China Copper Conductor 4 Cores Cable ZR-YJV 4x240mm2 Flame Retardant Cable For
China Copper Conductor 4 Cores Cable ZR-YJV 4x240mm2 Flame Retardant Cable For

  1. China Copper Conductor 4 Cores Cable ZR-YJV 4x240mm2 Flame Retardant Cable For

Copper Conductor 4 Cores Cable ZR-YJV 4x240mm2 Flame Retardant Cable For

  1. MOQ: 1 Meter
  2. Price:
  3. Get Latest Price
Conductor nominal area (per core) 240 mm²
Packaging Details General Packaging or As Requirements
Conductor diameter (approx.) 19.0–21.0 mm
Filler / binder FR PP filler + FR tape
Cable shape Round
Approx. weight 7600 – 9500 kg/km
Outer sheath Flame-retardant PVC (ZR grade)
Supply Ability 10000 meters per month
Insulation thickness 1.7 mm (240 mm² class)
Overall cable diameter 50.0 – 58.0 mm
Design weight ≈ 8200 kg/km
Number of cores 4
Conductor (×4) Bare annealed copper, Class 2 stranded, commonly 61×∅2.25 mm (also 37×∅2.87 mm compact / 48×2.52 mm), conductor Ø ≈ 19.0–21.0 mm depending on compaction
Conductor construction Class 2, 61×∅2.25 mm,IEC 60228 / GB/T 3956, min. 15 wires
Payment Terms L/C,T/T
Insulation (×4) XLPE
Design outer diameter ≈ 53.0 mm
Delivery Time Less than 15 days
Diameter over insulated core 22.4–24.4 mm,conductor + 2×1.7
Sheath thickness 2.5 mm (GB/T 12706 multi-core 185–300 mm² range)
Model Number ZR-YJV 4*240mm²
Certification CE/ISO/CCC
Brand Name TD
Place of Origin China

View Detail Information

Inquiry by Email Get Latest Price
Chat online Now Ask for best deal
  1. Product Details
  2. Company Details

Product Specification

Conductor nominal area (per core) 240 mm² Packaging Details General Packaging or As Requirements
Conductor diameter (approx.) 19.0–21.0 mm Filler / binder FR PP filler + FR tape
Cable shape Round Approx. weight 7600 – 9500 kg/km
Outer sheath Flame-retardant PVC (ZR grade) Supply Ability 10000 meters per month
Insulation thickness 1.7 mm (240 mm² class) Overall cable diameter 50.0 – 58.0 mm
Design weight ≈ 8200 kg/km Number of cores 4
Conductor (×4) Bare annealed copper, Class 2 stranded, commonly 61×∅2.25 mm (also 37×∅2.87 mm compact / 48×2.52 mm), conductor Ø ≈ 19.0–21.0 mm depending on compaction Conductor construction Class 2, 61×∅2.25 mm,IEC 60228 / GB/T 3956, min. 15 wires
Payment Terms L/C,T/T Insulation (×4) XLPE
Design outer diameter ≈ 53.0 mm Delivery Time Less than 15 days
Diameter over insulated core 22.4–24.4 mm,conductor + 2×1.7 Sheath thickness 2.5 mm (GB/T 12706 multi-core 185–300 mm² range)
Model Number ZR-YJV 4*240mm² Certification CE/ISO/CCC
Brand Name TD Place of Origin China
High Light Copper Conductor 4 Cores Cable ,4 Cores Cable ZR-YJV ,4x240mm2 Flame Retardant Cable

Copper Conductor ZR-YJV 4*240mm² Flame Retardant Cable for Industrial Wiring


Code

Meaning

ZR

Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC).

YJ

XLPE (cross-linked polyethylene) insulation

V

PVC outer sheath — flame-retardant grade, contains halogen (Cl)

0.6/1 kV

Rated voltage U₀/U = 600/1000 V; Uₘ = 1.2 kV

4×240 mm²

Four cores, nominal copper conductor area 240 mm² per core

ZR-YJV 4×240 mm² — Cable Engineering Specification 

1. Product Identification & Ratings. ZR-YJV 4×240 — flame-retarding four-core cable, four 240 mm² Cu conductors, XLPE insulation, one ST2 PVC sheath, rated 0.6/1 kV (Um = 1.2 kV), 50 Hz; built and proof-tested per GB/T 12706.1 / IEC 60502-1, stranding per GB/T 3956, ZC fire class per GB/T 19666. ≈ 64.0 mm, ≈ 10452 kg/km (Al ≈ 4242), 100 m coils/drums.


2. Construction Stack. Conductor → outer sheath:

Layer Build Wall Diameter
Conductor (×4) Annealed Cu, Class 2, 61 × 2.25 mm (1+6+12+18+24) each — ≈ 20.2 mm
Insulation (×4) XLPE 1.7 mm ≈ 23.6 mm
Lay-up Four cores + central filler + binder tape — ≈ 57.0 mm (calc.)
Sheath Flame-retarded PVC, ST2, black 2.6 mm ≈ 64.0 mm


3. Electrical Ratings. R ≤ 0.0754 Ω/km @ 20 °C; routine 3.5 kV / 5 min; insulation resistance ≥ 36.7 MΩ·km; XLPE volume resistivity ≥ 1×10¹² Ω·cm; capacitance ≤ 0.45 μF/km. Reference ampacity (four cores loaded) ≈ 440 A air / 450 A buried @ 25 °C — Mingda 4×240, cross-checked with 3×240 (identical per-core values).


Parameter

Value

Note

Rated voltage U₀/U

0.6 / 1 kV

Uₘ = 1.2 kV

Test voltage AC (5 min)

3.5 kV

Routine

Type-test voltage

4.0 kV

IEC 60502-1

DC resistance @20 °C (Class 2 Cu, per core)

≤ 0.0754 Ω/km

GB/T 3956 max

AC resistance @90 °C (est.)

≈ 0.098 Ω/km

per core

Current rating in air (30 °C, single circuit, 4-core)

≈ 460–495 A

common catalogue value

Current rating in air (design)

≈ 475 A

apply grouping + ambient correction

Direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m)

≈ 480–535 A

common catalogue 490–520 A

Design buried rating

≈ 505 A

soil thermal resistivity correction required

Short-circuit current (1 s, Cu, 250 °C, per core)

≈ 24.0 kA

reference

Frequency

50/60 Hz AC

—


4. Cable Structure


Layer

Description

Conductor (×4)

Bare annealed copper, Class 2 stranded, commonly 61×∅2.25 mm (also 37×∅2.87 mm compact / 48×2.52 mm), conductor Ø ≈ 19.0–21.0 mm depending on compaction

Conductor screen

Omitted (not required for 0.6/1 kV)

Insulation (×4)

XLPE,

Insulation thickness

1.7 mm (240 mm² class)

Filler

Flame-retardant PP/PE to form round assembly

Binder

Flame-retardant tape over laid-up cores

Inner binder / assembly

FR tape, no inner sheath required for plain YJV

Outer sheath

Flame-retardant PVC (ZR grade)

Sheath thickness

2.5 mm (GB/T 12706 multi-core 185–300 mm² range)

Sheath colour

Black (standard)


5.Cable Basic Parameters and Test Parameters



ZR-YJV 4×240 mm² — Test / Verification Parameters (per GB/T 12706.1 & IEC 60502-1)
Stage Test Item Method / Standard Acceptance Criterion Notes
Routine Conductor DC resistance GB/T 3956 (IEC 60228) ≤ 0.0754 Ω/km @ 20 °C (per core) Every production length
Routine Power-frequency withstand voltage GB/T 12706.1 / IEC 60502-1 3.5 kV AC / 5 min, no breakdown Conductor-to-earth/water
Routine Construction check GB/T 2951 Ins. ≥ 1.7 mm; sheath ≥ 2.6 mm; OD within tolerance Thickness & diameter
Sample Hot set test — XLPE GB/T 12706.1 §16.3.13 / GB/T 2951.11 200 ± 3 °C, 15 min, 0.2 MPa: load elongation ≤ 175 %; permanent ≤ 15 % Cross-linking degree
Sample Conductor construction & diameter GB/T 3956 Class 2; 61 × 2.25 mm; Ø ≈ 20.2 mm Per batch
Type Single-cable flame test GB/T 18380.12 No flame spread to top reference ZR property
Type Bunched flame test — class C GB/T 18380.35 Char ≤ 2.5 m; 20 min; ≥ 1.5 L/m ZC class
Type Bending test GB/T 12706.1 No damage on specified mandrel Multi-core rule
Post-install DC withstand test Q/GDW 13244.1-2018 2.4 kV DC / 15 min, no breakdown New installations
Optional Insulation resistance @ 20 °C Factory method ≥ 36.7 MΩ·km Not routine in GB/T 12706.1
Optional XLPE volume resistivity Material test ≥ 1 × 10¹² Ω·cm Material reference


6. Thermal & Fire. 90 °C continuous, 250 °C short-circuit (≤ 5 s); −20~+45 °C ambient, ≥ 0 °C laying; ZC per GB/T 19666 — GB/T 18380.12 single-burn + GB/T 18380.35 class-C bunched (char ≤ 2.5 m); PVC is halogen-bearing → WDZ-YJY for LSZH.



7. Installation & Care. Bend ≥ 15 × OD; DC site test 4U0 = 2.4 kV / 15 min before energising (Q/GDW 13244.1-2018); pre-heat drums below 0 °C; de-rate 440/450 A for ambient, grouping, burial; lugs/glands for the 20.2 mm core.


Insulation Test Data
ZR-YJV  0.6/1 kV  4 × 240 mm²  (Cu / XLPE / FR-PVC)
1.  Cable Identification
Item Description Standard / Note
Designation ZR-YJV 0.6/1 kV 4×240 mm² GB/T 12706.1-2020
Conductor Bare annealed copper, Class 2 stranded, 61×∅2.25 mm GB/T 3956 / IEC 60228
Insulation XLPE (cross-linked polyethylene), 1.7 mm nominal GB/T 12706.1-2020
Outer sheath Flame-retardant PVC (ZR grade), 2.5 mm nominal, black GB/T 19666-2019
Rated voltage U₀/U 0.6 / 1 kV (Uₘ = 1.2 kV) IEC 60502-1
Number of cores 4 (three-phase L1+L2+L3+N or L1+L2+L3+PE, equal sizes) —
2.  Insulation Design Data  (CORE)
Parameter Value Remarks
Insulation material XLPE (cross-linked polyethylene) —
Nominal thickness (eₙ) 1.7 mm 240 mm² class
Minimum allowable thickness (e_min) 1.36 mm eₙ − 0.34 mm (GB/T 12706.1-2020, Table 3)
Insulator colours Brown/black/grey/blue or red/yellow/blue/green-yellow (or as specified) IEC 60446
Volume resistivity @ 90 °C ≥ 10¹² Ω·cm —
Dielectric loss factor (tan δ) @ 20 °C ≤ 1 × 10⁻³ reference
Relative permittivity (εᵣ) ≈ 2.3 – 2.5 reference
Long-term service temp. 90 °C GB/T 12706.1-2020
Short-circuit temp. (≤ 5 s) 250 °C IEC 60502-1
Emergency overload temp. 105 – 130 °C transient
Diameter over insulated core 22.4–24.4 mm conductor 19.0–21.0 + 2×1.7
3.  Thermal Characteristics
Property Value Remarks
Max. conductor operating temp. (normal) 90 °C long-term
Max. conductor temp. — short-circuit (≤ 5 s) 250 °C IEC 60502-1
Emergency overload temp. 105 °C (up to 130 °C transient) —
Min. installation ambient temp. 0 °C (pre-heat below 0 °C) —
Service ambient range (PVC sheath) −15 °C to +90 °C —
Flame retardant class (sheath) Class C (ZR per GB/T 19666) —
4.  Insulation Test Schedule
Test Item Test Value / Condition Result
Routine withstand test (AC) 3.5 kV AC, 5 min — no breakdown PASS
Type test voltage 4.0 kV AC PASS (IEC 60502-1)
Partial discharge test ≤ 10 pC @ 1.73 U₀ (1.73 kV) PASS (XLPE)
Insulation resistance (IR) ≥ 10⁴ MΩ·km @ 20 °C (reference) PASS
Hot-set test (XLPE cross-linking) 200 °C, 15 min, load 0.2 N/mm² — elongation ≤ 175 %, permanent set ≤ 15 % PASS (IEC 60811-507)
Aging test (air oven) 135 °C, 168 h — tensile strength / elongation retained ≥ 80 % PASS
Tensile strength (insulation) ≥ 12.5 MPa (XLPE, before aging) PASS
Elongation at break (insulation) ≥ 200 % (XLPE, before aging) PASS
Cold bend test −15 °C, 4 h — no cracking PASS
Water absorption ≤ 1 mg/cm² (85 °C, 336 h, reference) PASS
Breakdown voltage (insulation) ≥ 20 kV/mm (reference) PASS
DC resistance of conductor @ 20 °C ≤ 0.0754 Ω/km (Class 2 Cu, per core) PASS (GB/T 3956)
Dielectric loss (tan δ) measurement ≤ 1 × 10⁻³ @ 20 °C PASS (reference)
Spark test (during production) 6 – 10 kV (online), pinhole detection PASS
Thickness measurement (microscopic) eₙ = 1.7 mm; e_min ≥ 1.36 mm PASS
5.  Electrical Parameters
Parameter Value Note
Rated voltage U₀/U 0.6 / 1 kV Uₘ = 1.2 kV
Test voltage AC (5 min, routine) 3.5 kV IEC 60502-1
Type-test voltage 4.0 kV IEC 60502-1
DC resistance @ 20 °C (per core) ≤ 0.0754 Ω/km GB/T 3956 / IEC 60228, Class 2 max
AC resistance @ 90 °C (est.) ≈ 0.098 Ω/km per core
Current rating — in air (30 °C, single circuit) ≈ 460–495 A (design ≈ 475 A) 4-core
Current rating — direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m) ≈ 480–535 A (design ≈ 505 A) 4-core
Short-circuit current (1 s, Cu, 250 °C, per core) ≈ 24.0 kA reference
Frequency 50/60 Hz AC —
6.  Dimensional / Inspection Result
Item Design / Limit Measured (example)
Conductor construction Class 2, 61×∅2.25 mm 61×2.25 mm
Conductor diameter 19.0–21.0 mm 20.2 mm
Insulation thickness (each core) 1.7 mm (min. 1.36 mm) 1.72 / 1.70 / 1.71 / 1.68 mm
Diameter over insulated core 22.4–24.4 mm 23.4 mm
Sheath thickness 2.5 mm (min. 2.2 mm) 2.51 mm
Overall cable diameter ≈ 51.0–55.0 mm (range 50.0–58.0) 53.2 mm
DC resistance @ 20 °C (per core) ≤ 0.0754 Ω/km 0.0745 Ω/km
Approx. weight 7600 – 9500 kg/km (design ≈ 8200) 8150 kg/km
Footnotes
1. All tests performed at ambient 20 ± 5 °C and 45–75 % RH unless otherwise stated.
2. Routine tests: withstand (3.5 kV / 5 min), conductor resistance, dimensional check. Type tests: 4.0 kV, partial discharge, hot-set, aging, mechanical (per IEC 60502-1).
3. Test values marked “reference” are typical design values — confirm against manufacturer test report / GB/T 12706.1-2020.
4. Insulation thickness for 240 mm² class = 1.7 mm nominal (GB/T 12706.1-2020, Table 3); minimum = 1.7 − 0.34 = 1.36 mm. Sheath thickness = 2.5 mm for 185–300 mm² range.
5. For low-smoke halogen-free → use WDZ-YJY 4×240; for fire-survival → NH-ZR-YJV / WDZN-YJY 4×240; for armoured → ZR-YJV22 4×240.
6. Plain-round 240 mm² shows maker-to-maker dimensional variance (OD 50–58 mm, weight 7600–9500 kg/km); design values are mid-range estimates — verify with manufacturer catalog.


8.Cross Section Structure



Four-core construction from conductor to outer sheath · nominal values per GB/T 12706.1 / IEC 60502-1 · not to exact scale
No. Layer Material / Construction Nominal Thickness (mm) Diameter (mm) Function / Remarks
1 Conductor (Cu) × 4 Annealed copper, Class 2 stranded — 61 × 2.25 mm per core (61/2.25, 1+6+12+18+24), nominal 240 mm² per core — ≈ 20.2 (Ø per core) Current-carrying element; max DC resistance ≤ 0.0754 Ω/km @ 20 °C (per core)
2 Insulation (XLPE) × 4 Cross-linked polyethylene 1.7 ≈ 23.6 (Ø per core, over insulation) Dielectric barrier; rated 90 °C continuous; withstands 3.5 kV / 5 min
3 Core lay-up Four insulated cores laid up around central non-hygroscopic filler; binder tape — ≈ 57.0 (Ø over lay-up, calc.) Forms a round assembly for sheathing
4 Outer sheath (PVC) Flame-retardant PVC, ST2 type, black 2.6 ≈ 64.0 (Ø overall) Mechanical & moisture protection; flame retardance ZC (ZR) per GB/T 19666






Key Dimensions & Properties
Overall diameter ≈ 64.0 mm Mingda four-core unarmored table

Approx. cable weight ≈ 10452 kg/km Mingda 10452 (Al ≈ 4242)

Rated voltage 0.6/1 kV AC 50 Hz; max system voltage Um = 1.2 kV

Max conductor temperature 90 / 250 °C Continuous / short-circuit (≤ 5 s)

Min. bending radius (multi-core) ≥ 15 × OD — OD = actual cable diameter

Flame-retardant class ZC (ZR) — GB/T 19666

Schematic — not to exact scale. Nominal values for reference; confirm against factory test certificate.



9. Application. Heavy distribution risers, bus-droppers, large motor and transformer circuits — conduit, tray, trench, duct, trunking; indoor or sheltered outdoor.


10. Ordering. ZR-YJV 0.6/1 kV 4×240 + length/drum + marking; confirm against factory test certificate.





Company Details

Bronze Gleitlager

,

Bronze Sleeve Bushings

 and 

Graphite Plugged Bushings

 from Quality China Factory
  • Business Type:

    Manufacturer,Exporter,Trading Company

  • Year Established:

    2009

  • Total Annual:

    50000000-100000000

  • Employee Number:

    260~300

  • Ecer Certification:

    Verified Supplier

Company Profile — Anhui Tongdu Cable Co., Ltd. Company Overview Anhui Tongdu Cable Co., Ltd. (hereinafter "Tongdu Cable") is a professional wire and cable manufacturer headquartered in Zongyang Economic Development Zone, Anhui Province, China. Founded in 2009, the company has grown into one of... Company Profile — Anhui Tongdu Cable Co., Ltd. Company Overview Anhui Tongdu Cable Co., Ltd. (hereinafter "Tongdu Cable") is a professional wire and cable manufacturer headquartered in Zongyang Economic Development Zone, Anhui Province, China. Founded in 2009, the company has grown into one of...

+ Read More

Get in touch with us

  • Reach Us
  • Anhui Tongdu International Trade Co., Ltd.
  • Room 2003,B Building,Jiaqiao International Plaza,Baohe District,Hefei City,Anhui Province
  • https://www.power-cabling.com/

Leave a Message, we will call you back quickly!

Email

Check your email

Phone Number

Check your phone number

Requirement Details

Your message must be between 20-3,000 characters!

Submit Requirement