Shaanxi Qindiyuan Environmental Protection Equipment Co., Ltd.
| Payment Terms | T/T |
| Supply Ability | 99pcs 4-6 weeks |
| Delivery Time | 5-7 work days |
| Mountingtype | DIN Rail or Panel Mount |
| Dimensions | 100mm x 22.5mm x 110mm |
| Outputcurrent | Max 100mA |
| Enclosurematerial | Aluminum or Stainless Steel |
| Powerrating | 1W to 5W |
| Operatingtemperaturerange | -40°C to +70°C |
| Outputvoltage | 24V DC |
| Inputvoltage | 24V DC |
| Safetyapprovals | Ex ia IIC, Ex ib IIC |
| Ingressprotection | IP20 to IP65 |
| Inputcurrent | Max 100mA |
| Isolationvoltage | 2500V AC |
| Productname | Intrinsic Safety Barriers |
| Responsetime | Less than 1ms |
| Brand Name | PR |
| Model Number | PR 9203B |
| Certification | CO |
| Place of Origin | Denmark |
View Detail Information
Explore similar products
DIN Rail Mount HART Transparent Repeater PR 9106B 24 VDC Supply With Splitter
PR 9107B HART Transparent Driver 24 VDC Supply Fast Response Time For Pressure
Temperature / MA Converter PR 9113B With RTD TC Input Active Passive MA Output
DIN Rail Mount Intrinsic Safety Barrier PR 9116B Universal Converter With
Product Specification
| Payment Terms | T/T | Supply Ability | 99pcs 4-6 weeks |
| Delivery Time | 5-7 work days | Mountingtype | DIN Rail or Panel Mount |
| Dimensions | 100mm x 22.5mm x 110mm | Outputcurrent | Max 100mA |
| Enclosurematerial | Aluminum or Stainless Steel | Powerrating | 1W to 5W |
| Operatingtemperaturerange | -40°C to +70°C | Outputvoltage | 24V DC |
| Inputvoltage | 24V DC | Safetyapprovals | Ex ia IIC, Ex ib IIC |
| Ingressprotection | IP20 to IP65 | Inputcurrent | Max 100mA |
| Isolationvoltage | 2500V AC | Productname | Intrinsic Safety Barriers |
| Responsetime | Less than 1ms | Brand Name | PR |
| Model Number | PR 9203B | Certification | CO |
| Place of Origin | Denmark | ||
| High Light | Alarm Universal Ex Driver ,Solenoid Universal Ex Driver | ||
Universal Ex driver for solenoids, acoustic alarms and LEDs with extended self-diagnostics. Available in 1 or 2 channel configurations. Can be supplied separately or installed on power rail PR 94.
| Operating temperature | -20°C to +60°C |
| Storage temperature | -20°C to +85°C |
| Calibration temperature | 20...28°C |
| Relative humidity | < 95% RH (non-condensing) |
| Protection degree | IP20 |
| Installation in | Pollution degree 2 & measurement / overvoltage category II |
| Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
| Dimensions (HxWxD) with PR 4500 | 109 x 23.5 x 131 mm |
| Weight approx. | 170 g |
| DIN rail type | DIN EN 60715/35 mm |
| Wire size | 0.13...2.08 mm² AWG 26...14 stranded wire |
| Screw terminal torque | 0.5 Nm |
| Vibration | IEC 60068-2-6 2...13.2 Hz: ±1 mm 13.2...100 Hz: ±0.7 g |
| Supply voltage | 19.2...31.2 VDC |
| Fuse | 1.25 A SB / 250 VAC |
| Max. required power | ≤ 1.9 W / ≤ 3.1 W (1 / 2 ch.) - low current ≤ 2.5 W (1 ch.) - high current |
| Max. power dissipation, 1 / 2 ch. | ≤ 1.1 W / ≤ 2.0 W (1 / 2 ch.) - low current |
| Max. power dissipation | ≤ 1.7 W (1 ch.) - high current |
| Test/working: Input to any | 2.6 kVAC / 300 VAC reinforced isolation |
| Output 1 to output 2 | 1.5 kVAC / 150 VAC reinforced isolation |
| Status relay to supply | 1.5 kVAC / 150 VAC reinforced isolation |
| Programming | PR 4500 communication interfaces |
| EMC immunity influence | < ±0.5% of span |
| Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
| Trigger level LOW | ≤ 2.0 VDC |
| Trigger level HIGH | ≥ 4.0 VDC |
| Max. external voltage | 28 VDC |
| Input impedance | 3.5 kΩ |
| Trigger level LOW | ≤ 8.0 VDC |
| Trigger level HIGH | ≥ 10.0 VDC |
| Max. external voltage | 28 VDC |
| Input impedance | 3.5 kΩ |
| Max. voltage | 125 VAC / 110 VDC |
| Max. current | 0.5 AAC / 0.3 ADC |
| Max. AC power | 62.5 VA / 32 W |
| Output ripple | < 40 mVRMS |
| EMC | 2014/30/EU & UK SI 2016/1091 |
| LVD | 2014/35/EU & UK SI 2016/1101 |
| ATEX | 2014/34/EU & UK SI 2016/1107 |
| RoHS | 2011/65/EU & UK SI 2012/3032 |
| EAC | TR-CU 020/2011 |
| EAC Ex | TR-CU 012/2011 |
| EAC LVD | TR-CU 004/2011 |
| ATEX | KEMA 07ATEX0147 X |
| IECEx | KEM 09.0001X |
| UKEX | DEKRA 21UKEX0181X DEKRA 23UKEX0106X |
| FM US | FM19US0057X / FM19CA0030X |
| INMETRO | DEKRA 23.0008X |
| UL US, UL 61010-1 | E314307 |
| UL US, UL 913 | E233311 (only 9203xxxx-U9) |
| CCC | 2020322304003423 |
| KCs | 21_AV4BO_0182X / 21_AV4BO_0183X (only 9203Bxxx-KCs) |
| EAC Ex | EAEU KZ 7500361.01.01.08756 |
| DNV Marine | TAA00000JD |
| ClassNK | TA24034M |
| SIL | SIL 2 certified & fully assessed according to IEC 61508 |
Company Details
Business Type:
Manufacturer,Distributor/Wholesaler,Agent,Exporter,Trading Company,Seller
Year Established:
2018
Total Annual:
5000000-10000000
Employee Number:
50~100
Ecer Certification:
Verified Supplier
.gtr-container-def789 { font-family: Verdana, Helvetica, "Times New Roman", Arial, sans-serif; color: #1a1a19; line-height: 1.6; padding: 16px; max-width: 100%; box-sizing: border-box; overflow-wrap: break-word; } .gtr-container-def789 p { font-size: 14px;... .gtr-container-def789 { font-family: Verdana, Helvetica, "Times New Roman", Arial, sans-serif; color: #1a1a19; line-height: 1.6; padding: 16px; max-width: 100%; box-sizing: border-box; overflow-wrap: break-word; } .gtr-container-def789 p { font-size: 14px;...
Get in touch with us
Leave a Message, we will call you back quickly!