| Payment Terms | L/C,D/A,D/P,T/T,Western Union |
| Supply Ability | 5000-10000 pieces/mouth |
| Delivery Time | 7-15 days |
| Packaging Details | box |
| SPD Type | T2、T3 (IEC 61643.11) |
| Nominal Operating Voltage (Un) | 220Vac(50Hz) |
| Maximum Continuous Operating Voltage (Uc) | 320Vac(50Hz) |
| Nominal Discharge Current (In) | 5kA/10kA |
| Voltage Protection Level (Up) | ≤1.25kV (LPF 5) / ≤1.5kV (LPF 10) |
| Response Time | ≤25ns |
| Brand Name | LLH |
| Model Number | LPF 5-320 |
| Place of Origin | Guangdong Province.China |
View Detail Information
Explore similar products
Nylon Surge Protection Devices Spds LED SPD 220V 5kA 10kA IP67 Outdoor Lightning
Outdoor Led Surge Protection Device 220V 320V 10kA 20kA IP67 T2 T3 SPD
Outdoor Street Light Led Spd Surge Protector IP67 T2 T3 220V 320V 10kA 20kA
Outdoor Led Lighting Spd 220V 5kA 10kA AC DC Surge Protection Device IP67 T2 T3
Product Specification
| Payment Terms | L/C,D/A,D/P,T/T,Western Union | Supply Ability | 5000-10000 pieces/mouth |
| Delivery Time | 7-15 days | Packaging Details | box |
| SPD Type | T2、T3 (IEC 61643.11) | Nominal Operating Voltage (Un) | 220Vac(50Hz) |
| Maximum Continuous Operating Voltage (Uc) | 320Vac(50Hz) | Nominal Discharge Current (In) | 5kA/10kA |
| Voltage Protection Level (Up) | ≤1.25kV (LPF 5) / ≤1.5kV (LPF 10) | Response Time | ≤25ns |
| Brand Name | LLH | Model Number | LPF 5-320 |
| Place of Origin | Guangdong Province.China | ||
| High Light | LED SPD surge protection device ,Outdoor LED SPD 220V ,Industrial lighting surge protector IP67 | ||
| Product Features |
|
● One port, full mode protection
|
|
● Small size and easy installation
|
|
● Protection level up to IP67
|
|
● Suitable for installation in LPZ 2-3 and subsequent lightning protection zones, parallel installation in the front end of the final level equipment of the AC/DC power supply system, widely used as lightning protectors for LED street lights, sensors, and other equipment
|
|
Standards
|
IEC 61643-11
|
|
|
SPD type
|
T2,T3
|
|
|
Models
|
LPF 5-320
|
LPF-10-320
|
|
Electrical parameters
|
||
|
Nominal operating voltage Un
|
220Vac(50Hz)
|
|
|
Maximum continuous operating voltage Uc
|
320Vac(50Hz)
|
|
|
Nominal discharge current (8/20μs)In
|
5kA
|
10kA
|
|
Maximum discharge current (8/20μs) Imax
|
10kA
|
20kA
|
|
Voltage protection level In@Up
|
≤1.25kV
|
≤1.5kV
|
|
Response time tA
|
≤25ns
|
≤25ns
|
|
Protection Circuit
|
L-N,L-E,N-E
|
L-N,L-E,N-E
|
|
Failure and alarm
|
||
|
Deterioration indication
|
LED green: OK; Off: Fail (optional function)
|
|
|
Fixed method
|
φ4mmFixing lug
|
|
Wire length
|
200mm
|
|
Wire cross-sectional area
|
1.5mm2
|
|
Product size
|
42mmx30mmx23mm
|
|
Shell material and flame retardant grade
|
Nylon,VO
|
|
Installation position
|
Indoor and outdoor
|
|
Degrees of protection provided by enclosure
|
IP67
|
|
Temperature range
|
-40℃…+80℃
|
|
Humidity range
|
Relative humidity ≤ 95% (max 40 ℃)
|
Notices
1.This product is engineered for parallel installation at the front end of LED street lights and sensing devices, to provide surge protection for outdoor equipment.
2.Utilize the included φ4mm mounting lugs to ensure a secure installation, enhancing resistance to wind-induced forces and mechanical vibration in outdoor environments.
3.Properly seal all wiring connections to preserve the product’s IP67 ingress protection rating, preventing dust and moisture ingress.
4.Avoid mounting the device in locations prone to heavy mechanical shock or exposure to corrosive chemicals, to maintain long-term performance.
5.Replace the SPD promptly if the optional LED status indicator turns off (indicating device failure) or after experiencing a severe surge event.
6.This product is designed exclusively for AC 220Vac power systems; always verify the system voltage before installation to ensure compatibility.
FAQ
Q1: Does this device have any status indicators, and what do they mean?
A1: Yes, it features an optional green LED indicator. When the light is solid green, it indicates that the SPD is functioning normally and providing protection. If the light turns off or changes state, it signals a fault or degradation, prompting an immediate replacement to maintain safety.
Q2: What is the response time of this SPD, and why is it important?
A2: It has an ultra-fast response time of less than 25 nanoseconds (≤25ns). This rapid reaction time is crucial because it can instantly clamp dangerous transient overvoltages caused by lightning or power grid fluctuations, preventing damage to sensitive electronic components before they occur.
Q3: How do I know when the SPD needs to be replaced?
A3:
Q4: What kind of surge waveforms can this SPD handle?
A4: It is tested and certified to handle standard 8/20μs lightning surge waveforms, which are the most common in outdoor lightning protection scenarios, effectively absorbing and diverting surge currents from lightning strikes.
Q5:Is this SPD flame retardant? What safety features does it have?
A5:Yes, its shell is made of V0 flame-retardant nylon, which self-extinguishes within 10 seconds after ignition, preventing fire spread. It also has overvoltage protection between poles, enhancing overall safety.
Company Details
Business Type:
Manufacturer
Year Established:
2018
Total Annual:
1000000-10000000
Employee Number:
20~100
Ecer Certification:
Verified Supplier
Shenzhen Leilihai Electric Co., Ltd We are a high-tech enterprise that integrates the research and development, manufacturing, sales, and installation services of lightning protection devices and lightning protection system supporting products. The company has successively passed the German TUV cer... Shenzhen Leilihai Electric Co., Ltd We are a high-tech enterprise that integrates the research and development, manufacturing, sales, and installation services of lightning protection devices and lightning protection system supporting products. The company has successively passed the German TUV cer...
Get in touch with us
Leave a Message, we will call you back quickly!