| Supply Ability | 30000 sets per year |
| Delivery Time | 15-20 working days after payment or receipt of L/C |
| discharge_time | <= 10 s |
| Packaging Details | Plywood outer case with bubble bag and paper corner protection |
| max_filling_weight | 114 kg |
| relief_pressure | 5.0 +/- 0.225 MPa |
| power_supply | DC 24V / 1.6A |
| Payment Terms | T/T, L/C |
| storage_pressure | 2.5 MPa |
| extinguishing_agent | HFC-227ea (heptafluoropropane) |
| cylinder_capacity | 120 L, red epoxy coated |
| zone_configuration | Single zone total flooding |
| working_temperature | 0 to 50 degrees C |
| cabinet_dimension | 550 x 550 x 1900 mm |
| actuation_mode | Automatic, electrical manual, mechanical manual |
| Brand Name | xingjin |
| Certification | CCC, CNAS, CMA, ILAC-MRA |
| Place of Origin | China |
| Model Number | GQQ120 |
View Detail Information
Explore similar products
120L Cylinder Capacity GB25972-2010 Certified Enclosed Flooding FM200 Gas
100L Cylinder Manual Actuation FM200 Gas Suppression System Colorless Tasteless
Totally Automatic One Zone FM200 Fire Suppression System with No Pipeline for
40L Single Cabinet FM200 Fire Extinguishing System Pipe Network FM200 Gas
Product Specification
| Supply Ability | 30000 sets per year | Delivery Time | 15-20 working days after payment or receipt of L/C |
| discharge_time | <= 10 s | Packaging Details | Plywood outer case with bubble bag and paper corner protection |
| max_filling_weight | 114 kg | relief_pressure | 5.0 +/- 0.225 MPa |
| power_supply | DC 24V / 1.6A | Payment Terms | T/T, L/C |
| storage_pressure | 2.5 MPa | extinguishing_agent | HFC-227ea (heptafluoropropane) |
| cylinder_capacity | 120 L, red epoxy coated | zone_configuration | Single zone total flooding |
| working_temperature | 0 to 50 degrees C | cabinet_dimension | 550 x 550 x 1900 mm |
| actuation_mode | Automatic, electrical manual, mechanical manual | Brand Name | xingjin |
| Certification | CCC, CNAS, CMA, ILAC-MRA | Place of Origin | China |
| Model Number | GQQ120 | ||
| High Light | 120L HFC-227ea cylinder ,red cabinet suppression unit ,clean agent total flooding | ||
The 120L red HFC-227ea fire suppression system is a factory-assembled, self-contained cabinet unit engineered for total flooding protection of rooms where water-based extinguishing would destroy the very assets it is meant to save. At the heart of the unit sits a 120 litre cylinder finished in high-visibility red epoxy, filled with HFC-227ea (heptafluoropropane) clean agent to a maximum working weight of 114 kg.
Because the agent is stored as a liquefied gas and discharged as a colourless, electrically non-conductive vapour, the system extinguishes a fire in under ten seconds and leaves no powder, foam or water residue behind. Each cabinet arrives pre-piped, pre-wired and pressure tested, so commissioning on site is reduced to fixing the enclosure, connecting DC24V power and running the discharge nozzle into the protected room.
| Parameter | Specification |
|---|---|
| Extinguishing agent | HFC-227ea (heptafluoropropane, FM200) |
| Cylinder capacity | 120 L |
| Maximum filling weight | 114 kg |
| Storage pressure | 2.5 MPa |
| Relief valve pressure | 5.0 ± 0.225 MPa |
| Maximum working pressure | 4.2 MPa |
| Discharge time | ≤ 10 s |
| Working temperature | 0 °C to 50 °C |
| Power supply | DC 24 V / 1.6 A |
| Cabinet dimensions | 550 x 550 x 1900 mm (L x W x H) |
| Actuation mode | Automatic, electrical manual, mechanical manual |
| Extinguishing pattern | Enclosed total flooding, single zone |
The 120L red HFC-227ea system is specified wherever a fire must be stopped inside a sealed room without damaging the contents. Typical installations include data centres and server halls, telecom base station shelters, UPS and battery rooms, process control rooms, archive and record storage, museum display areas, clean rooms, anechoic chambers, medical imaging suites and emergency power facilities.
The same cabinet also protects high-risk production zones such as paint spraying lines, oil-immersed transformers, printing machinery, ageing racks and generator rooms, because the clean agent works on energised electrical equipment without risk of short circuits.
Because the cylinder, valve, solenoid, nozzle, detectors and release panel leave the factory as one tested assembly, installation requires no pipe network calculation and no welding on site. A two-person crew normally positions the cabinet, anchors it to the floor, connects the 220V feed to the panel and routes the discharge pipe through the wall into the protected space.
Cylinders are refillable, the pressure gauge is visible through the cabinet door, and a five-year quality guarantee covers the vessel and valve assembly.
Each system is packed in a plywood outer case with bubble bag and paper corner protection, strapped and moisture sealed for sea freight. Every cylinder is hydrostatically tested and every valve is helium leak checked before shipment, and the unit is supplied with filling certificates, a pressure test report, an installation and commissioning manual and a wiring diagram.
Delivery is normally 15 to 20 working days after receipt of payment or confirmed L/C, with a supply capacity of 30,000 sets per year.
Company Details
Business Type:
Manufacturer,Exporter
Year Established:
2010
Total Annual:
600000-1200000
Employee Number:
100~300
Ecer Certification:
Verified Supplier
About Us: Guangzhou Xingjin Fire Equipment Co., Ltd. is a professional enterprise dedicated to the research, development and production of HFC-227ea (FM200), Novec1230, CO2 and inert gas products. For many years, the company has been committed to improving product quality, enriching pro... About Us: Guangzhou Xingjin Fire Equipment Co., Ltd. is a professional enterprise dedicated to the research, development and production of HFC-227ea (FM200), Novec1230, CO2 and inert gas products. For many years, the company has been committed to improving product quality, enriching pro...
Get in touch with us
Leave a Message, we will call you back quickly!