| Conductor (×2, N/PE) | Copper, Class 2 stranded, nominal 19×∅2.52 mm (95 mm²), conductor Ø ≈ 12–14 mm |
| Overall cable diameter | 58 – 70 mm |
| Packaging Details | General Packaging or As Requirements |
| Armour | Double steel tape, thickness 0.5 mm × 2 layers (overlapped) |
| Conductor material | Copper (Cu) |
| Outer sheath thickness | 3.0 mm |
| Bedding thickness | 1.5 mm |
| Conductor class | Class 2 stranded |
| Supply Ability | 100000 meters per month |
| Conductor nominal area | 185 mm² (phase, ×3), 95 mm² (N/PE, ×2) |
| Conductor construction (N/PE) | 19×∅2.52 mm (95 mm²) |
| Armour (steel tape) | 0.5 mm × 2 layers |
| Approx. weight | 7.5 – 9.0 kg/m (7500–9000 kg/km) |
| Insulation (all cores) | XLPE (cross-linked polyethylene), nominal thickness 1.4 mm (for 0.6/1 kV class), colours: red/black (phase), blue (neutral), yellow/green (earth) |
| Conductor (×3, phase) | Copper, Class 2 stranded, nominal 37×∅2.52 mm (185 mm²), conductor Ø ≈ 17–19 mm |
| Design outer diameter | ≈ 64 mm |
| Filler & bedding | PVC filler, round profile, inner PVC bedding thickness ≈ 1.5 mm |
| Design weight | ≈ 8200 kg/km |
| Payment Terms | L/C,T/T |
| Outer sheath | PVC (polyvinyl chloride), flame retardant Category C compound, nominal thickness 3.0 mm (typical), colour: black |
| Insulation thickness | 1.4 mm |
| Delivery Time | Less than 15 days |
| Number of cores | 5 |
| Conductor construction (phase) | 37×∅2.52 mm (185 mm²) |
| Model Number | ZC-YJV22-3x185mm²+2x95mm² |
| Certification | CE/ISO/CCC |
| Brand Name | TONGDU |
| Place of Origin | China |
View Detail Information
Explore similar products
High Capacity 5 Core Flex ZR-YJV 4x300mm2+1x150mm2 XLPE Copper Flame Retardant
0.6/1kV ZC-YJV 5x16mm² Copper XLPE PVC Flame-Retardant Power Cable for
WDZBN-YJY 5 Core 3x50mm²+2x25mm² Low Smoke Halogen Free Fire Resistant XLPE
50mm2 Copper 5 Core Armoured Cable XLPE For Indoor Outdoor Power Distribution
Product Specification
| Conductor (×2, N/PE) | Copper, Class 2 stranded, nominal 19×∅2.52 mm (95 mm²), conductor Ø ≈ 12–14 mm | Overall cable diameter | 58 – 70 mm |
| Packaging Details | General Packaging or As Requirements | Armour | Double steel tape, thickness 0.5 mm × 2 layers (overlapped) |
| Conductor material | Copper (Cu) | Outer sheath thickness | 3.0 mm |
| Bedding thickness | 1.5 mm | Conductor class | Class 2 stranded |
| Supply Ability | 100000 meters per month | Conductor nominal area | 185 mm² (phase, ×3), 95 mm² (N/PE, ×2) |
| Conductor construction (N/PE) | 19×∅2.52 mm (95 mm²) | Armour (steel tape) | 0.5 mm × 2 layers |
| Approx. weight | 7.5 – 9.0 kg/m (7500–9000 kg/km) | Insulation (all cores) | XLPE (cross-linked polyethylene), nominal thickness 1.4 mm (for 0.6/1 kV class), colours: red/black (phase), blue (neutral), yellow/green (earth) |
| Conductor (×3, phase) | Copper, Class 2 stranded, nominal 37×∅2.52 mm (185 mm²), conductor Ø ≈ 17–19 mm | Design outer diameter | ≈ 64 mm |
| Filler & bedding | PVC filler, round profile, inner PVC bedding thickness ≈ 1.5 mm | Design weight | ≈ 8200 kg/km |
| Payment Terms | L/C,T/T | Outer sheath | PVC (polyvinyl chloride), flame retardant Category C compound, nominal thickness 3.0 mm (typical), colour: black |
| Insulation thickness | 1.4 mm | Delivery Time | Less than 15 days |
| Number of cores | 5 | Conductor construction (phase) | 37×∅2.52 mm (185 mm²) |
| Model Number | ZC-YJV22-3x185mm²+2x95mm² | Certification | CE/ISO/CCC |
| Brand Name | TONGDU | Place of Origin | China |
| High Light | ZC-YJV22 5 Core Cable ,5 Core Cable 3x185mm2 ,2x95mm2 armoured xlpe cable | ||
ZC-YJV22 5 Core 3x185mm²+2x95mm² Armored XLPE Flame Retardant Copper Cable 0.6/1kV
|
Code |
Meaning |
|---|---|
|
ZC |
Flame retardant Category C (GB/T 18380.3 / IEC 60332-3-24, Class C) |
|
YJ |
XLPE (cross-linked polyethylene) insulation |
|
V |
PVC outer sheath |
|
22 |
Steel tape armoured (double steel tape) |
|
3×185 mm² |
Three phase cores, each 185 mm² copper |
|
+2×95 mm² |
Two additional cores, each 95 mm² copper (typically 1×N + 1×PE) |
Construction: Copper conductors, XLPE insulation, steel tape armour, PVC sheath, 5-core low voltage power cable with flame retardant Category C.
![]()
![]()
1. Overview & Ratings. ZC-YJV22 3×185+2×95 is a 5-core (3P+N+PE) low-voltage steel tape armored XLPE power cable rated 0.6/1 kV (Um = 1.2 kV), 90 °C continuous. Built per GB/T 12701 / IEC 60502-1, ZC flame retardant per GB/T 19666. Three 185 mm² phase conductors plus two 95 mm² N/PE conductors. Finished OD ≈ 62 mm, ≈ 8200 kg/km, on wooden drums.
2. Construction Stack (Conductor → Outer).
| Layer | Build | Wall | Diameter |
|---|---|---|---|
| Phase conductors (×3) | Compacted stranded Cu, Class 2, 3×185 mm² | — | ≈ 16 mm each |
| N/PE conductors (×2) | Compacted stranded Cu, Class 2, 2×95 mm² | — | ≈ 11.6 mm each |
| XLPE insulation | Cross-linked polyethylene | 1.8 (phase) / 1.6 (N) | 19.6 / 14.8 mm |
| Filler + binder | PP filler + non-woven tape | — | ≈ 56 mm |
| Steel tape armor | Double steel tape, gap-wrapped | 0.5 + 0.5 mm | ≈ 58.5 mm |
| PVC outer sheath | PVC, dark grey, ST2 | ≈ 2.5 mm | ≈ 62 mm |
3. Electrical Characteristics. Phase DC resistance ≤ 0.0991 Ω/km; N/PE resistance ≤ 0.193 Ω/km at 20 °C. Routine test 3.5 kV AC / 5 min; insulation resistance ≥ 36.7 MΩ·km; capacitance ≤ 0.45 μF/km. Nominal ampacity ≈ 370 A (air, 25 °C).
|
Property |
Value |
|---|---|
|
Material |
XLPE (cross-linked polyethylene) |
|
Nominal thickness |
1.4 mm (0.6/1 kV class) |
|
Long-term service temp. |
90 °C |
|
Short-circuit temp. (≤5 s) |
250 °C (Cu conductor limit) |
|
Emergency overload temp. |
130 °C |
|
Routine test voltage (AC, 5 min) |
3.5 kV (for 0.6/1 kV) |
|
Type-test voltage (AC) |
4.0 kV (for 0.6/1 kV) |
|
Partial discharge test |
≤ 10 pC at 1.73 U₀ (1.04 kV) |
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
GB/T 12706.1 / IEC 60502-1 |
|
Max. system voltage Uₘ |
1.2 kV |
— |
|
Test voltage AC (5 min) |
3.5 kV |
Routine test |
|
DC resistance @20 °C (185 mm²) |
≤ 0.0991 Ω/km |
GB/T 3956 Class 2 Cu max |
|
DC resistance @20 °C (95 mm²) |
≤ 0.193 Ω/km |
GB/T 3956 Class 2 Cu max |
|
AC resistance @90 °C (est., 185 mm²) |
≈ 0.126 Ω/km |
per phase core |
|
AC resistance @90 °C (est., 95 mm²) |
≈ 0.246 Ω/km |
N/PE core |
|
Capacitance (approx.) |
≈ 0.30 µF/km |
core to sheath |
|
Inductive reactance (approx.) |
≈ 0.09 Ω/km |
at 50 Hz, 5-core armoured |
|
Current rating in air (30 °C) |
335 A |
3-phase loaded, 3×185 mm² (derated for 5-core) |
|
Current rating buried (20 °C) |
295 A |
direct buried, 5-core |
|
Current rating in conduit (30 °C) |
280 A |
3-phase, 5-core |
|
Short-circuit current (1 s, Cu, 250 °C, 185 mm²) |
≈ 18.5 kA (18500 A) |
per phase core |
|
Short-circuit current (1 s, Cu, 250 °C, 95 mm²) |
≈ 9.5 kA (9500 A) |
per N/PE core |
|
Frequency |
50/60 Hz AC |
— |
Reference values: 185 mm² Cu at 335 A, 3-phase 400 V → max balanced load ≈ 232 kVA. Voltage drop at 335 A ≈ 42.2 V/km per phase core (≈1.8% per 100 m at 400 V).
4. Thermal & Fire. 90 °C continuous; 250 °C short-circuit (≤ 5 s); ambient −20~+45 °C. ZC flame retardant per GB/T 19666 — GB/T 18380.12 single-burn + GB/T 18380.35 class-C bunched.
|
Property |
Value |
|---|---|
|
Max. conductor operating temp. |
90 °C (continuous) |
|
Max. short-circuit temp. (≤5 s) |
250 °C (Cu conductor) |
|
Emergency overload temp. |
130 °C |
|
Min. installation ambient temp. |
0 °C (PVC sheath); below 0 °C pre-heating required |
|
Service ambient range |
−20 °C to +90 °C (with PVC sheath) |
|
Fire survival |
Flame retardant Category C (IEC 60332-3-24) |
|
Property |
Value / Requirement |
|---|---|
|
Flame retardant |
IEC 60332-3-24 Category C (bunched cable test, flame propagation ≤ 2.5 m) |
|
Halogen content |
Contains halogen (PVC sheath & XLPE) |
|
Smoke density |
Standard (non-low-smoke) |
|
Corrosivity |
Corrosive (PVC) |
|
Fire survival (circuit integrity) |
Not applicable (flame retardant only); use NH-YJV22 for circuit integrity |
5. Installation Practice & Handling. Bend ≥ 15 × OD ≈ 930 mm. Direct burial, trench, duct, or tray. Site DC test 2.4 kV / 15 min before energizing. Armor must be grounded at both ends. At 8200 kg/km, use cable rollers. Pre-heat drums below 0 °C.
|
Parameter |
Value |
Remarks |
|---|---|---|
|
Minimum bending radius |
≥ 15 × OD → ≈ 960 mm at Ø64 mm |
static installation |
|
Max. pulling tension |
18500 N |
Cu conductor, use proper pulling grips |
|
Direct burial |
Excellent (steel tape armour protects from mechanical damage) |
use warning tape |
|
Conduit ID |
≥ 1.5 × OD → ≥ 96 mm; use 100 mm, 125 mm or 150 mm |
— |
|
Fixing |
cable clamps, tray, direct buried |
— |
|
Impact resistance |
High (steel tape armour) |
— |
|
Water resistance |
Good (PVC sheath + armour) |
not watertight |
|
UV resistance |
Good (black PVC, outdoor rated) |
— |
|
Termination note |
Cu conductors — standard compression lugs or mechanical lugs |
strip length 25–30 mm per core |
6. Typical Service Applications. LV distribution mains, transformer secondaries, heavy industrial feeders, commercial building risers — where direct burial and mechanical protection are required.
![]()
7. Testing & QA Regime. Routine: conductor DC resistance, 3.5 kV AC withstand, insulation resistance, dimensional check. Type: XLPE heating test, bending test, flame retardancy, short-circuit test.
Cable Parameters
| ZC-YJV22 3×185+2×95 mm² — LV Steel Tape Armored XLPE Power Cable — Full Parameter Sheet | ||||
| 5-core (3+2) armored cable · Cu conductors / XLPE insulation / double steel tape armor / PVC sheath · 0.6/1 kV · ZC flame retardant · ≈ 62 mm | ||||
| Section | Parameter | Value | Unit | Remarks / Standard |
| 01 · Identification | ||||
| Cable type | ZC-YJV22 — LV steel tape armored XLPE power cable | — | Armored power | |
| Rated voltage (U0/U) | 0.6/1 | kV | LV distribution | |
| Number of cores | 3 × 185 + 2 × 95 | — | 3P + N + PE | |
| Conductor material | Annealed copper, compacted stranded | — | Class 2 per GB/T 3956 | |
| Insulation material | XLPE (cross-linked polyethylene) | — | 90 °C rated | |
| Armor type | Double steel tape (22) | — | Steel tape armored | |
| Sheath material | PVC (outer) | — | Dark grey | |
| Flame retardant | ZC (Class C) | — | GB/T 19666 | |
| Standard | GB/T 12701 / IEC 60502-1 | — | LV power cable | |
| 02 · Conductor (Cu) | ||||
| Conductor type | Compacted stranded annealed copper | — | Class 2 | |
| Phase conductor area | 3 × 185 | mm² | L1/L2/L3 | |
| Neutral/earth area | 2 × 95 | mm² | N + PE | |
| Phase stranding | ≈ 60 × 2.05 mm | — | 185 mm² | |
| N/PE stranding | ≈ 19 × 2.53 mm | — | 95 mm² | |
| DC resistance (phase) @ 20 °C | ≤ 0.0991 | Ω/km | Cu 185 mm² | |
| DC resistance (N/PE) @ 20 °C | ≤ 0.193 | Ω/km | Cu 95 mm² | |
| Conductor weight per km | ≈ 2550 | kg/km | 5-core Cu | |
| 03 · Insulation | ||||
| Insulation type | XLPE (cross-linked polyethylene) | — | Thermoset | |
| Phase insulation thickness | ≈ 1.8 | mm | 185 mm² | |
| N/PE insulation thickness | ≈ 1.6 | mm | 95 mm² | |
| Phase core OD | ≈ 19.6 | mm | Insulated | |
| N/PE core OD | ≈ 14.8 | mm | Insulated | |
| 04 · Armor & Sheath | ||||
| Armor type | Double steel tape, gap-wrapped | — | 22 | |
| Armor thickness | ≈ 0.5 + 0.5 | mm | Two layers | |
| Sheath type | PVC outer sheath | — | ST2 | |
| Sheath thickness | ≈ 2.5 | mm | LV | |
| Finished outer diameter | ≈ 62 | mm | Overall | |
| Sheath color | Dark grey / black | — | Standard | |
| 05 · Electrical | ||||
| Rated voltage (U0/U) | 0.6/1 | kV | LV | |
| Max voltage | 1.2 | kV | Um | |
| DC resistance (phase) @ 20 °C | ≤ 0.0991 | Ω/km | Cu 185 | |
| Test voltage (AC) | 3.5 kV / 5 min | — | Routine | |
| Insulation resistance | ≥ 36.7 | MΩ·km | XLPE | |
| Nominal current (ampacity) | ≈ 370 | A | Air, 25 °C | |
| Capacitance | ≤ 0.45 | μF/km | XLPE | |
| 06 · Thermal & Fire | ||||
| Max conductor temp. | 90 | °C | XLPE continuous | |
| Short-circuit temp. | 250 | °C | Max 5 s | |
| Ambient range | -20 ~ +45 | °C | Underground / outdoor | |
| Laying temperature | ≥ 0 | °C | Direct burial / trench | |
| Flame retardancy | ZC (Class C) | — | GB/T 19666 | |
| 07 · Mechanical | ||||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 930 | mm | Armed | |
| Crush resistance | Good (steel armor) | — | Direct burial | |
| Pulling force | Moderate | — | Armed | |
| 08 · Installation | ||||
| Laying methods | Direct burial, trench, duct, tray | — | Armed cable | |
| Bending radius | ≥ 15 × OD ≈ 930 mm | — | Armed | |
| Site test | 4U0 = 2.4 kV DC / 15 min | — | Before energizing | |
| Connectors | Cu lugs for 185 / 95 mm² | — | Compression | |
| 09 · Packing | ||||
| Standard supply length | 100 m / drum | m | Large drum | |
| Reel / packing type | Wooden drum | — | Export standard | |
| Surface marking | ZC-YJV22, 3×185+2×95, 0.6/1kV, GB/T 12701 | — | Continuous printing | |
| Approx. cable weight | ≈ 8200 | kg/km | 5-core armored | |
| 10 · Applications | ||||
| Typical use | LV distribution mains, transformer secondaries, industrial feeders | — | Power distribution | |
| Application level | Low voltage | — | 0.6/1 kV | |
| Installation type | Direct burial / trench / duct | — | Armed | |
Cable Test Parameters
| Test Parameters — ZC-YJV22 3×185+2×95 mm² Armored Cable | ||||
| No. | Test Item | Test Condition / Method | Requirement | Type |
| 1 | Conductor DC resistance | GB/T 3956, 20 °C | ≤ 0.0991 Ω/km (185); ≤ 0.193 Ω/km (95) | Routine |
| 2 | Voltage test (AC) | 3.5 kV AC, 5 min | No breakdown | Routine |
| 3 | Insulation resistance | 5000 V DC | ≥ 36.7 MΩ·km | Routine |
| 4 | Insulation thickness | Micrometer | ≥ 1.8 mm (185); ≥ 1.6 mm (95) | Routine |
| 5 | XLPE heating test | 90 °C conductor, 4 h | No damage | Type |
| 6 | Bending test | 15× OD, cycles | No damage | Type |
| 7 | Flame retardancy | GB/T 19666 Class C | ZC certified | Type |
| 8 | Dimensional check | Caliper | OD ≈ 62 mm | Routine |
| 9 | Armor continuity | Per GB/T 12701 | Steel tape continuous | Routine |
| 10 | Sheath test | Voltage / thickness | PVC ≥ 2.5 mm | Routine |
| 11 | Short-circuit test | 250 °C, 5 s | No damage | Type |
| 12 | Printing legibility | Visual | Marking readable | Routine |
Cable Cross Section Stucture
![]()
| ZC-YJV22 3×185+2×95 mm² — Cross-Section Construction Diagram (Schematic) | |||||
| 5-core (3+2) armored: Cu conductors → XLPE insulation → filler/binder → double steel tape armor → PVC sheath · 0.6/1 kV · ≈ 62 mm | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Phase conductors (×3) | Compacted stranded Cu, Class 2, 3×185 mm² | — | ≈ 16 each | R ≤ 0.0991 Ω/km |
| 2 | N/PE conductors (×2) | Compacted stranded Cu, Class 2, 2×95 mm² | — | ≈ 11.6 each | R ≤ 0.193 Ω/km |
| 3 | XLPE insulation | Cross-linked polyethylene | 1.8 (phase) / 1.6 (N) | 19.6 / 14.8 | 90 °C rated |
| 4 | Filler + binder tape | PP filler + non-woven tape | — | ≈ 56 | Round out the core |
| 5 | Steel tape armor | Double steel tape, gap-wrapped | 0.5 + 0.5 | ≈ 58.5 | 22 armor |
| 6 | PVC outer sheath | PVC, dark grey, ST2 | ≈ 2.5 | ≈ 62 | Outer protection |
| Key Dimensions & Properties (expanded) | |||||
| Finished cable diameter | ≈ 62 | mm | Overall | ||
| Approx. cable mass | ≈ 8200 | kg/km | 5-core armored Cu | ||
| Nominal voltage rating | 0.6/1 | kV | LV distribution | ||
| Max conductor temp. | 90 | °C | XLPE continuous | ||
| Short-circuit temp. | 250 | °C | Max 5 s | ||
| Min bending radius (fixed) | ≥ 15 × OD ≈ 930 | mm | Armed | ||
| DC resistance (phase) @ 20 °C | ≤ 0.0991 | Ω/km | Cu 185 mm² | ||
| DC resistance (N/PE) @ 20 °C | ≤ 0.193 | Ω/km | Cu 95 mm² | ||
| Test voltage (AC) | 3.5 kV / 5 min | — | Routine | ||
| Nominal current (ampacity) | ≈ 370 | A | Air, 25 °C | ||
| Number of cores | 3P + N + PE (5) | — | 5-core | ||
| Armor type | Double steel tape (22) | — | Direct burial | ||
| Flame retardancy | ZC (Class C) | — | GB/T 19666 | ||
| Standard | GB/T 12701 / IEC 60502-1 | — | LV power | ||
| Schematic — not to exact scale. Finished OD ≈ 62 mm and weight ≈ 8200 kg/km from cross-referenced industry samples. ZC-YJV22 3×185+2×95 is a 5-core (3P+N+PE) LV steel tape armored XLPE power cable. Values marked (est.) require confirmation against the factory test certificate. | |||||
Construction Description
| Construction Description — ZC-YJV22 3×185+2×95 mm² armored LV power cable | |||
| Layer-by-layer armored power cable: Cu conductors / XLPE insulation / filler / double steel tape armor / PVC sheath · 0.6/1 kV · 90 °C · ≈ 62 mm | |||
| 1. Product Identity & Ratings | |||
| ZC-YJV22 3×185+2×95 is a 5-core (3P+N+PE) low-voltage steel tape armored XLPE power cable rated 0.6/1 kV, 90 °C continuous. Built per GB/T 12701 / IEC 60502-1, ZC flame retardant per GB/T 19666. Designed for distribution mains and direct burial. Finished OD ≈ 62 mm, mass ≈ 8200 kg/km, on wooden drums. | |||
| 2. Five Copper Conductors (3+2) | |||
| Three 185 mm² phase conductors (compact stranded Cu, ~60×2.05 mm) plus two 95 mm² conductors for neutral and protective earth (~19×2.53 mm). Phase resistance ≤ 0.0991 Ω/km; N/PE resistance ≤ 0.193 Ω/km at 20 °C. | |||
| 3. XLPE Insulation | |||
| Cross-linked polyethylene insulation, 1.8 mm on phase cores and 1.6 mm on N/PE cores. XLPE operates at 90 °C continuous (250 °C short-circuit), higher than PVC. This allows higher ampacity for the same cross-section. | |||
| 4. Steel Tape Armor (22) | |||
| Double steel tape armor gap-wrapped over the cored assembly. Provides mechanical protection for direct burial — resists crush and rodent damage. The armor must be grounded at both ends for safety. | |||
| 5. Site Handling & Operational Notes | |||
| • Bend radius 15×OD (≈ 930 mm). • Direct burial / trench / duct. • Site DC test 2.4 kV / 15 min before energizing. • Armor must be grounded. • At 8200 kg/km, heavy — use cable rollers. • Pre-heat below 0 °C. |
8. Standards & Conformity. GB/T 12701 (LV power cables); IEC 60502-1 (international); GB/T 3956 (conductors); GB/T 19666 (ZC flame retardant).
9. Packaging, Storage & Logistics. Wooden drums, 100 m per drum. Continuous marking: ZC-YJV22, 3×185+2×95, 0.6/1kV, GB/T 12701. Store indoors, dry.
![]()
10. Procurement Specification. State "ZC-YJV22 0.6/1 kV 3×185+2×95" + drum length. Confirm against factory test certificate.
11. Cable Industry FAQ.
Company Details
Business Type:
Manufacturer,Exporter,Trading Company
Year Established:
2009
Total Annual:
50000000-100000000
Employee Number:
260~300
Ecer Certification:
Verified Supplier
Company Profile — Anhui Tongdu Cable Co., Ltd. Company Overview Anhui Tongdu Cable Co., Ltd. (hereinafter "Tongdu Cable") is a professional wire and cable manufacturer headquartered in Zongyang Economic Development Zone, Anhui Province, China. Founded in 2009, the company has grown into one of... Company Profile — Anhui Tongdu Cable Co., Ltd. Company Overview Anhui Tongdu Cable Co., Ltd. (hereinafter "Tongdu Cable") is a professional wire and cable manufacturer headquartered in Zongyang Economic Development Zone, Anhui Province, China. Founded in 2009, the company has grown into one of...
Get in touch with us
Leave a Message, we will call you back quickly!