| Battery Chemistry | LFP, 3.2 V / 314 Ah cells |
| Cooling | Liquid cooling; automatic refilling |
| Operating Temperature | −35 to +55°C; derate above 45°C |
| Protocols | Modbus / IEC104 / MQTT |
| Delivery Time | Confirmed after configuration approval |
| Rated Load Power | 125 kW |
| Weight | ≤2.7 t |
| PV Input Voltage | 150–950 V |
| Battery DC Range | 728–936 V |
| Dimensions W × D × H | 1520 × 1350 × 2270 mm |
| Cycle Life | ≥8,000 to 70% SOH; conditions to confirm |
| Maximum PV Input | 250 kW DC |
| Transfer Time | 10 ms (datasheet) |
| Grid / Diesel Power | 187 kW / 187 kW |
| Protection / Corrosion | IP55 / C4H |
| Battery Configuration | 1P260S |
| Unbalanced Load | 100% supported |
| Packaging Details | Export packaging and shipping dimensions to be confirmed for the selected configuration. |
| Battery Energy | 261.2 kWh |
| Communication | LAN / RS485 |
| MPPT Channels | 10 |
| Installation | Floor-mounted |
| Brand Name | YINTU |
| Model Number | YT-Hybrid ESS-125kW/261kWh-Pro |
View Detail Information
Explore similar products
Integrated Commercial & Industrial Energy Storage IP65 Protection 250 KW Hybrid
150.5 KWh Commercial And Industrial Energy Storage Smart Temp Control Fire
52 KWh / 25 KW Hybrid ESS Energy Storage Cabinets IP54 For Commercial Industrial
Customized Industrial Commercial Energy Storage Cabinets 125 KW 261 KWh Liquid
Product Specification
| Battery Chemistry | LFP, 3.2 V / 314 Ah cells | Cooling | Liquid cooling; automatic refilling |
| Operating Temperature | −35 to +55°C; derate above 45°C | Protocols | Modbus / IEC104 / MQTT |
| Delivery Time | Confirmed after configuration approval | Rated Load Power | 125 kW |
| Weight | ≤2.7 t | PV Input Voltage | 150–950 V |
| Battery DC Range | 728–936 V | Dimensions W × D × H | 1520 × 1350 × 2270 mm |
| Cycle Life | ≥8,000 to 70% SOH; conditions to confirm | Maximum PV Input | 250 kW DC |
| Transfer Time | 10 ms (datasheet) | Grid / Diesel Power | 187 kW / 187 kW |
| Protection / Corrosion | IP55 / C4H | Battery Configuration | 1P260S |
| Unbalanced Load | 100% supported | Packaging Details | Export packaging and shipping dimensions to be confirmed for the selected configuration. |
| Battery Energy | 261.2 kWh | Communication | LAN / RS485 |
| MPPT Channels | 10 | Installation | Floor-mounted |
| Brand Name | YINTU | Model Number | YT-Hybrid ESS-125kW/261kWh-Pro |
| High Light | 10 MPPT Commercial ESS ,On Grid Commercial Battery Storage ,IP55 Rating Commercial Energy Storage Cabinets | ||
COMMERCIAL & INDUSTRIAL ENERGY STORAGE SOLUTIONS
Bring a larger solar array and commercial battery storage into one project-configured energy system. This Pro cabinet combines 261.2 kWh of LFP storage with 125 kW load power, up to 250 kW of DC photovoltaic input and separate grid/diesel power ratings of 187 kW.
The system integrates a high-voltage LFP battery, hybrid power conversion, 10 MPPT channels and intelligent liquid cooling. Its iBMS supports SOC/SOP calibration, while on-grid, off-grid and switching modes provide a basis for site-specific energy management. The source configuration is Stars CL261Pro.
YINTU is an energy storage solution provider. We work with experienced manufacturing partners to match equipment, controls and service scope to each customer’s site.
Use the 250 kW PV input capability to support facilities with extensive roof space and daytime production loads. The battery can store available solar energy for later use; the dispatch strategy must reflect the actual load curve, export rules and battery operating limits.
Coordinate charging and discharging around site demand peaks and tariff periods. YINTU helps define the target operating window and reserve level; achievable savings require the customer’s tariff and measured consumption data.
Combine solar generation, storage and a compatible diesel source for projects where grid availability is limited. Confirm generator control, minimum loading, source transfer and protection before selecting the final operating strategy.
The datasheet lists 10 ms grid/off-grid transfer and 100% unbalanced-load support. Size the protected circuits against continuous power, motor starting requirements and reserve energy; this does not imply uninterrupted operation for every load.
Multiple tracking channels provide flexibility for PV design. The datasheet specifies MC4 connections and a 150–950 V input range; array design must still satisfy all electrical and environmental limits.
Integrated thermal management supports the battery cabinet across the stated ambient range. Output derates above 45°C, so ventilation, solar exposure and local climate remain part of equipment selection.
SOC/SOP calibration supports energy and power estimation. The datasheet states at least 8,000 cycles to 70% SOH; the operating and test conditions must be confirmed for lifecycle modelling.
IP55 protection, C4H corrosion classification, active early warning and pack/cluster aerosol protection form the listed design basis. Water suppression and explosion venting are optional, subject to the selected safety design.
The source describes modular plug-and-play expansion. Confirm the permitted number of cabinets, electrical arrangement, control architecture and commissioning requirements before increasing system size.
PV feeds the integrated MPPT stage; the battery and hybrid conversion system coordinate stored energy with the site load. Grid and diesel are separate source interfaces that require approved controls and protection. The 250 kW PV, 187 kW source and 125 kW load ratings describe different interfaces and must not be treated as interchangeable output ratings.
| Parameter | Specification |
|---|---|
| Battery chemistry / cell rating | LFP / 3.2 V / 314 Ah |
| Nominal energy | 261.2 kWh |
| Battery configuration | 1P260S |
| Battery DC voltage range | 728–936 V |
| Cycle life | ≥8,000 cycles to 70% SOH; test conditions to confirm |
| Rated load power | 125 kW |
| Grid / diesel power | 187 kW / 187 kW |
| Maximum PV input | 250 kW DC |
| PV configuration | 10 MPPTs (20S); MC4 connectors; 150–950 V |
| Transfer time / unbalanced load | 10 ms / 100% |
| Operating modes | On-grid, off-grid and on/off-grid switching |
| AC voltage and frequency | Not specified in this datasheet; confirm for the destination site |
| Parameter | Specification |
|---|---|
| Protection / corrosion | IP55 complete system / C4H |
| Cooling | Intelligent liquid cooling with automatic refilling |
| Ambient temperature | −35 to +55°C; derating above 45°C |
| Altitude | ≤2,000 m; derating above 2,000 m |
| Relative humidity | 0–95%, non-condensing |
| Noise | ≤75 dB; measurement distance not specified |
| Dimensions (W × D × H) | 1520 × 1350 × 2270 mm |
| Weight / installation | ≤2.7 t / floor-mounted |
| Parameter | Specification |
|---|---|
| Battery management | iBMS with SOC/SOP calibration |
| Communication interfaces | LAN / RS485 |
| Protocols | Modbus / IEC104 / MQTT |
| Fire protection | Pack-level and cluster-level aerosol; active early warning |
| Optional safety features | Water suppression and explosion venting |
| Datasheet standard references | IEC/EN 62619; IEC 62477; IEC 60529; IEC 61000-6-2; IEC 61000-6-4; UN 38.3 |
Identify the priority: peak management, solar self-consumption, backup, EV charging or microgrid operation. Use actual load and generation profiles to set power, energy and reserve requirements.
YINTU coordinates model selection and technical clarification with the manufacturing partner, including destination voltage, frequency, environmental conditions, monitoring and optional functions.
Confirm the final configuration, interconnection requirements, protection design, installation responsibilities, commissioning plan, documentation and after-sales scope in the project proposal. Prices and delivery schedules depend on the approved configuration.
No. The datasheet rates load power at 125 kW. The 250 kW figure describes DC photovoltaic input; the grid and diesel interfaces are each listed at 187 kW.
Calculate duration from the selected loads, usable state-of-charge window, conversion losses and reserve policy. The nominal 261.2 kWh value alone cannot establish a guaranteed backup time.
A diesel interface is listed. YINTU will coordinate a compatibility review covering voltage, frequency, controls and protection before including an existing generator in the solution.
No. Pack/cluster aerosol and early warning are listed in the source; water suppression and explosion venting are optional. Confirm the final scope and local requirements in the technical agreement.
Send YINTU your site location, utility voltage and frequency, interval load profile, solar capacity, generator details, tariff structure and backup priorities. We will coordinate a configuration proposal with our manufacturing partners.
Specifications are transcribed from the supplied product datasheet and remain subject to the approved technical agreement. Nominal energy does not guarantee usable energy or backup duration. Cycle life and efficiency depend on test conditions and operation. Listed standards are datasheet references, not a blanket certification claim; request model-specific supporting documents.
Company Details
Business Type:
Distributor/Wholesaler,Exporter,Trading Company
Year Established:
2016
Total Annual:
$ 10 million-$ 20,million
Employee Number:
50~100
Ecer Certification:
Verified Supplier
Your Partner for Energy Storage Product Sourcing YINTU Energy is the energy storage business of Hunan Yintu New Materials Co., Ltd. Established in 2016, our company has 10-50 employees and an export share of 100%. We connect overseas distributors, installers, EPC companies and project buyers with... Your Partner for Energy Storage Product Sourcing YINTU Energy is the energy storage business of Hunan Yintu New Materials Co., Ltd. Established in 2016, our company has 10-50 employees and an export share of 100%. We connect overseas distributors, installers, EPC companies and project buyers with...
Get in touch with us
Leave a Message, we will call you back quickly!