-life and safety-risk prediction, active balancing and automatic cluster switching are described as maintenance-support features. The non-walk-in enclosure allows external maintenance. Monitoring supports inspection and planning but is not a guarantee of uninterrupted availability.
In the illustrated AC-coupled example, the battery DC output connects to a compatible bidirectional PCS, then through the project transformer and switchgear to the grid. A photovoltaic plant connects through its own inverter and interface equipment to the AC collector. Plant EMS/PPC coordinates dispatch and exchanges status with the BMS. This battery container does not connect directly to PV strings or the AC grid. Alternative architectures require an approved project design.
| Parameter | Specification |
|---|---|
| Model | YT-Utility ESS-5015kWh |
| Cell chemistry / specification | LFP / 3.2 V / 314 Ah |
| Rated battery energy | 5015.96 kWh; P2 at 25 ±3°C |
| Nominal DC voltage | 1331.2 V |
| Battery voltage range | 1164.8–1497.6 V |
| Charge / discharge rate | ≤0.5 CP |
| Source maximum charge / discharge power | 2500 kW; configuration reference, not guaranteed AC export |
| Battery charging temperature | 0 to +50°C |
| Battery discharging temperature | −20 to +55°C |
| Recommended ambient temperature | 25 ±10°C |
| Cycle life | ≥6000 cycles; 25 ±10°C; 90% DOD; 80% EOL |
| Parameter | Specification |
|---|---|
| Cooling method / medium | Liquid cooling / water + glycol |
| Temperature difference | <2.5°C (battery cells) |
| BMS architecture | 3-level |
| Auxiliary power supply | Approx. 40 kW; 400 V / 50 Hz; 3N + PE |
| Fire suppression | Perfluorohexanone + water; S-type aerosol / HFC-227EA optional |
| Ingress protection | IP55 |
| Corrosion protection | C4; C5 optional |
| Lightning protection | Level II |
| Parameter | Specification |
|---|---|
| System operating temperature | −20 to +50°C; derating above 45°C |
| Storage conditions | −20 to +55°C; less than 6 months |
| Operating humidity | 0–95% RH; non-condensing |
| Altitude | ≤3000 m |
| Installation | Outdoor; non-walk-in external maintenance |
| Daily duty | Up to 2 charges and 2 discharges per day |
| Dimensions (W × D × H) | 6058 × 2438 × 2896 mm (20 ft) |
| Approximate weight | 41 t |
| Parameter | Specification |
|---|---|
| Communication interfaces | CAN / Ethernet / RS485 |
| External communication protocol | Modbus TCP |
| PCS and AC grid connection | Separately specified project equipment |
| Plant EMS / PPC | Project-level control scope to be confirmed |
| Standards listed in source | GB/T 36276; GB/T 34131 |
Auxiliary AC supply ratings describe internal service power, not AC export capability. “CP” and “P2” are source designations retained without reinterpretation. Nameplate battery energy is not guaranteed usable AC energy. Standards are source references; confirm certificates and test-report scope for the supplied configuration. The source describes an AC-coupled configuration using 215 kW modular PCS units. This listing is for the DC battery container; PCS inclusion, topology and the 2500 kW configuration rating require separate project agreement.
Use generation and grid-dispatch profiles to define AC power, usable energy, delivery duration and reserve commitments. Evaluate auxiliary demand, conversion losses, temperature derating and the agreed end-of-life capacity target.
YINTU coordinates battery and PCS interface reviews with manufacturing partners. Check the full DC voltage window, communications, grid requirements, foundations, lifting access, corrosion conditions and maintenance clearances.
Confirm the battery supply boundary, external PCS, plant EMS/PPC, transformer, switchgear, protection, auxiliary power, civil works, fire design and commissioning responsibilities. Grid connection and local approvals are project-specific.
The published scope is the DC battery container. A compatible PCS and the required AC/MV interface are specified separately. The auxiliary AC supply does not make the container a standalone grid-connected system.
No direct PV-string interface is offered in this listing. Solar integration requires the appropriate PV inverter or DC conversion architecture, protection and plant controls. The illustrated scheme is one possible AC-coupled arrangement.
Start with the required AC MW, usable MWh, dispatch duration and end-of-life target. Account for the usable SOC window, conversion losses, auxiliary demand, temperature derating and reserve commitments. Select the converter against the entire battery voltage window and the agreed charge/discharge limits.
These functions require a specifically engineered complete system, including suitable PCS controls, auxiliary-power arrangements, protection and an approved operating sequence. They are not standalone capabilities guaranteed by this DC battery container.
No. The ≥6000-cycle figure applies under the stated test conditions, depth of discharge and end-of-life threshold. Warranty terms and expected degradation for the actual operating profile require a separate agreement.
Share the required AC power and usable energy, solar generation profile, grid connection voltage, dispatch schedule, site climate and available layout. YINTU can coordinate battery selection, PCS matching and technical clarification with manufacturing partners for a defined project scope.
Parameters are based on the supplied model datasheet and remain subject to final technical confirmation. Illustrations show application concepts, not completed YINTU projects. Listed standards require configuration-specific documentation; cycle life and design life are not warranty commitments.
Company Details
Business Type:
Distributor/Wholesaler,Exporter,Trading Company
Year Established:
2016
Total Annual:
$ 10 million-$ 20,million
Employee Number:
50~100
Ecer Certification:
Verified Supplier
Your Partner for Energy Storage Product Sourcing YINTU Energy is the energy storage business of Hunan Yintu New Materials Co., Ltd. Established in 2016, our company has 10-50 employees and an export share of 100%. We connect overseas distributors, installers, EPC companies and project buyers with... Your Partner for Energy Storage Product Sourcing YINTU Energy is the energy storage business of Hunan Yintu New Materials Co., Ltd. Established in 2016, our company has 10-50 employees and an export share of 100%. We connect overseas distributors, installers, EPC companies and project buyers with...
Get in touch with us
Leave a Message, we will call you back quickly!