| PE conductor (×1) | Bare annealed copper, Class 2 stranded, 7×∅2.14 mm, conductor Ø ≈ 6.42–6.85 mm depending on compaction |
| Sheath thickness | 1.7 mm (GB/T 12706 multi-core 35–70 mm² range) |
| Insulation (×5) | XLPE, colours: brown/black/grey (L1/L2/L3), blue (N), yellow/green striped (PE) |
| Packaging Details | General Packaging or As Requirements |
| Number of cores | 5 (4+1) |
| PE conductor diameter (approx.) | 6.42–6.85 mm |
| Outer sheath | Flame-retardant PVC (ZR grade) |
| Diameter over PE insulated core | 8.22–8.65 mm |
| Supply Ability | 10000 meters per month |
| PE conductor construction | Class 2, 7×∅2.14 mm,IEC 60228 / GB/T 3956 |
| PE insulation thickness | 0.9 mm (25 mm² class) |
| Filler / binder | FR PP filler + FR tape |
| Design outer diameter | ≈ 26.5 mm |
| Phase/Neutral conductor nominal area | 50 mm² |
| Phase/Neutral conductor (×4) | Bare annealed copper, Class 2 stranded, 19×∅1.78 mm, conductor Ø ≈ 9.0–9.6 mm depending on compaction |
| Overall cable diameter | 24.5 – 29.5 mm |
| PE conductor nominal area | 25 mm² |
| Approx. weight | 1100 – 1350 kg/km |
| Payment Terms | L/C,T/T |
| Phase/Neutral conductor construction | Class 2, 19×∅1.78 mm,IEC 60228 / GB/T 3956 |
| Diameter over phase/neutral insulated core | 11.2–11.8 mm |
| Delivery Time | Less than 15 days |
| Phase/Neutral conductor diameter (approx.) | 9.0–9.6 mm |
| Phase/Neutral insulation thickness | 1.1 mm (50 mm² class) |
| Design weight | ≈ 1210 kg/km |
| Cable shape | Round |
| Model Number | ZR-YJV 4x50mm²+1x25mm² |
| Certification | CE/ISO/CCC |
| Brand Name | TONGDU |
| Place of Origin | China |
View Detail Information
Explore similar products
High Capacity 5 Core Flex ZR-YJV 4x300mm2+1x150mm2 XLPE Copper Flame Retardant
ZC-YJV22 5 Cores Cable 3x185mm2+2x95mm2 Armoured XLPE Flame Retardant Cable 0.6
0.6/1kV ZC-YJV 5x16mm² Copper XLPE PVC Flame-Retardant Power Cable for
WDZBN-YJY 5 Core 3x50mm²+2x25mm² Low Smoke Halogen Free Fire Resistant XLPE
Product Specification
| PE conductor (×1) | Bare annealed copper, Class 2 stranded, 7×∅2.14 mm, conductor Ø ≈ 6.42–6.85 mm depending on compaction | Sheath thickness | 1.7 mm (GB/T 12706 multi-core 35–70 mm² range) |
| Insulation (×5) | XLPE, colours: brown/black/grey (L1/L2/L3), blue (N), yellow/green striped (PE) | Packaging Details | General Packaging or As Requirements |
| Number of cores | 5 (4+1) | PE conductor diameter (approx.) | 6.42–6.85 mm |
| Outer sheath | Flame-retardant PVC (ZR grade) | Diameter over PE insulated core | 8.22–8.65 mm |
| Supply Ability | 10000 meters per month | PE conductor construction | Class 2, 7×∅2.14 mm,IEC 60228 / GB/T 3956 |
| PE insulation thickness | 0.9 mm (25 mm² class) | Filler / binder | FR PP filler + FR tape |
| Design outer diameter | ≈ 26.5 mm | Phase/Neutral conductor nominal area | 50 mm² |
| Phase/Neutral conductor (×4) | Bare annealed copper, Class 2 stranded, 19×∅1.78 mm, conductor Ø ≈ 9.0–9.6 mm depending on compaction | Overall cable diameter | 24.5 – 29.5 mm |
| PE conductor nominal area | 25 mm² | Approx. weight | 1100 – 1350 kg/km |
| Payment Terms | L/C,T/T | Phase/Neutral conductor construction | Class 2, 19×∅1.78 mm,IEC 60228 / GB/T 3956 |
| Diameter over phase/neutral insulated core | 11.2–11.8 mm | Delivery Time | Less than 15 days |
| Phase/Neutral conductor diameter (approx.) | 9.0–9.6 mm | Phase/Neutral insulation thickness | 1.1 mm (50 mm² class) |
| Design weight | ≈ 1210 kg/km | Cable shape | Round |
| Model Number | ZR-YJV 4x50mm²+1x25mm² | Certification | CE/ISO/CCC |
| Brand Name | TONGDU | Place of Origin | China |
| High Light | Copper Core 5 core shielded cable ,5 core shielded cable 1100kg/km ,1350kg/km 50mm 5 core swa | ||
Copper Core 4+1 Cable ZR-YJV 4x50mm²+1x25mm² XLPE Flame Retardant 0.6/1kV
Cable Designation & Meaning
|
Code |
Meaning |
|---|---|
|
ZR |
Legacy prefix for flame retardant; under GB/T 19666-2019 it defaults to Class C (modern equivalent: ZC). |
|
YJ |
XLPE (cross-linked polyethylene) insulation |
|
V |
PVC outer sheath — flame-retardant grade, contains halogen (Cl) |
|
0.6/1 kV |
Rated voltage U₀/U = 600/1000 V; Uₘ = 1.2 kV |
|
4×50+1×25 mm² |
Four equal phase/neutral cores of 50 mm² copper + one reduced protective earth (PE) core of 25 mm² copper |
![]()
1. Product Overview & Rating Summary. ZR-YJV 4×50+1×25 sits at the top of the standard 4+1-core flame-retardant range before stepping into the 70 mm² and larger sizes: four 50 mm² annealed copper phase conductors are cabled around a central 25 mm² copper neutral/PE core, each insulated in XLPE and enclosed in a single ST2 PVC oversheath rated for 0.6/1 kV at 50 Hz. Manufacture and type testing are performed to GB/T 12706.1 / IEC 60502-1, stranding complies with GB/T 3956, and the ZR marking denotes class ZC flame retardance under GB/T 19666. The finished outer diameter is roughly 33 mm and the nominal mass is about 2450 kg per kilometre in copper (1150 kg/km for the aluminium YJLV equivalent), delivered in 100 m coils or wooden drums with ≥ Ø 1200 mm flanges — approximately 245 kg per 100 m.
2. Layer-by-Layer Construction (Conductor to Jacket).
| Layer | Construction | Wall | Diameter |
|---|---|---|---|
| Phase conductor (×4) | Annealed Cu, Class 2 stranded, 19 × 1.78 mm (1+6+12) each | — | ≈ 9.0 mm |
| Neutral conductor (×1) | Annealed Cu, Class 2 compact, 7 × 2.14 mm (1+6) | — | ≈ 6.7 mm |
| Phase insulation (×4) | XLPE | 1.4 mm | ≈ 11.8 mm |
| Neutral insulation (×1) | XLPE | 1.2 mm | ≈ 9.1 mm |
| Core assembly | Central neutral + 4 phase cores cabled around + PP filler + polyester binder | — | ≈ 29.4 mm (derived) |
| Outer jacket | Flame-retarded PVC, ST2 compound, black | 1.8 mm | ≈ 33.0 mm (finished) |
3. Electrical Characteristics. Each 50 mm² phase conductor is limited to 0.387 Ω/km at 20 °C, climbing to around 0.49 Ω/km at the 90 °C operating point; the 25 mm² neutral/PE is capped at 0.741 Ω/km. Every production length survives the routine 3.5 kV AC power-frequency proof held for five minutes. Finished-cable insulation resistance remains above 36.7 MΩ·km, XLPE volume resistivity exceeds 1×10¹² Ω·cm, and typical values include capacitance ≤ 0.38 μF/km, inductance ≈ 0.26 mH/km and 50 Hz AC impedance ≈ 0.40 Ω/km. On a one-second short circuit each 50 mm² phase withstands about 5.75 kA (the 25 mm² neutral on a 2.88 kA basis), using I = k·A/√t with k = 115 for copper/XLPE. With all four phase cores energised, reference loading is 175 A in free air at 25 °C and 145 A directly buried at 25 °C — engineering estimates to be confirmed against the factory test certificate.
Electrical Parameters
|
Parameter |
Value |
Note |
|---|---|---|
|
Rated voltage U₀/U |
0.6 / 1 kV |
Uₘ = 1.2 kV |
|
Test voltage AC (5 min) |
3.5 kV |
Routine |
|
Type-test voltage |
4.0 kV |
IEC 60502-1 |
|
DC resistance @20 °C (phase/neutral, per core) |
≤ 0.387 Ω/km |
GB/T 3956 max, 50 mm² |
|
DC resistance @20 °C (PE, per core) |
≤ 0.727 Ω/km |
GB/T 3956 max, 25 mm² |
|
AC resistance @90 °C (est., phase/neutral) |
≈ 0.503 Ω/km |
per core |
|
AC resistance @90 °C (est., PE) |
≈ 0.945 Ω/km |
per core |
|
Current rating in air (30 °C, single circuit, 4-core+1) |
≈ 145–165 A |
based on 50 mm² phase |
|
Current rating in air (design) |
≈ 155 A |
apply grouping + ambient correction |
|
Direct buried (20–25 °C, soil 1.0–1.2 K·m/W, 0.7 m) |
≈ 170–190 A |
common catalogue 175–183 A |
|
Design buried rating |
≈ 179 A |
soil thermal resistivity correction required |
|
Short-circuit current (1 s, Cu, 250 °C, phase/neutral) |
≈ 5.0 kA |
50 mm² reference |
|
Short-circuit current (1 s, Cu, 250 °C, PE) |
≈ 2.5 kA |
25 mm² reference |
|
Frequency |
50/60 Hz AC |
— |
Cable Parameters
![]()
Cable Test Parameters
![]()
Cable Structure Parameters
![]()
| Layered 4+1 conductor build-up from copper strand to PVC jacket · nominal dimensions per GB/T 12706.1 / IEC 60502-1 · finished Ø ≈ 33 mm per cross-referenced industry sample | |||||
| No. | Layer | Material / Construction | Nominal Thickness (mm) | Diameter (mm) | Function / Remarks |
| 1 | Phase conductor (Cu) × 4 | Annealed copper, Class 2 stranded — 19 wires of 1.78 mm per core (1+6+12 layout), nominal area 50 mm² each | — | ≈ 9.0 (Ø each phase core) | Line-current carrying phase conductors; DC resistance capped at 0.387 Ω/km at 20 °C |
| 2 | Neutral conductor (Cu) × 1 | Annealed copper, Class 2 compact strand — 7 wires of 2.14 mm (7/2.14, 1+6 layout), nominal area 25 mm² | — | ≈ 6.7 (Ø neutral core) | Return / PE path; DC resistance capped at 0.741 Ω/km at 20 °C |
| 3 | Phase insulation (XLPE) × 4 | Cross-linked polyethylene dielectric | 1.4 | ≈ 11.8 (Ø each phase core, incl. insulation) | Electrical isolation; 90 °C continuous rating; withstands 3.5 kV for 5 min |
| 4 | Neutral insulation (XLPE) × 1 | Cross-linked polyethylene dielectric | 1.2 | ≈ 9.1 (Ø neutral core, incl. insulation) | Electrical isolation for the neutral/PE conductor |
| 5 | Core assembly | Neutral core at centre + four phase cores cabled around + PP filler + polyester binder tape | — | ≈ 29.4 (Ø over assembled cores) | 4+1 configuration; derived from finished Ø 33 − 2×1.8 sheath |
| 6 | Outer jacket (PVC) | Flame-retardant PVC, ST2 compound, black | 1.8 | ≈ 33.0 (Ø finished cable) | Mechanical and moisture protection; ZC flame retardance per GB/T 19666 |
| Key Dimensions & Properties (expanded) | |||||
| Finished cable diameter | ≈ 33.0 | mm | Cross-referenced industry 4+1 sample | ||
| Approximate cable mass | ≈ 2450 | kg/km | Cu build-up (cross-referenced industry data) | ||
| Approximate mass, aluminium build | ≈ 1150 | kg/km | YJLV equivalent (est.) | ||
| Nominal voltage rating | 0.6/1 | kV | AC 50 Hz; maximum system voltage Um = 1.2 kV | ||
| Conductor temperature limits | 90 / 250 | °C | Continuous service / short-circuit (≤ 5 s) | ||
| Minimum bend radius (multi-core) | ≥ 15 × OD ≈ 495 | mm | OD = actual finished cable diameter | ||
| Flame-retardant classification | ZC (ZR) | — | Per GB/T 19666 | ||
| Short-circuit current, phase (1 s) | ≈ 5.75 | kA | I = k·A/√t, k=115 for Cu/XLPE | ||
| Short-circuit current, neutral (1 s) | ≈ 2.88 | kA | 25 mm² neutral, same k factor | ||
| AC impedance @ 50 Hz | ≈ 0.40 | Ω/km | √(R² + X²); R-dominant (est.) | ||
| Capacitance (typical) | ≤ 0.38 | μF/km | Per phase core (est.) | ||
| Inductance (typical) | ≈ 0.26 | mH/km | Multi-core cable (est.) | ||
| Air ampacity @ 25 °C | ≈ 175 | A | 4 phase cores loaded, Cu (est.) | ||
| Buried ampacity @ 25 °C | ≈ 145 | A | 4 phase cores loaded, Cu (est.) | ||
| Maximum pulling tension | ≤ 8000 | N | 40 N/mm² of main phase core area (est.) | ||
| Schematic — not to exact scale. Finished Ø ≈ 33 mm and weight ≈ 2450 kg/km from cross-referenced industry samples; conductor/insulation diameters calculated from GB/T 3956 and GB/T 12706.1; ampacity 175/145 A is an engineering estimate for 4+1 cables. Values marked (est.) require confirmation against the factory test certificate. | |||||
![]()
4. Thermal Response & Flame Performance. XLPE sustains a 90 °C continuous conductor temperature and tolerates a 250 °C short-circuit peak for up to five seconds. The cable is rated for service ambients between −20 and +45 °C, must not be uncoiled below 0 °C without pre-conditioning, and uses 25 °C as the reference soil temperature for buried ratings. Flame behaviour meets class ZC of GB/T 19666, proven by both the single-cable vertical test (GB/T 18380.12) and the category-C bunched test (GB/T 18380.35) with char height limited to 2.5 m. The PVC jacket is halogenated and will emit smoke and acid gas in a fire; low-smoke zero-halogen projects must specify WDZ-YJY instead.
5. Installation Practice & Handling. Bends must not fall below 15 times the actual outer diameter — about 495 mm for this size. Before first energisation, apply the DC site withstand at 4U0 = 2.4 kV for 15 minutes in line with Q/GDW 13244.1-2018. Drums held below 0 °C in storage must be warmed indoors before uncoiling; pulling tension should stay within 8000 N, and for longer runs a powered winch with a proper pulling grip is advisable. The 175 A (air) and 145 A (buried) references require derating whenever ambient temperature, cable grouping or soil thermal resistivity deviates from reference conditions. Crimp lugs, glands and heat-shrink termination kits must be matched to the 9.0 mm phase core, 6.7 mm neutral core and ≈ 33 mm jacket, and both phase and neutral short-circuit withstand should be coordinated with upstream protective device settings.
6. Typical Service Applications. This cross-section serves heavy main and sub-main distribution circuits: main distribution risers in high-rise commercial buildings, transformer secondary feeders up to about 250 kVA, motor connections in the 22–45 kW range, machine-tool and process-line power leads, factory workshop and warehouse distribution panels, elevator and escalator supply circuits, and auxiliary power in light-industrial installations. Approved installation methods include steel or PVC conduit, cable trunking, tray and indoor ducting, both indoors and in covered outdoor locations. For direct burial or mechanically exposed routing, the steel-tape armoured ZR-YJV22 variant is recommended.
![]()
7. Testing & Quality Assurance Regime. Routine tests on every length include phase and neutral DC resistance verification (≤ 0.387 / 0.741 Ω/km at 20 °C), the 3.5 kV AC / 5 min withstand, conductor continuity across all five cores and dimensional inspection covering phase insulation ≥ 1.4 mm, neutral insulation ≥ 1.2 mm, sheath ≥ 1.8 mm and overall diameter ≈ 33 mm. Sample and type tests comprise the XLPE hot-set trial at 200 ± 3 °C for 15 minutes under 0.2 MPa (load elongation ≤ 175 %, permanent set ≤ 15 %), XLPE tensile ≥ 12.5 MPa with elongation ≥ 200 %, PVC sheath tensile ≥ 10 MPa with elongation ≥ 125 %, PVC thermal stability ≥ 200 minutes at 200 °C, single-cable and category-C bunched flame trials, and bending assessment. Commissioning on site requires insulation-resistance measurement, the DC 2.4 kV / 15 min withstand and positive L1/L2/L3/N/PE identification before switching. A factory test certificate accompanies each drum.
Cable Insution Parameters
![]()
Cable Flame Retardant Parameters
![]()
8. Standards & Conformity. Design and production are governed by GB/T 12706.1 and IEC 60502-1 for 0.6/1 kV extruded-insulation power cables. Conductors satisfy GB/T 3956 / IEC 60228 Class 2 — the 50 mm² phase as nineteen wires of 1.78 mm with R ≤ 0.387 Ω/km, and the 25 mm² neutral as seven wires of 2.14 mm with R ≤ 0.741 Ω/km. Flame retardance is classified under GB/T 19666 (ZC as the default for the ZR marking) and proven by GB/T 18380.12 and GB/T 18380.35 category C. Installation acceptance follows Q/GDW 13244.1-2018 and GB 50168, while surface marking complies with GB/T 6995. Cables can also be supplied to IEC, BS, DIN, ICEA or JIS requirements on request. Because the ST2 PVC jacket contains halogen, tunnels, metro systems, hospitals and other confined public areas call for WDZ-YJY.
9. Packaging, Storage & Logistics. Standard delivery is 100 m per coil or wooden drum, with bespoke cut lengths available on request. Each drum carries type, voltage, supplier identity, production year and sequential metre marking per GB/T 6995. Storage should be in dry, covered premises at −20 to +45 °C, shielded from direct sunlight, moisture, oils and sharp objects; coils and drums remain sealed until installation and are stored upright on their flanges rather than flat. In cold conditions, condition drums indoors to ≥ 0 °C before pulling. During transit, coils and drums must be secured against rolling and impact, and the cable must never be dragged across abrasive ground or sharp edges.
![]()
10. Procurement Specification. State "ZR-YJV 0.6/1 kV 4×50+1×25" together with the required length or drum arrangement and marking preferences. Specify the flame-retardant class (ZC is standard; ZA or ZB available), jacket colour and any special drum requirements. Always request the factory test certificate to confirm the actual unarmoured diameter (≈ 33 mm), weight (≈ 2450 kg/km) and ampacity for the production batch. Where low-smoke zero-halogen or armoured construction is needed, order WDZ-YJY or ZR-YJV22 respectively.
11. Cable Industry FAQ.
Company Details
Business Type:
Manufacturer,Exporter,Trading Company
Year Established:
2009
Total Annual:
50000000-100000000
Employee Number:
260~300
Ecer Certification:
Verified Supplier
Company Profile — Anhui Tongdu Cable Co., Ltd. Company Overview Anhui Tongdu Cable Co., Ltd. (hereinafter "Tongdu Cable") is a professional wire and cable manufacturer headquartered in Zongyang Economic Development Zone, Anhui Province, China. Founded in 2009, the company has grown into one of... Company Profile — Anhui Tongdu Cable Co., Ltd. Company Overview Anhui Tongdu Cable Co., Ltd. (hereinafter "Tongdu Cable") is a professional wire and cable manufacturer headquartered in Zongyang Economic Development Zone, Anhui Province, China. Founded in 2009, the company has grown into one of...
Get in touch with us
Leave a Message, we will call you back quickly!