China ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distributio
China ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distributio

  1. China ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distributio

ZR-YJV 4 Core Electrical Cable 4x185mm2 Flame Retardant Copper Power Distributio

  1. MOQ: 1 Meter
  2. Price:
  3. Get Latest Price
Conductor nominal area 185 mm²
Packaging Details General Packaging or As Requirements
Conductor diameter 16.8–18.5 mm
Filler / binder FR PP filler + FR tape
Cable shape Round
Approx. weight 6200 – 7800 kg/km
Outer sheath Flame-retardant PVC (ZR grade)
Supply Ability 10000 meters per month
Insulation thickness 1.6 mm (185 mm² class)
Overall cable diameter 45.0 – 52.0 mm
Design weight ≈ 6700 kg/km
Number of cores 4
Conductor (×4) Bare annealed copper, Class 2 stranded, commonly 37×∅2.52 mm (also 19×∅3.55 mm compact / 36×2.55 mm), conductor Ø ≈ 16.8–18.5 mm depending on compaction
Conductor construction Class 2, 37×∅2.52 mm,IEC 60228 / GB/T 3956, min. 15 wires
Payment Terms L/C,T/T
Insulation (×4) XLPE
Design outer diameter ≈ 48.0 mm
Delivery Time Less than 15 days
Diameter over insulated core 20.0–21.7 mm,conductor + 2×1.6
Sheath thickness 2.4 mm (GB/T 12706 multi-core 150–300 mm² range)
Model Number ZR-YJV 4*185mm²
Certification CE/ISO/CCC
Brand Name TD
Place of Origin China

View Detail Information

Inquiry by Email Get Latest Price
Chat online Now Ask for best deal
  1. Product Details
  2. Company Details

Product Specification

Conductor nominal area 185 mm² Packaging Details General Packaging or As Requirements
Conductor diameter 16.8–18.5 mm Filler / binder FR PP filler + FR tape
Cable shape Round Approx. weight 6200 – 7800 kg/km
Outer sheath Flame-retardant PVC (ZR grade) Supply Ability 10000 meters per month
Insulation thickness 1.6 mm (185 mm² class) Overall cable diameter 45.0 – 52.0 mm
Design weight ≈ 6700 kg/km Number of cores 4
Conductor (×4) Bare annealed copper, Class 2 stranded, commonly 37×∅2.52 mm (also 19×∅3.55 mm compact / 36×2.55 mm), conductor Ø ≈ 16.8–18.5 mm depending on compaction Conductor construction Class 2, 37×∅2.52 mm,IEC 60228 / GB/T 3956, min. 15 wires
Payment Terms L/C,T/T Insulation (×4) XLPE
Design outer diameter ≈ 48.0 mm Delivery Time Less than 15 days
Diameter over insulated core 20.0–21.7 mm,conductor + 2×1.6 Sheath thickness 2.4 mm (GB/T 12706 multi-core 150–300 mm² range)
Model Number ZR-YJV 4*185mm² Certification CE/ISO/CCC
Brand Name TD Place of Origin China
High Light ZR-YJV 4 core electrical cable ,4 core electrical cable 4x185mm2 ,copper power wire 300mm2

ZR-YJV 4*185mm² Flame Retardant 4 Core Copper Power Distribution Cable


Code

Meaning

ZR

Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC).

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC outer sheath — flame-retardant grade, contains halogen (Cl)

0.6/1 kV

Rated voltage U₀/U = 600/1000 V; Uₘ = 1.2 kV

4×185 mm²

Four cores, nominal copper conductor area 185 mm² per core

ZR-YJV 4×185 mm² — Cable Engineering Data

1. Product Scope & Ratings. ZR-YJV 4×185 — flame-retarding four-core cable, four 185 mm² Cu conductors, XLPE insulation, one ST2 PVC sheath, rated 0.6/1 kV (Um = 1.2 kV), 50 Hz; manufactured and tested per GB/T 12706.1 / IEC 60502-1, conductor grading per GB/T 3956, ZC flame class per GB/T 19666. ≈ 56.8 mm, ≈ 8034 kg/km (Al ≈ 3310), 100 m coils/drums.



2. Construction Stack. Conductor → outer sheath:


Layer Build Wall Diameter
Conductor (×4) Annealed Cu, Class 2, 37 × 2.52 mm (1+6+12+18) each — ≈ 17.60 mm
Insulation (×4) XLPE 1.6 mm ≈ 20.80 mm
Lay-up Four cores + central filler + binder tape — ≈ 50.2 mm (calc.)
Sheath Flame-retarded PVC, ST2, black 2.4 mm ≈ 56.8 mm



3. Electrical Ratings. R ≤ 0.0991 Ω/km @ 20 °C; routine 3.5 kV / 5 min; insulation resistance ≥ 36.7 MΩ·km; XLPE volume resistivity ≥ 1×10¹² Ω·cm; capacitance ≤ 0.45 μF/km. Reference ampacity (four cores loaded) ≈ 375 A air / 390 A buried @ 25 °C — Mingda 4×185, cross-checked with 3×185 (identical per-core values).


Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

Uₘ = 1.2 kV

Test voltage AC (5 min)

3.5 kV

Routine

Type-test voltage

4.0 kV

IEC 60502-1

DC resistance @20 °C (Class 2 Cu, per core)

≤ 0.0991 Ω/km

GB/T 3956 max

AC resistance @90 °C (est.)

≈ 0.129 Ω/km

per core

Current rating in air (30 °C, single circuit, 4-core)

≈ 390–420 A

common catalogue value

Current rating in air (design)

≈ 400 A

apply grouping + ambient correction

Direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m)

≈ 410–460 A

common catalogue 420–450 A

Design buried rating

≈ 435 A

soil thermal resistivity correction required

Short-circuit current (1 s, Cu, 250 °C, per core)

≈ 18.5 kA

reference

Frequency

50/60 Hz AC

—


4. Thermal & Fire. 90 °C continuous, 250 °C short-circuit (≤ 5 s); −20~+45 °C ambient, ≥ 0 °C laying; ZC per GB/T 19666 — GB/T 18380.12 single-burn + GB/T 18380.35 class-C bunched (char ≤ 2.5 m); PVC is halogen-bearing → WDZ-YJY for LSZH.



ZR-YJV 4×185 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1)
Stage Test Item Method / Standard Acceptance Criterion Notes
Routine Conductor DC resistance GB/T 3956 (IEC 60228) ≤ 0.0991 Ω/km @ 20 °C (per core) Every production length
Routine Power-frequency withstand voltage GB/T 12706.1 / IEC 60502-1 3.5 kV AC / 5 min, no breakdown Conductor-to-earth/water
Routine Construction check GB/T 2951 Ins. ≥ 1.6 mm; sheath ≥ 2.4 mm; OD within tolerance Thickness & diameter
Sample Hot set test — XLPE GB/T 12706.1 §16.3.13 / GB/T 2951.11 200 ± 3 °C, 15 min, 0.2 MPa: load elongation ≤ 175 %; permanent ≤ 15 % Cross-linking degree
Sample Conductor construction & diameter GB/T 3956 Class 2; 37 × 2.52 mm; Ø ≈ 17.60 mm Per batch
Type Single-cable flame test GB/T 18380.12 No flame spread to top reference ZR property
Type Bunched flame test — class C GB/T 18380.35 Char ≤ 2.5 m; 20 min; ≥ 1.5 L/m ZC class
Type Bending test GB/T 12706.1 No damage on specified mandrel Multi-core rule
Post-install DC withstand test Q/GDW 13244.1-2018 2.4 kV DC / 15 min, no breakdown New installations
Optional Insulation resistance @ 20 °C Factory method ≥ 36.7 MΩ·km Not routine in GB/T 12706.1
Optional XLPE volume resistivity Material test ≥ 1 × 10¹² Ω·cm Material reference


5. Installation & Care. Bend ≥ 15 × OD; DC site test 4U0 = 2.4 kV / 15 min before energising (Q/GDW 13244.1-2018); pre-heat drums below 0 °C; de-rate 375/390 A for ambient, grouping, burial; lugs/glands for the 17.60 mm core.



6. Flame Retardant Test Parameters


Technical Datasheet — Flame-Retardant (FR) Characteristics
ZR-YJV  0.6/1 kV  4 × 185 mm²  (Cu / XLPE / FR-PVC)
1.  Cable Identification
Code / Item Meaning / Value Standard / Note
ZR Flame Retardant (legacy prefix); under GB/T 19666-2019 defaults to Class C; modern equivalent = ZC GB/T 19666-2019
YJ XLPE — cross-linked polyethylene insulation —
V PVC outer sheath — flame-retardant grade, contains halogen (Cl) GB/T 19666-2019
0.6/1 kV Rated voltage U₀/U = 600/1000 V; maximum Uₘ = 1.2 kV IEC 60502-1
4 × 185 mm² Four cores, nominal copper conductor area 185 mm² per core (all cores equal) —
Construction Unarmoured, non-screened, round multi-core —
Application note Four-core → three-phase AC with neutral (L1+L2+L3+N) or with PE (L1+L2+L3+PE), equal conductor sizes —
2.  Flame-Retardant & Fire Performance  (CORE)
Property Value / Requirement Standard
Flame Retardant Class Class C (bundled cables, char length ≤ 2.5 m) GB/T 19666-2019; GB/T 18380.3 / IEC 60332-3-24
Legacy designation ZR (= ZC); modern prefix preferred: ZC GB/T 19666-2019
Test method — flame Bunched flame test (category C), char ≤ 2.5 m after flame removal GB/T 18380.3 (IEC 60332-3-24)
Halogen content Contains halogen — Cl from PVC sheath; releases HCl on burning GB/T 17650 / IEC 60754-1/-2
Smoke density Heavy dark smoke — NOT low-smoke (no LSZH certification) GB/T 17651 / IEC 61034
Corrosivity Corrosive — HCl gas generated during fire GB/T 17650 / IEC 60754-2
pH / conductivity of gases Not certified (PVC base — acidic / conductive combustion gases) GB/T 17650 / IEC 60754-2
Limited Oxygen Index (LOI) PVC typical ≈ 45–49 % O₂ (reference, design value) ASTM D2863 / GB/T 2406, reference
Max. conductor operating temp. 90 °C (long-term service) GB/T 12706.1-2020
Max. short-circuit temp. (≤5 s) 250 °C IEC 60502-1
Emergency overload temp. 105 °C (up to 130 °C transient) IEC 60502-1
Service ambient range (PVC sheath) −15 °C to +90 °C —
Min. installation ambient temp. 0 °C (pre-heat required below 0 °C) —
Note: ZR = Flame Retardant only — it does NOT imply low-smoke (LSZH) or fire-survival. PVC sheath is halogenated; upgrade to WDZ-YJY / WDZN-YJY for LSZH or NH-ZR-YJV for fire-survival circuits.
3.  Fire Test Summary
Test Requirement ZR-YJV 4×185 Verdict
Bunched flame test (Class C) Char length ≤ 2.5 m PASS (design, Class C)
Single flame test (IEC 60332-1) Self-extinguishing PASS (XLPE/PVC FR)
Smoke density (IEC 61034) Light transmittance ≥ 60 % for LSZH N/A (PVC = heavy smoke)
Halogen content (IEC 60754) ≤ 0.5 % HCl for LSZH N/A (contains Cl)
Acidity / corrosivity (IEC 60754-2) pH ≥ 4.3; conductivity ≤ 10 µS/mm for LSZH N/A (corrosive HCl)
Fire-survival (BS 6387 / IEC 60331) Circuit integrity during/after fire N/A — use NH-ZR-YJV / WDZN-YJY
4.  Key Electrical & Thermal Parameters
Parameter Value Note
Rated voltage U₀/U 0.6 / 1 kV Uₘ = 1.2 kV
Test voltage AC (5 min, routine) 3.5 kV IEC 60502-1
Type-test voltage 4.0 kV IEC 60502-1
DC resistance @ 20 °C (per core) ≤ 0.0991 Ω/km GB/T 3956 / IEC 60228, Class 2 max
AC resistance @ 90 °C (est.) ≈ 0.129 Ω/km per core
Current rating — in air (30 °C, single circuit) ≈ 390–420 A (design ≈ 400 A) 4-core
Current rating — direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m) ≈ 410–460 A (design ≈ 435 A) 4-core
Short-circuit current (1 s, Cu, 250 °C, per core) ≈ 18.5 kA reference
Frequency 50/60 Hz AC —
Design recommendation: ≈ 400 A in air / ≈ 435 A buried, then apply grouping & ambient + soil-thermal-resistivity correction. Buried rating often > air rating due to better heat dissipation under reference conditions. Catalogue values vary by maker — confirm before specification.
5.  Construction & Material Specification
Layer (inside → out) Description / Specification FR Contribution
Conductor (×4) Bare annealed copper, Class 2 stranded, 37×∅2.52 mm, conductor Ø ≈ 16.8–18.5 mm None (Cu non-combustible)
Conductor screen Omitted (not required for 0.6/1 kV) —
Insulation (×4) XLPE, colours: brown/black/grey/blue etc., 1.6 mm nominal XLPE — low flame spread
Filler Flame-retardant PP / PE to form round assembly FR additive
Binder Flame-retardant tape over laid-up cores FR barrier
Outer sheath Flame-retardant PVC (ZR grade), 2.4 mm nominal, black Primary FR layer (halogenated)
Armour None —
Metallic screen None —
6.  Dimensional Data
Item Typical Value Remarks
Conductor nominal area (per core) 185 mm² —
Number of cores 4 —
Conductor construction Class 2, 37×∅2.52 mm IEC 60228 / GB/T 3956, min. 15 wires
Conductor diameter (approx.) 16.8–18.5 mm compact vs solid-round
Insulation thickness 1.6 mm 185 mm² class
Diameter over insulated core 20.0–21.7 mm conductor + 2×1.6
Sheath thickness 2.4 mm GB/T 12706, 150–300 mm² range
Overall cable diameter ≈ 46.0–50.0 mm (catalogue range 45.0–52.0 mm) plain-round design
Design outer diameter ≈ 48.0 mm common Chinese maker value
Approx. weight 6200 – 7800 kg/km (plain YJV Cu ≈ 6400–7000) design ≈ 6700 kg/km
Cable shape Round —



7.  Mechanical & Installation Parameters
Parameter Value Note
Minimum bending radius (unarmoured multi-core) ≥ 15 × OD ≈ 675–720 mm @ Ø45–48 mm (≈ 720 mm @ 48 mm) —
Max. pulling tension (Cu only) 50 N/mm² × 185 mm² × 4 = 37,000 N = 37 kN total use conductor sock, avoid sheath grip
Direct burial Allowed in non-aggressive soil; for mechanical load / road crossing use ZR-YJV22 4×185 —
Conduit ID ≥ 1.5 × OD → ≥ 68–72 mm (use 75 mm or 90 mm conduit) —
Fixing spacing Horizontal tray ≈ 800 mm; vertical ≈ 1500 mm —
Elevation difference limit None (XLPE) —
8.  Selection Guide — When FR Matters
Scenario Recommended Cable Reason
Flame-retardant, halogenated acceptable (standard) ZR-YJV 4×185 (this cable) Class C FR, PVC sheath, cost-effective
Low-smoke halogen-free required (LSZH) WDZ-YJY 4×185 LSZH sheath — IEC 61034 / IEC 60754 compliant
Fire-survival circuit (circuit integrity) NH-ZR-YJV / WDZN-YJY 4×185 BS 6387 / IEC 60331 fire-survival grade
Heavy mechanical load / buried under roads ZR-YJV22 4×185 Steel-tape armoured version
Separate PE and N required 5-core version (e.g. 5×185 or 4×185+1×95) 4×185 has combined/shared PE-N only
Applicable standards: GB/T 12706.1-2020 (equiv. IEC 60502-1) · GB/T 3956 / IEC 60228 · GB/T 19666-2019 · GB/T 18380.3 · GB/T 17651 / IEC 61034 · GB/T 17650 / IEC 60754.  |  Packing: steel-wooden drum or coil, 100–500 m typical.  |  HS code (China): 8544 4921.
Values are typical / design reference. Plain-round 185 mm² shows maker-to-maker dimensional variance (OD 45–52 mm, weight 6200–7800 kg/km) — always confirm with manufacturer test reports & relevant local regulations before final specification.



7.Cross Section Structure



Four-core construction from conductor to outer sheath · nominal values per GB/T 12706.1 / IEC 60502-1 · not to exact scale
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (Cu) × 4 Annealed copper, Class 2 stranded — 37 × 2.52 mm per core (37/2.52, 1+6+12+18), nominal 185 mm² per core — ≈ 17.60 (Ø per core) Current-carrying element; max DC resistance ≤ 0.0991 Ω/km @ 20 °C (per core)
2 Insulation (XLPE) × 4 Cross-linked polyethylene 1.6 ≈ 20.80 (Ø per core, over insulation) Dielectric barrier; rated 90 °C continuous; withstands 3.5 kV / 5 min
3 Core lay-up Four insulated cores laid up around central non-hygroscopic filler; binder tape — ≈ 50.2 (Ø over lay-up, calc.) Forms a round assembly for sheathing
4 Outer sheath (PVC) Flame-retardant PVC, ST2 type, black 2.4 ≈ 56.8 (Ø overall) Mechanical & moisture protection; flame retardance ZC (ZR) per GB/T 19666
Key Dimensions & Properties
Overall diameter ≈ 56.8 mm Mingda four-core unarmored table

Approx. cable weight ≈ 8034 kg/km Mingda 8034 (Al ≈ 3310)

Rated voltage 0.6/1 kV AC 50 Hz; max system voltage Um = 1.2 kV

Max conductor temperature 90 / 250 °C Continuous / short-circuit (≤ 5 s)

Min. bending radius (multi-core) ≥ 15 × OD — OD = actual cable diameter

Flame-retardant class ZC (ZR) — GB/T 19666

Schematic — not to exact scale. Nominal values for reference; confirm against factory test certificate.



8. Application. Heavy distribution risers, plant rooms, large motor and transformer circuits, industrial sub-feeds — conduit, tray, trench, duct, trunking; indoor or sheltered outdoor.




9. Ordering. ZR-YJV 0.6/1 kV 4×185 + length/drum + marking; confirm against factory test certificate.





Company Details

Bronze Gleitlager

,

Bronze Sleeve Bushings

 and 

Graphite Plugged Bushings

 from Quality China Factory
  • Business Type:

    Manufacturer,Exporter,Trading Company

  • Year Established:

    2009

  • Total Annual:

    50000000-100000000

  • Employee Number:

    260~300

  • Ecer Certification:

    Verified Supplier

Company Profile — Anhui Tongdu Cable Co., Ltd. Company Overview Anhui Tongdu Cable Co., Ltd. (hereinafter "Tongdu Cable") is a professional wire and cable manufacturer headquartered in Zongyang Economic Development Zone, Anhui Province, China. Founded in 2009, the company has grown into one of... Company Profile — Anhui Tongdu Cable Co., Ltd. Company Overview Anhui Tongdu Cable Co., Ltd. (hereinafter "Tongdu Cable") is a professional wire and cable manufacturer headquartered in Zongyang Economic Development Zone, Anhui Province, China. Founded in 2009, the company has grown into one of...

+ Read More

Get in touch with us

  • Reach Us
  • Anhui Tongdu International Trade Co., Ltd.
  • Room 2003,B Building,Jiaqiao International Plaza,Baohe District,Hefei City,Anhui Province
  • https://www.power-cabling.com/

Leave a Message, we will call you back quickly!

Email

Check your email

Phone Number

Check your phone number

Requirement Details

Your message must be between 20-3,000 characters!

Submit Requirement