China 560V 100Ah High Voltage LiFePO4 Battery Bank With CAN RS485 Interface
China 560V 100Ah High Voltage LiFePO4 Battery Bank With CAN RS485 Interface

  1. China 560V 100Ah High Voltage LiFePO4 Battery Bank With CAN RS485 Interface

560V 100Ah High Voltage LiFePO4 Battery Bank With CAN RS485 Interface

  1. MOQ: 2 Units
  2. Price: Negotiable
  3. Get Latest Price
Delivery Time 10-15 Days for Samples; 30-40 Days for Bulk Production
Electrical Safety Focus High - Voltage Isolation and Controlled Access
Communication Requirement Verified CAN or RS485 Protocol
Local Monitoring Role LCD for Battery - Side Status Checks
System Control Relationship PCS - Directed Energy Conversion
Payment Terms L/C,T/T,Western Union
Protection Coordination BMS with External System Disconnects
Commissioning Method Ten - Module Voltage and Polarity Record
Supply Ability 5000 pcs per month
Technical Approval Package PCS Model , Firmware , Wiring and Protocol
PCS Integration Level Upper - Voltage Modular Battery Platform
Packaging Details Heavy-Duty Wooden Case with Protective Foam
Certification CE , MSDS , UN38.3
Place of Origin China
Model Number BAT-51KWH-51.2V-RM-Q-2
Brand Name Voltertech

View Detail Information

Inquiry by Email Get Latest Price
Chat online Now Ask for best deal
  1. Product Details
  2. Company Details

Product Specification

Delivery Time 10-15 Days for Samples; 30-40 Days for Bulk Production Electrical Safety Focus High - Voltage Isolation and Controlled Access
Communication Requirement Verified CAN or RS485 Protocol Local Monitoring Role LCD for Battery - Side Status Checks
System Control Relationship PCS - Directed Energy Conversion Payment Terms L/C,T/T,Western Union
Protection Coordination BMS with External System Disconnects Commissioning Method Ten - Module Voltage and Polarity Record
Supply Ability 5000 pcs per month Technical Approval Package PCS Model , Firmware , Wiring and Protocol
PCS Integration Level Upper - Voltage Modular Battery Platform Packaging Details Heavy-Duty Wooden Case with Protective Foam
Certification CE , MSDS , UN38.3 Place of Origin China
Model Number BAT-51KWH-51.2V-RM-Q-2 Brand Name Voltertech
High Light High Voltage LiFePO4 Battery Bank ,100Ah LiFePO4 Battery Bank ,560V LiFePO4 Battery Bank

560V 100Ah High Voltage LiFePO4 Battery Bank with CAN RS485 Interface

This 560V 100Ah high voltage LiFePO4 battery bank provides 51.20kWh of nominal energy through ten series-connected rack modules. It is designed for compatible PCS systems where a higher DC battery platform, communication integration and structured electrical commissioning are required.

PCS Voltage Approval

The PCS must support the complete 464–560Vdc operating range. The maximum supported DC voltage must remain suitable for the battery’s upper operating limit, while the minimum value must allow operation at the lower end of the battery range.

The PCS insulation level, DC switching equipment and protective devices must also be selected for the system voltage. Equipment rated for a lower battery platform should not be used without formal approval.

Communication Approval

CAN or RS485 communication may exchange supported battery information with a compatible PCS. The required interface should be confirmed from the PCS documentation.

Communication approval should include:

1. PCS brand and exact model.

2. Firmware or software version.

3. CAN or RS485 battery protocol.

4. Cable connector and pin definition.

A matching connector is not sufficient if the data protocol differs.

Current and Power Coordination

The normal charge and discharge current is 50A, and the maximum is 100A. The project PCS current should be selected according to required power, cable design and the preferred battery operating strategy.

The maximum current is a battery boundary and does not mean that continuous operation at the maximum value is required.

High-voltage output cables, M8 terminals, breakers, fuses, contactors and disconnects must be suitable for the configured current and complete DC voltage.

Ten-Module Commissioning Record

Each module voltage should be recorded before connection. The installation team should then confirm the module order and polarity as the series links are completed.

Before PCS connection, measure the full battery-bank voltage and compare it with the expected value. The system output should remain isolated if the reading is inconsistent.

After electrical checks are complete, verify CAN or RS485 communication, PCS alarms and the available LCD information.

BMS and External Protection Boundaries

The BMS includes overcharge, overdischarge, overcurrent, short-circuit and overtemperature protection. These functions protect the battery within its designed operating boundaries.

External high-voltage protection remains necessary. The project should include suitable isolation, cable protection, disconnect devices and emergency procedures.

A 560V battery system should only be installed and commissioned by qualified personnel using high-voltage procedures appropriate to the site.

560V High Voltage Integration Data

High-Voltage Energy Bank 560V / 100Ah / 51.20kWh
PCS Operating Voltage Range 464–560Vdc
Normal Battery Current 50A Charge / Discharge
Maximum Battery Current 100A Charge / Discharge
Series Battery Modules Ten 51.2V 100Ah Rack Modules
Communication Method CAN / RS485
Battery-Side Display LCD
Protection Coverage Overcharge / Overdischarge / Overcurrent / Short Circuit / Overtemperature
Installation Environment IP20 / -10°C to 50°C / No Condensation / ≤1500m

560V High Voltage Battery FAQ

Can this battery connect to a PCS with a 600V maximum input?

Maximum voltage alone is not sufficient. The PCS minimum voltage, current limits and communication compatibility must also be checked.

Can RS485 communication be configured after installation?

The required interface and protocol should preferably be confirmed before production and commissioning.

Can one module be bypassed if it is unavailable?

No bypass operation should be assumed. Changing the module count changes the complete battery voltage and system configuration.

Does the LCD show all PCS information?

No. It provides supported battery-side information. PCS data depends on the external equipment and communication integration.

What is required before technical approval?

Provide the PCS datasheet, firmware, battery protocol, cable definition, protection design and planned operating current.

560V PCS Integration Approval

Need to verify a 560V battery bank with a specific PCS?

Submit the PCS and Protection Design for Review

Company Details

Bronze Gleitlager

,

Bronze Sleeve Bushings

 and 

Graphite Plugged Bushings

 from Quality China Factory
  • Business Type:

    Manufacturer

  • Year Established:

    15 Years

  • Total Annual:

    5000000-10000000

  • Employee Number:

    50~100

  • Ecer Certification:

    Verified Supplier

About Voltertech Co., Limited Voltertech Co., Limited is a professional provider of energy storage systems and renewable energy solutions, serving distributors, solar installers, EPC contractors, wholesalers, and project developers worldwide. Our product portfolio includes residential energy st... About Voltertech Co., Limited Voltertech Co., Limited is a professional provider of energy storage systems and renewable energy solutions, serving distributors, solar installers, EPC contractors, wholesalers, and project developers worldwide. Our product portfolio includes residential energy st...

+ Read More

Get in touch with us

  • Reach Us
  • Voltertech Co.,Limited
  • Room 2506A, Guangzhou International Finance Centre (IFC), NO.5 Zhujiang West Road ,Tianhe District ,Guangzhou,Guangdong,China
  • https://www.voltertechenergy.com/

Leave a Message, we will call you back quickly!

Email

Check your email

Phone Number

Check your phone number

Requirement Details

Your message must be between 20-3,000 characters!

Submit Requirement