China factories

Chat Now Send Email
China factory - Hunan Yintu New Materials Co., Ltd.

Hunan Yintu New Materials Co., Ltd.

  • China,Changsha ,Hunan
  • Verified Supplier
  1. Home
  2. Products
  3. About Us
  4. Contact Us

Leave a Message

we will call you back quickly!

Submit Requirement
China Custom Commercial And Industrial Energy Storage Systems Liquid Cooled 125 KW 261
China Custom Commercial And Industrial Energy Storage Systems Liquid Cooled 125 KW 261

  1. China Custom Commercial And Industrial Energy Storage Systems Liquid Cooled 125 KW 261
  2. China Custom Commercial And Industrial Energy Storage Systems Liquid Cooled 125 KW 261
  3. China Custom Commercial And Industrial Energy Storage Systems Liquid Cooled 125 KW 261

Custom Commercial And Industrial Energy Storage Systems Liquid Cooled 125 KW 261

  1. MOQ: 1 unit
  2. Price: Quotation on request
  3. Get Latest Price
Rated AC Voltage 400 V
Battery Pack Protection IP67
Communication Ethernet / RS485
Solution Provider YINTU
Payment Terms T/T
Rated Battery Energy 261.248 kWh
Integrated Systems Battery / PCS / BMS / EMS
Nominal DC Voltage 832 V
Frequency 50 / 60 Hz
Protocols Modbus TCP / Modbus RTU
Dimensions W × D × H 1000 × 1300 × 2300 mm
Supply Ability 5 units
Battery Chemistry LFP
Cooling Liquid cooling
DC Voltage Range 728–936 V
Operating Temperature −15°C to +45°C
Rated AC Current 180 A
System Protection IP55
Rated AC Power 125 kW
Application C&I demand management and solar storage
Delivery Time Confirmed in the project quotation
Cell Capacity 314 Ah
Equipment Series YOTAI Ener Hexon Smart261L
Model Number Ener Hexon Smart261L
Place of Origin China
Brand Name YOTAI

View Detail Information

Inquiry by Email Get Latest Price
Chat online Now Ask for best deal
  1. Product Details
  2. Company Details

Product Specification

Rated AC Voltage 400 V Battery Pack Protection IP67
Communication Ethernet / RS485 Solution Provider YINTU
Payment Terms T/T Rated Battery Energy 261.248 kWh
Integrated Systems Battery / PCS / BMS / EMS Nominal DC Voltage 832 V
Frequency 50 / 60 Hz Protocols Modbus TCP / Modbus RTU
Dimensions W × D × H 1000 × 1300 × 2300 mm Supply Ability 5 units
Battery Chemistry LFP Cooling Liquid cooling
DC Voltage Range 728–936 V Operating Temperature −15°C to +45°C
Rated AC Current 180 A System Protection IP55
Rated AC Power 125 kW Application C&I demand management and solar storage
Delivery Time Confirmed in the project quotation Cell Capacity 314 Ah
Equipment Series YOTAI Ener Hexon Smart261L Model Number Ener Hexon Smart261L
Place of Origin China Brand Name YOTAI
High Light 261 kWh Liquid Cooled Commercial ESS ,125 kW Commercial Battery Storage ,Custom Commercial And Industrial Energy Storage

COMMERCIAL & INDUSTRIAL ENERGY STORAGE SOLUTIONS

125 kW / 261 kWh Liquid-Cooled C&I Energy Storage Cabinet

Smart261L combines a 125 kW power conversion system with 261.248 kWh of rated battery energy in one outdoor liquid-cooled cabinet. It is a compact equipment option for commercial and industrial sites that need to shift energy use, manage grid demand and coordinate on-site solar generation.

Equipment Overview

The manufacturer describes five liquid-cooled battery packs, a sub-controller, PCS, BMS, EMS, liquid-cooling equipment and electrical auxiliaries in an integrated cabinet. LFP cells are rated at 3.2 V / 314 Ah. The cabinet measures 1000 × 1300 × 2300 mm (W × D × H), with a 1.3 m² equipment footprint before maintenance and fire-safety clearances.

YINTU is an energy storage solution provider. We match project requirements with products from capable manufacturing partners, including YOTAI, and coordinate equipment selection, technical clarification and supply. The equipment described here is YOTAI's Ener Hexon series; YINTU's project scope is agreed in the quotation.

Ener Hexon Smart261L application concept
Illustrative application concept. Equipment and site layout depend on the project.

Commercial & Industrial Application Scenarios

Factories and industrial parks

Discharge during selected high-demand periods to reduce the site's grid draw, then recharge when generation or the tariff schedule makes it appropriate. Review interval demand, transformer loading, production shifts and the required SOC reserve together; savings depend on the actual tariff and operating profile.

Commercial rooftop solar

Use an AC-coupled design to store surplus production from a compatible external PV inverter and supply later operating hours. This can improve on-site solar use where daytime production and consumption do not align. Export limits, metering and EMS control must be defined for the site.

Solar-storage EV charging hubs

Coordinate the cabinet with charger demand and on-site PV to buffer selected charging peaks. Charging power, simultaneous sessions and battery recharge opportunities determine the useful storage contribution. Grid connection limits remain part of the engineering design.

Critical circuits at business facilities

The datasheet includes off-grid operation and black-start features. A project can evaluate designated essential circuits at logistics facilities, airports or industrial premises. Load starting current, isolation, switching time and protection coordination must be checked; this listing does not promise uninterrupted UPS performance.

Managed multi-cabinet installations

The manufacturer describes expansion from 125 kW to 1.25 MW. YINTU can coordinate the cabinet count, site EMS and distribution design for a staged project. Demand-response or VPP participation depends on the local programme, approved controls and grid requirements.

System Features and Project Value

Liquid thermal management

Liquid cooling is integrated, with a manufacturer-stated battery-pack temperature difference below 2.5°C. Assess performance under the agreed ambient and operating duty; no cycle-life increase is guaranteed by this listing.

Protection and monitoring

The manufacturer describes thermal-runaway early warning, combustible-gas detection, pressure relief and targeted fire suppression. These functions complement the site's fire strategy and maintenance plan.

Outdoor enclosure

IP55 system protection and IP67 battery-pack protection are stated. C3 corrosion protection is standard, with C4/C5 options to be confirmed for the project.

Local and remote operation

Ethernet and RS485 interfaces support Modbus TCP and Modbus RTU. Define dispatch commands, data access, alarms and the integration boundary with the site controller.

How the System Fits Your Site

In the illustrated AC-coupled arrangement, solar PV connects through an external PV inverter to the site AC bus. Smart261L exchanges energy with that bus through its integrated PCS. The datasheet does not specify a direct PV DC input. Off-grid operation requires an engineered isolation and switching arrangement; grid approval and export settings are project-specific.

Ener Hexon Smart261L conceptual system topology
Concept diagram only. Follow the approved single-line diagram and installation documents.

Technical Specifications

Battery / DC

Parameter Specification
Cell type LFP, 3.2 V / 314 Ah
Rated battery energy 261.248 kWh
Nominal DC voltage 832 V
DC voltage range 728–936 V
Charge/discharge rate ≤0.5 CP, as stated in the datasheet

AC performance

Parameter Specification
Grid-connected rated power 125 kW
Grid voltage 400 V, −20% to +10%
Rated AC current 180 A
Rated frequency 50 / 60 Hz
Frequency range 45–55 / 55–65 Hz
Grid-connected current distortion THDi <3% at rated power
Power factor >0.99 at rated power; adjustable −1 (leading) to 1 (lagging)
Off-grid voltage / frequency 400 V ±5%; 50 / 60 Hz
Off-grid voltage distortion <3% with linear load

Cabinet and site conditions

Parameter Specification
Cooling Liquid cooling
Dimensions (W × D × H) 1000 × 1300 × 2300 mm
Weight 2300 kg; datasheet states +5% allowance
Ingress protection System IP55; battery pack IP67
Corrosion protection C3; C4/C5 optional
Operating temperature −15°C to +45°C
Storage temperature −20°C to +45°C; SOC 30–50%; less than 6 months
Relative humidity 0–95% RH, non-condensing
Installation Outdoor
Altitude <2000 m stated; higher-altitude operation requires supplier confirmation
Daily operation Maximum two charges and two discharges per day, per datasheet
Fire extinguishing agent Perfluoro(2-methyl-3-pentanone)

Control and documentation

Parameter Specification
Communication Ethernet / RS485
Protocols Modbus TCP / Modbus RTU
Datasheet-listed standards GB/T 36276; GB/T 34131
Compliance scope Request the exact model's reports and destination-specific grid / installation approvals

From Site Requirements to a Storage Solution

1. Define the operating objective

Identify whether the priority is peak management, solar self-consumption, backup or microgrid operation. Use the actual load profile and generation resources to set the power, energy and operating reserve.

2. Match equipment and interfaces

YINTU coordinates equipment selection and technical clarification with the manufacturing partner, including voltage, controls, environment, expansion and optional functions.

3. Confirm delivery and service scope

Agree the final equipment list, metering, protection, switchgear, transformer (if required), cables, foundations, installation, commissioning and service responsibilities before ordering. PV modules, generators, wind turbines, EV chargers and site works are included only when listed in the quotation. Warranty, lead time, MOQ and price are confirmed for the selected configuration.

Frequently Asked Questions

Can solar panels connect directly to the cabinet?

This datasheet specifies an AC-connected PCS and does not give PV MPPT input ratings. Use an external PV inverter in an AC-coupled design unless a separately documented PV interface is offered.

How long can it supply a 125 kW load?

261.248 kWh divided by 125 kW is about 2.09 hours as a nominal energy-to-power ratio. Usable AC runtime will be lower and depends on SOC limits, losses, auxiliaries and site conditions; size backup from a complete load assessment.

Is the cabinet a complete turnkey power station?

The cabinet integrates major storage subsystems. Grid connection works, site switchgear, protection settings, civil works and installation still require a project-specific scope.

Can YINTU adapt the solution to our site?

YINTU coordinates capacity and power selection, equipment interfaces and manufacturer clarification against the project requirements. Final engineering, supply and service responsibilities are recorded in the agreed scope.

Discuss Your C&I Energy Storage Project

Send the project country, AC voltage and frequency, interval load data, tariff schedule, existing PV and generator details, required backup loads and duration, site plan, ambient conditions and target delivery date. YINTU will coordinate a suitable configuration, equipment interfaces, documentation and quotation with the manufacturing partner.

Figures are taken from the supplied manufacturer datasheet and are subject to the final order specification. Rated battery energy is not guaranteed usable AC energy. Runtime depends on the usable SOC window, load, temperature, conversion losses and auxiliary consumption. Application images are illustrative concepts, not photographs of completed YINTU projects. Topology drawings show operating concepts and are not installation wiring diagrams.

Company Details

Bronze Gleitlager

,

Bronze Sleeve Bushings

 and 

Graphite Plugged Bushings

 from Quality China Factory
  • Business Type:

    Distributor/Wholesaler,Exporter,Trading Company

  • Year Established:

    2016

  • Total Annual:

    $ 10 million-$ 20,million

  • Employee Number:

    50~100

  • Ecer Certification:

    Verified Supplier

Your Partner for Energy Storage Product Sourcing YINTU Energy is the energy storage business of Hunan Yintu New Materials Co., Ltd. Established in 2016, our company has 10-50 employees and an export share of 100%. We connect overseas distributors, installers, EPC companies and project buyers with... Your Partner for Energy Storage Product Sourcing YINTU Energy is the energy storage business of Hunan Yintu New Materials Co., Ltd. Established in 2016, our company has 10-50 employees and an export share of 100%. We connect overseas distributors, installers, EPC companies and project buyers with...

+ Read More

Get in touch with us

  • Reach Us
  • Hunan Yintu New Materials Co., Ltd.
  • 201, Building B6, Xinggongchang Industrial Park, No.1 Lantian North Road, Economic Development Zone, Changsha, Hunan, China
  • https://www.yintuenergy.com/

Leave a Message, we will call you back quickly!

Email

Check your email

Phone Number

Check your phone number

Requirement Details

Your message must be between 20-3,000 characters!

Submit Requirement